Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-27 Cont ID  
Sent By jgomez Date 2020-02-27 Time 10:20 Rev Time 0.00
Received By jgomez Date 2020-02-27 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-19 Cont ID  
Sent By jgomez Date 2020-02-19 Time 17:57 Rev Time 0.00
Received By jgomez Date 2020-02-19 Time 15:23 Sent To  
Notes
2020-02-19 18:00:01RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)OK
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME,
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 C) PROVIDE CORRECT INFORMATION ON ITEM #1 ON PAGE 1 OF
 4. THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING
 HOUSE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 D) REVISE COOLING INFORMATION ON ITEM #12 ON PAGE 1 OF
 4 TO MATCH PLANS AND COOLING EQUIPMENT INFORMATION
 SUBMITTED. THE SEER OF THIS EQUIPMENT IS 14.50 NOT 16.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 IT IS NOT CLEAR HOW THE SEER OF THE EQUIPMENT WAS
 CHANGED. PAGE 1 OF 4 SHOWS 14.5 SEER BUT THE FINAL
 RESULTS DIDN'T CHANGE. THE TOTAL PROPOSED MODIFIED
 LOADS (36.27) AND THE TOTAL BASELINE LOADS (40.62)
 STAYED THE SAME AS THE OLD ENERGY CALCULATIONS THAT
 WERE SUBMITTED EARLIER. THIS IS A COMPUTER GENERATED
 PROGRAM. ANY CHANGES WILL RESULT IN CHANGES ON THE
 FINAL OUTPUT. CLARIFY/REVISE AS REQUIRED. ORIGINAL
 COMPUTER GENERATED ENERGY CALCULATIONS NEED TO BE
 REVISED. (NOTE: OWNER TOOK ONE COPY OF THE OLD ENERGY
 CALCULATIONS AND THE NEW ENERGY CALCULATIONS THAT WERE
 RESUBMITTED TO TAKE BACK TO THE PERSON WHO DID THE
 ENERGY CALCULATIONS).
 IN ADDITION, AFTER TALKING TO THE MR. BARIS (OWNER) WE
 FOUND OUT THAT THE EQUIPMENT SIZE SHOWN ON THE ENERGY
 CALCULATIONS (1-1/2 TON.) DOESN'T MATCH THE EQUIPMENT
 SIZE SHOWN ON THE A/C PLAN (3.5 TON). REVISE AS
 REQUIRED TO MATCH TO AVOID CONFLICTS/DELAYS.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 E) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NOT 3 EXTERIOR DOORS. SEE PROPOSED PLAN AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 F) WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THE
 WINDOWS FRAME IS PVC NOT METAL. SEE WINDOW SCHEDULE ON
 ENGINEERED DRAWING 2.0 AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED. ALSO, REVISE WINDOW AREAS TO
 MATCH PLANS. NOTE: COORDINATE WITH DOOR INFORMATION
 COMMENT #1(E) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 2- SPECIFY THE SIZE AND TYPE OF EXISTING WINDOW AND
 SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 RESPONSE:
 THIS IS OK. SEE CURRENT PERMIT #19100358 FOR WINDOW
 REPLACEMENT. INSPECTIONS FOR WINDOWS ARE CURRENTLY DONE
 UNDER THIS PERMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-17 Cont ID  
Sent By jgomez Date 2020-01-17 Time 17:40 Rev Time 0.00
Received By jgomez Date 2020-01-17 Time 17:39 Sent To  
Notes
2020-01-17 17:42:58RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME,
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE CORRECT INFORMATION ON ITEM #1 ON PAGE 1 OF
 4. THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING
 HOUSE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE COOLING INFORMATION ON ITEM #12 ON PAGE 1 OF
 4 TO MATCH PLANS AND COOLING EQUIPMENT INFORMATION
 SUBMITTED. THE SEER OF THIS EQUIPMENT IS 14.50 NOT 16.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NOT 3 EXTERIOR DOORS. SEE PROPOSED PLAN AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THE
 WINDOWS FRAME IS PVC NOT METAL. SEE WINDOW SCHEDULE ON
 ENGINEERED DRAWING 2.0 AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED. ALSO, REVISE WINDOW AREAS TO
 MATCH PLANS. NOTE: COORDINATE WITH DOOR INFORMATION
 COMMENT #1(E) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
  
 2- SPECIFY THE SIZE AND TYPE OF EXISTING WINDOW AND
 SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5 FBC-EXISTING BUILDING.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-25 Cont ID  
Sent By jpearson Date 2020-02-25 Time 09:58 Rev Time 0.00
Received By jpearson Date 2020-02-25 Time 09:58 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-02 Cont ID  
Sent By jpearson Date 2020-01-02 Time 15:53 Rev Time 0.00
Received By jpearson Date 2020-01-02 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-27 Cont ID  
Sent By jgomez Date 2020-02-27 Time 10:31 Rev Time 0.00
Received By jgomez Date 2020-02-27 Time 09:44 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-02-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-11 Time 13:59 Sent To  
Notes
2020-02-12 13:59:09R37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-17 Cont ID  
Sent By jgomez Date 2020-01-17 Time 17:43 Rev Time 0.00
Received By jgomez Date 2019-12-23 Time 09:43 Sent To I
Notes
2019-12-24 09:43:56R37

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-26 Cont ID  
Sent By ccole Date 2020-02-26 Time 15:34 Rev Time 0.00
Received By ccole Date 2020-02-13 Time 15:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-16 Cont ID  
Sent By ccole Date 2020-01-16 Time 14:19 Rev Time 0.00
Received By ccole Date 2020-01-16 Time 13:10 Sent To  
Notes
2020-01-16 14:50:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120949
 1/16/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OWNER/AGENT SHALL SIGN AND DATE THE ENERGY
 EFFICIENCY COMPLIANCE FORM R405-2017- SECTION
 R103.1.1.2 FBC EC.
  
 2) PROVIDE PRODUCT DATA SHEETS FOR THE NEW WINDOWS TO
 VERIFY THE U-FACTOR AND 0.25 SHGC VALUES LISTED ON THE
 ENERGY FORM- R405.3 FBC EC.
  
 3) R30 UNDER ATTIC INSULATION IS SHOWN ON THE ENERGY
 FORM. PLEASE PROVIDE A SECTION DRAWING OR NOTE OR THE
 PLAN TO VERIFY COMPLIANCE- SECTION R405.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By lcrespo Date 2020-02-14 Time 06:13 Rev Time 0.00
Received By lcrespo Date 2020-02-14 Time 06:13 Sent To  
Notes
2020-02-14 06:39:3502/14/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-02 Cont ID  
Sent By lcrespo Date 2020-01-02 Time 10:13 Rev Time 0.00
Received By lcrespo Date 2020-01-02 Time 07:27 Sent To  
Notes
2020-01-02 10:14:1701/02/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By awooten Date 2020-01-07 Time   Rev Time  
Received By   Date 2020-01-07 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved