Plan Review Details - Permit 19120975
Plan Review Stops For Permit 19120975
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-13 Cont ID  
Sent By lmarchan Date 2020-03-13 Time 13:34 Rev Time 0.00
Received By lmarchan Date 2020-03-10 Time 14:26 Sent To  
Notes
2020-03-10 14:27:05RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-17 Cont ID  
Sent By tklarge Date 2020-01-17 Time 15:22 Rev Time 0.00
Received By tklarge Date 2020-01-14 Time 13:42 Sent To  
Notes
2020-01-15 13:42:50RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-27 Cont ID  
Sent By tklarge Date 2019-12-27 Time 05:05 Rev Time 0.00
Received By tklarge Date 2019-12-23 Time 09:08 Sent To  
Notes
2019-12-24 09:08:57ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-13 Cont ID  
Sent By tklarge Date 2020-03-13 Time 08:49 Rev Time 0.00
Received By tklarge Date 2020-03-13 Time 08:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-01-17 Cont ID  
Sent By tklarge Date 2020-01-17 Time 15:20 Rev Time 0.00
Received By tklarge Date 2020-01-17 Time 15:00 Sent To  
Notes
2020-01-17 15:22:08NOTE:NONE OF THE COMMENTS FROM THE PREVIOUS REVIEW HAVE
 BEENADDRESSED.
  
 1) A REDUCED PRESSURE ZONE (RPZ) BACKFLOW PREVENTION
 DEVICE IS REQUIRED AT THE WATER METER FOR THE
 IRRIGATION SYSTEM PER THE CITY OF WEST PALM
 CROSS-CONNECTION CONTROL MANUAL AS ADOPTED BY CITY
 ORDINANCE.PRESSURE VACUUM BREAKERS ARE ONLY PERMITTED
 TO BE USED ON ONE AND TWO FAMILY DWELLINGS.
 2)THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY
 OF WEST PALM CROSS-CONNECTION CONTROL MANUAL AS ADOPTED
 BY CITY ORDINANCE AND SEC. 605.2 OF THE 2017
 FBC-PLUMBING.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 DEVICE. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 SHALL BE SUBMITTED ALONG WITH A PERMIT APPLICATION
 FORM.
 4) IDENTIFY THE LOCATION OF THE WATER METER ON THE
 PLANS. WPB AMEND. TO FBC SEC.107.2.1. THE BACKFLOW
 DEVICE SHALL BE LOCATED AS CLOSE AS POSSIBLE TO THE
 WATER METER PER THE CITY OF WEST PALM CROSS-CONNECTION
 CONTROL MANUAL AS ADOPTED BY CITY ORDINANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By tklarge Date 2019-12-27 Time 05:04 Rev Time 0.00
Received By tklarge Date 2019-12-27 Time 03:40 Sent To I
Notes
2019-12-27 04:38:101) A REDUCED PRESSURE ZONE (RPZ) BACKFLOW PREVENTION
 DEVICE IS REQUIRED AT THE WATER METER FOR THE
 IRRIGATION SYSTEM PER THE CITY OF WEST PALM
 CROSS-CONNECTION CONTROL MANUAL AS ADOPTED BY CITY
 ORDINANCE.PRESSURE VACUUM BREAKERS ARE ONLY PERMITTED
 TO BE USED ON ONE AND TWO FAMILY DWELLINGS.
 2)THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY
 OF WEST PALM CROSS-CONNECTION CONTROL MANUAL AS ADOPTED
 BY CITY ORDINANCE AND SEC. 605.2 OF THE 2017
 FBC-PLUMBING.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 DEVICE. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 SHALL BE SUBMITTED ALONG WITH A PERMIT APPLICATION
 FORM.
 4) IDENTIFY THE LOCATION OF THE WATER METER ON THE
 PLANS. WPB AMEND. TO FBC SEC.107.2.1. THE BACKFLOW
 DEVICE SHALL BE LOCATED AS CLOSE AS POSSIBLE TO THE
 WATER METER PER THE CITY OF WEST PALM CROSS-CONNECTION
 CONTROL MANUAL AS ADOPTED BY CITY ORDINANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  