Plan Review Details - Permit 19120885
Plan Review Stops For Permit 19120885
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-06 Cont ID  
Sent By rmcphers Date 2020-05-06 Time 10:06 Rev Time 0.00
Received By rmcphers Date 2020-05-06 Time 08:10 Sent To  
Notes
2020-05-06 10:00:09SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) EXTERIOR WALL CANNOT BE BUILT CODE PRESCRIPTIVE PER
 FBC R301.2.1.1
 2) PLEASE PROVIDE DIGITALLY SIGNED AND SEALED EXTERIOR
 WALL DRAWINGS FROM AN ARCHITECT OR ENGINEER TO COMPLY
 WITH WIND LOADS PER FBC 1609.1.1
 3) PLEASE SHOW THE WIND DESIGN DATA USED PER FBC
 1603.1.4
 4) WALL DETAILS SHOWN ON THE DRAWING (2 OF 4) IS
 MISSING - BEAM SIZE, STRAPPING TYPE NAME - NUMBER OF
 NAILS - SIZE OF NAILS, - IS THE ROOF EXISTING? - IF SO
 PLEASE STATE AS SUCH ON THE DRAWING.
 5) PLEASE PROVIDE MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVALS FOR THE ROOFING - SHOWN ON THE DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jgomez Date 2020-01-07 Time 18:03 Rev Time 0.00
Received By jgomez Date 2020-01-07 Time 11:36 Sent To HIST
Notes
2020-01-07 18:09:17RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- PLANS SUBMITTED SHOW A DINING ROOM AND BEDROOM #2 ON
 THE REAR OF THE MAIN HOUSE. ACCORDING TO CITY RECORDS
 AND PROPERTY APPRAISER THIS AREA WAS A PORCH NOT
 LIVABLE SPACE.
 THERE ARE NO CITY RECORDS SHOWING PERMITS FOR THE
 CONVERSION OF THE PORCH TO LIVABLE SPACE. IT LOOKS LIKE
 THE WORK WAS DONE WITHOUT PERMITS AND INSPECTIONS. NEED
 TO REVISE PLANS TO SHOW THE ENCLOSURE OF THE PORCH TO
 INCREASE THE LIVABLE SPACE. PROVIDE COMPLETE
 INFORMATION, INCLUDING DIMENSIONS FOR THE ROOMS AND
 FRAMING DETAILS FOR THE DOORS AND WINDOWS. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. 801.3 FBC-EXISTING
 BUILDING AND SEC. R301.2.1 FBC-RESIDENTIAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- WINDOW SIZE FOR NEW BEDROOM #2 DOESN'T COMPLY WITH
 THE EGRESS REQUIREMENTS. REVISE AS REQUIRED SHOWING
 COMPLIANCE. SEC. 801.3 FBC-EXISTING BUILDING AND SEC.
 R310.2.1 FBC-RESIDENTIAL.
  
 3- WINDOW REPLACEMENT ON THE REST OF THE HOUSE: CLEARLY
 SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND TYPE AND
 SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5 FBC-EXISTING BUILDING.
  
 4- SHUTTERS FLORIDA PRODUCT APPROVAL FL11398-R4
 SUBMITTED: PROVIDE COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- IMPACT FEES: BECAUSE OF THE LIVABLE AREA ADDITION
 THE PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-22 Cont ID  
Sent By jpearson Date 2020-04-22 Time 08:36 Rev Time 0.00
Received By jpearson Date 2020-04-22 Time 07:18 Sent To  
Notes
2020-04-22 08:13:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. LOAD CALCULATION PROVIDED EXCEEDS THE CAPACITY OF
 THE SERVICE AND THE NEW PANEL SPECIFIED ON RISER
 DIAGRAM. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THIS LOAD CALCULATION SHOULD BE IN
 THE FORMAT SPECIFIED IN THE FBC RESIDENTIAL. NEC 215.2,
 220, 408.30; FBC RE E3602.2 (NOT PROVIDED OR
 CORRECTED.)
 2. PROVIDE CORRECTIONS TO ANY SERVICE EQUIPMENT THAT IS
 UNDERSIZED. NEC 110.3, 215.2, 240.4, 408.30 (NOT
 CORRECTED. MAIN BREAKER IN RISER STILL SHOWS AS 100
 AMP.)
 3. IF SERVICE IS TO BE UPGRADED, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT
 PROVIDED OR ADDRESSED.)
 4. CORRECTED.
 5. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-30 Cont ID  
Sent By jpearson Date 2019-12-30 Time 11:04 Rev Time 0.00
Received By jpearson Date 2019-12-30 Time 08:33 Sent To  
Notes
2019-12-30 08:47:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION PROVIDED EXCEEDS THE CAPACITY OF
 THE SERVICE AND THE NEW PANEL SPECIFIED ON RISER
 DIAGRAM. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THIS LOAD CALCULATION SHOULD BE IN
 THE FORMAT SPECIFIED IN THE FBC RESIDENTIAL. NEC 215.2,
 220, 408.30; FBC RE E3602.2
 2. PROVIDE CORRECTIONS TO ANY SERVICE EQUIPMENT THAT IS
 UNDERSIZED. NEC 110.3, 215.2, 240.4, 408.30
 3. IF SERVICE IS TO BE UPGRADED, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-04-27 Cont ID  
Sent By aborngra Date 2020-04-27 Time 12:48 Rev Time 0.00
Received By aborngra Date 2020-04-27 Time 12:47 Sent To  
Notes
2020-04-27 12:47:59EXTERNAL DIMENSIONAL MUNTINS WITH A LOW FLAT PROFILE OR
 PYRAMID.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By jgomez Date 2020-01-07 Time 18:09 Rev Time 0.00
Received By aborngra Date 2020-01-08 Time 15:13 Sent To PC
Notes
2020-01-08 15:15:14THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. PLEASE FOLLOW THE WPB-HP WINDOW PERMIT APPLICATION
 EXAMPLE.PDF EXAMPLE FOR BOTH THE WINDOWS AND DOORS.
 THIS DOCUMENT CAN BE OBTAINED BY EMAILING
 [email protected]. I HAVE ALSO INCLUDED A COPY WITH
 THE PERMIT. YOUR RESUBMITTAL SHOULD INCLUDE PHOTOS
 IDENTIFYING THE EXISTING WINDOWS, AND PROPOSED WINDOWS.
  
