Plan Review Details - Permit 19121025
Plan Review Stops For Permit 19121025
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-02-10 Cont ID  
Sent By cpuell Date 2020-02-10 Time 15:25 Rev Time 0.00
Received By cpuell Date 2020-02-10 Time 15:25 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-03-06 Cont ID  
Sent By pvalenti Date 2020-03-06 Time 09:40 Rev Time 0.00
Received By pvalenti Date 2020-03-06 Time 09:39 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By pvalenti Date 2020-02-26 Time 16:32 Rev Time 0.00
Received By pvalenti Date 2020-02-26 Time 16:32 Sent To  
Notes
2020-02-26 16:38:01***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By pvalenti Date 2020-01-30 Time 14:56 Rev Time 0.00
Received By pvalenti Date 2020-01-30 Time 13:35 Sent To  
Notes
2020-01-30 14:56:55ASBESTOS COMMENTS:
  
 FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-26 Cont ID  
Sent By pvalenti Date 2020-02-26 Time 16:38 Rev Time 0.00
Received By pvalenti Date 2020-02-26 Time 16:38 Sent To  
Notes
2020-02-26 16:42:35 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED:
  
 APPROVED LAND LORD STAMP WAS NOT FOUND. THIS IS NOT
 REQUIRED FOR BUILDING, HOWEVER, THE ZONING DEPARTMENT
 IS REQUESTING THIS APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By pvalenti Date 2020-01-30 Time 14:57 Rev Time 0.00
Received By pvalenti Date 2020-01-30 Time 13:35 Sent To  
Notes
2020-01-30 15:01:50***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE THE PALM BEACH OUTLETS
 MANAGEMENT APPROVAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-22 Cont ID  
Sent By fgiaquin Date 2020-03-22 Time 15:08 Rev Time 0.00
Received By fgiaquin Date 2020-03-21 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-01 Cont ID  
Sent By jpearson Date 2020-03-01 Time 10:36 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 10:36 Sent To I
Notes
2020-03-01 10:36:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROJECTS FOR THE PALM BEACH OUTLETS(PBO) REQUIRE
 APPROVAL BY PBO MANAGEMENT. PROVIDE PLANS STAMPED WITH
 PBO APPROVAL, OR LETTER FROM MANAGEMENT, AND RE-SUBMIT
 FOR REVIEW. WPB FBC 107.2.1 (RESPONSE STATED THE PBO
 MANAGMENT STAMP WAS SUPPLIED WITH NEW PLANS, BUT MOST
 OF THE SHEETS WERE NOT REPLACED. THE ELECTRICAL SHEETS
 WERE REPLACED, BUT THE MANAGEMENT STAMP IS NOT THERE.
 THIS APPROVAL MUST BE ON ALL SHEETS, OR IN LETTER FORM.
 PROVIDE CORRECTION.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-24 Cont ID  
Sent By jpearson Date 2020-01-24 Time 15:49 Rev Time 0.00
Received By jpearson Date 2020-01-24 Time 15:49 Sent To  
Notes
2020-01-24 15:49:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROJECTS FOR THE PALM BEACH OUTLETS(PBO) REQUIRE
 APPROVAL BY PBO MANAGEMENT. PROVIDE PLANS STAMPED WITH
 PBO APPROVAL, OR LETTER FROM MANAGEMENT, AND RE-SUBMIT
 FOR REVIEW. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-16 Cont ID  
Sent By sathomas Date 2020-01-16 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-01-16 Time 00:00 Sent To M
Notes
2020-01-16 14:58:14PROVISO:
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 WHERE REQUIRED, ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 S. THOMAS
 561-804-4728
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-22 Cont ID  
Sent By fgiaquin Date 2020-03-22 Time 15:08 Rev Time 0.00
Received By fgiaquin Date 2020-03-11 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-14 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-03 Cont ID  
Sent By lmarchan Date 2020-02-03 Time 08:08 Rev Time 0.00
Received By lmarchan Date 2020-01-09 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-24 Cont ID  
Sent By ccole Date 2020-02-24 Time 09:25 Rev Time 0.00
Received By ccole Date 2020-02-24 Time 08:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-01-15 Cont ID  
Sent By ccole Date 2020-01-15 Time 16:08 Rev Time 0.00
Received By ccole Date 2020-01-15 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-25 Cont ID  
Sent By shill Date 2020-02-25 Time 12:36 Rev Time 0.00
Received By shill Date 2020-02-21 Time 09:40 Sent To  
Notes
2020-06-10 13:39:03A BOTTLED WATER DISPENSER HAS BEEN INSTALLED. A
 PLUMBING PERMIT IS NOT REQUIRED. T.LARGE. 6/10/2020.
2020-02-25 12:36:39REVIEWED REMOTELY BY TIM HUNT
  
