Plan Review Details - Permit 19120840
Plan Review Stops For Permit 19120840
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-12-19 Cont ID  
Sent By pvalenti Date 2019-12-19 Time 16:23 Rev Time 0.00
Received By pvalenti Date 2019-12-19 Time 16:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-24 Cont ID  
Sent By pleduc Date 2019-12-23 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-12-24 Time 00:00 Sent To  
Notes
2019-12-24 14:07:31PROVISO:
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY
 MATERIAL.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-10 Cont ID  
Sent By shill Date 2020-02-10 Time 08:11 Rev Time 0.00
Received By shill Date 2019-12-18 Time 16:38 Sent To  
Notes
***NONE***