 A. SINGLE-HUNG WINDOWS SHOULD MATCH THE AWNING WINDOW
 CONFIGURATION WITH EXTERNAL DIMENSIONAL MUNTINS IN
 EITHER A PYRAMID OR LOW FLAT PROFILE.
 B. ALL FRONT ELEVATION WINDOWS (AND DOORS) NEED TO HAVE
 CLEAR GLASS.
 C. ALL REMAINING ELEVATIONS CAN HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 D. ALL WINDOWS AND THE SLIDING GLASS DOOR SHOULD HAVE
 AN ANODIZED FINISH.
  
 2. PROVIDE A PHOTO OF THE EXISTING DOORS AND PROVIDE A
 GRAPHIC OF WHAT THE PROPOSED DOORS WILL LOOK LIKE.
  
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  
2020-01-07 15:50:56***NOTE:
 THIS BUILDINGS WERE NOT FLAGGED AS HISTORIC AND ARE
 CONTRIBUTING HISTORIC BUILDINGS. ADDED HISTORIC HOLD.
 UNFORTUNATELY ROOF TILE WAS REPLACED IN 1998 AND 2004
 WITH SHINGLES WITHOUT HISTORICAL REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-06 Cont ID  
Sent By rmcphers Date 2020-05-06 Time 10:21 Rev Time 0.00
Received By rmcphers Date 2020-04-14 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-08 Cont ID  
Sent By lmarchan Date 2020-01-08 Time 16:16 Rev Time 0.00
Received By lmarchan Date 2019-12-19 Time 13:37 Sent To  
Notes
2019-12-20 13:38:03R34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-05-06 Cont ID  
Sent By rmcphers Date 2020-05-06 Time 10:06 Rev Time 0.00
Received By rmcphers Date 2020-05-06 Time 10:06 Sent To  
Notes
2020-05-06 10:21:32PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jgomez Date 2020-01-07 Time 16:38 Rev Time 0.00
Received By jgomez Date 2020-01-07 Time 16:38 Sent To  
Notes
2020-01-07 16:39:10IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-05 Cont ID  
Sent By ccole Date 2020-05-05 Time 12:04 Rev Time 0.00
Received By ccole Date 2020-04-29 Time 16:40 Sent To  
Notes
2020-05-05 12:20:17 
 3RD REVIEW FBC-2017 PLUMBING
 PERMIT #19120885
 5/5/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A PRODUCT DATA SHEET HAS BEEN SUBMITTED FOR A NEW
 28-GALLON ELECTRIC WATER HEATER HOWEVER THE PLANS SHOW
 ALL EXISTING WATER HEATERS. PLEASE SHOW THE LOCATION OF
 THE NEW WATER HEATER AND ADD IT TO THE THE PLUMBING
 SCOPE OF WORK ON SHEET 1- SECTION 107.2.1 WPB. PLEASE
 NOTE THAT A THERMAL EXPANSION DEVICE IS REQUIRED TO BE
 INSTALLED AT THE SUPPLY LINE TO THE WATER HEATER PER
 SECTION P2903.4 FBC RES.
  
 2) TWO DWELLING UNITS ARE SHOWN TO BE OR THE SAME LOT
 WHICH REQJUIRES INSTALLATION OF AN RPZ-TYPE BACKFLOW
 PREVENTER TO BE INSTALLED AT THE WATER METER ACCORDING
 TO THE CITY OF WPB CROSS-CONNECTION MANUAL. A SEPARATE
 PERMIT IS REQUIRED FOR THE INSTALLATION. PLEASE CONTACT
 THE THE CITY OF WPB UTILITIES DEPT. AT 561-822-2240 FOR
 MORE INFORMATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
2020-04-30 15:33:0704/30/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-02 Cont ID  
Sent By lcrespo Date 2020-01-02 Time 06:55 Rev Time 0.00
Received By lcrespo Date 2020-01-02 Time 06:23 Sent To  
Notes
2020-01-02 06:56:2801/02/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-04-17 Cont ID  
Sent By jgomez Date 2020-04-17 Time 15:09 Rev Time 0.00
Received By jgomez Date 2020-04-17 Time 15:09 Sent To  
Notes
2020-04-17 15:09:50NO LICENSED ARCHITECT/ENGINEER PLANS. JG.