 WATER COOLER MANUFACTURES INSTALLATION MANUAL SHALL BE
 ONSITE FOR THE INSPECTION. A BACKFLOW PROTECTION DEVICE
 IS REQUIRED . FBC-PLB 608.3
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-24 Cont ID  
Sent By gjohnson Date 2020-01-24 Time 17:41 Rev Time 0.00
Received By gjohnson Date 2020-01-24 Time 17:41 Sent To  
Notes
2020-01-24 18:00:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING PLAN SHOWING WATER ISOMETRIC . PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010. PER FBC PL 604.9
  
 3. A BACKFLOW WILL BE REQUIRED FRO WATER COOLER SUPPLY
 LINE. PER FBC PL 608.3
  
 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE FOR WATER COOLER. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-22 Cont ID  
Sent By shill Date 2020-03-22 Time 11:46 Rev Time 0.00
Received By shill Date 2020-03-22 Time 11:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By pvalenti Date 2020-02-26 Time 17:24 Rev Time 0.00
Received By pvalenti Date 2020-02-26 Time 17:24 Sent To  
Notes
2020-02-26 17:26:20***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND SIGNATURE REVIEW DENIED:
  
 PLEASE UPLOAD THE DOCUSIGN SECURED CERTIFICATE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-01-24 Cont ID  
Sent By jpearson Date 2020-01-24 Time 15:46 Rev Time 0.00
Received By jpearson Date 2020-01-24 Time 15:46 Sent To  
Notes
2020-01-24 15:46:21PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE IS NOT
 ACCEPTABLE IF IT STATES THAT IT IS SIGNED BY DOCUSIGN,
 INSTEAD OF THE INDIVIDUALS NAME. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 3 Status P Date 2020-03-19 Cont ID  
Sent By eschneid Date 2020-03-19 Time 16:06 Rev Time 0.25
Received By eschneid Date 2020-03-19 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-02-24 Cont ID  
Sent By eschneid Date 2020-02-24 Time 16:25 Rev Time 0.50
Received By eschneid Date 2020-02-24 Time 15:58 Sent To  
Notes
2020-02-24 16:25:50FAILED
  
 1) REPEAT COMMENT: THE PALM BEACH OUTLETS MANAGEMENT
 APPROVAL OF THE PLANS IS REQUIRED. EITHER PROVIDE THEIR
 STAMP ON THE PLANS OR PROVIDE A LETTER FROM THEM WHICH
 REFERENCES THE SPECIFIC PLAN SHEETS THAT ARE APPROVED.
  
 2) THE PLANS THEMSELVES MEET ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By eschneid Date 2020-01-27 Time 16:35 Rev Time 0.50
Received By eschneid Date 2020-01-27 Time 16:17 Sent To  
Notes
2020-01-27 16:37:24FAILED
  
 1) THE PALM BEACH OUTLETS MANAGEMENT APPROVAL OF THE
 PLANS IS REQUIRED. EITHER PROVIDE THEIR STAMP ON THE
 PLANS OR PROVIDE A LETTER FROM THEM WHICH REFERENCES
 THE SPECIFIC PLAN SHEETS THAT ARE APPROVED.
  
 2) THE PLANS THEMSELVES MEET ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]