Plan Review Details - Permit 19120825
Plan Review Stops For Permit 19120825
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 13:48 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By pleduc Date 2020-01-07 Time   Rev Time 0.00
Received By pleduc Date 2020-01-07 Time 13:24 Sent To I
Notes
2020-01-07 13:29:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A DDCV AND UNDERGROUND
 FIRE LINE WORK
  
 ALL FIRE LINE UNDERGROUND SHALL BE SUBMITTED
 UNDERPARATE PERMIT AND SHOP DRAWINGS AND COMPLY WITH
 NFPA 24.
  
 THE WORK SHALL BE COMPLETED BY A CERTIFIED STATE OF
 FLORIDA UNDERGROUND CONTRACTOR.
  
 PLEASE REVIEW AND COMPLY.
  
  
  
 2) THERE ARE NO INDICATION OF THE TYPE OF COMMODITY
 BEING PROTECTED, TYPE OF PALLETS, WRAPPINGS, STORAGE
 HEIGHT, ETC.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-04 Cont ID  
Sent By lmarchan Date 2020-03-04 Time 15:44 Rev Time 0.00
Received By lmarchan Date 2020-02-27 Time 13:14 Sent To  
Notes
2020-02-28 13:14:12RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-07 Cont ID  
Sent By cpuell Date 2020-01-07 Time 14:23 Rev Time 0.00
Received By cpuell Date 2019-12-18 Time 14:24 Sent To  
Notes
2019-12-19 14:25:06ROUTED TO FIRE INBOX