Plan Review Details - Permit 19120806
Plan Review Stops For Permit 19120806
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-03-09 Cont ID  
Sent By shill Date 2020-03-09 Time 14:22 Rev Time 0.00
Received By shill Date 2020-03-09 Time 14:22 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-03-07 Cont ID  
Sent By shill Date 2020-03-07 Time 10:18 Rev Time 0.00
Received By shill Date 2020-03-07 Time 10:18 Sent To  
Notes
2020-03-07 10:18:51A LETTER WAS UPLOADED BUT LACKS THE LANGUAGE REQUIRED,
 SEE BELOW. LETTER IS TO ONLY ACKNOWLEDGE THAT
 CONTRACTOR WILL FOLLOW THE INSTRUCTIONS ON THE WEBSITE.
 PLEASE EMAIL THE ACKNOWLEDGEMENT WITH THE FOLLOWING
 LANGUAGE TO [email protected].
  
  
 ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By jwitmer Date 2020-01-22 Time 14:41 Rev Time  
Received By jwitmer Date 2020-01-22 Time   Sent To  
Notes
2020-01-22 14:41:22ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-07 Cont ID  
Sent By shill Date 2020-03-07 Time 10:17 Rev Time 0.00
Received By shill Date 2020-03-07 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By jwitmer Date 2020-01-22 Time 14:54 Rev Time 0.00
Received By jwitmer Date 2020-01-22 Time 14:20 Sent To  
Notes
2020-01-22 14:53:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120806
 ADD: 460 S ROSEMARY AVE. SUITE: 186
 CONT: SOUTH FLORIDA CONSTRUCTION GROUP
 TEL: 954-782-1260
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 22/2020
 ACTION: DENIED
  
 1) SHEET S0.00 GENERAL NOTES UNDER THE HEADING OF WIND
 DESIGN THE PROVIDED PRESSURES ARE IN VULT. PLEASE
 CONVERT THEM TO VASD SINCE THE PRODUCT APPROVALS ARE
 ALL IN VASD. IT DOES APPEAR THE PRESSURES ARE GOOD FOR
 WALL ZONES 4 & 5 AND ROOF ZONES 1, 2 & 3. THANK YOU.
 2017 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-29 Cont ID  
Sent By jleahy Date 2020-01-29 Time 16:41 Rev Time 0.00
Received By jleahy Date 2020-01-29 Time 16:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-09 Cont ID  
Sent By pleduc Date 2020-03-09 Time   Rev Time 0.00
Received By pleduc Date 2020-03-09 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-03 Cont ID  
Sent By pleduc Date 2020-01-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-03 Time 09:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-03-12 Cont ID  
Sent By tklarge Date 2020-03-12 Time 11:09 Rev Time 0.00
Received By tklarge Date 2020-03-12 Time 11:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By tklarge Date 2020-03-11 Time 08:15 Rev Time 0.00
Received By tklarge Date 2020-03-11 Time 08:04 Sent To  
Notes
2020-03-11 08:15:241) SHT. P1.3 - COMBUSTION AIR CALCULATIONS - THE MAKEUP
 AIR FOR THE HOOD SYSTEM CANNOT BE USED FOR COMBUSTION
 AIR FOR THE GAS FRYER PER THE 0217 FBC-FUEL GAS SEC.
 304.4 THE AIR FOR THE HOOD IS DEDICATED FOR THE HOOD.
 COMPLY WITH 2017 FBC-FUEL GAS SEC.304.1 AND PROVIDE
 COMBUSTION AIR FOR THE FRYER IN ACCORDANCE WITH THIS
 SECTION.
 2) REGULATORS SHALL BE INSTALLED ON THE TANKLESS WATER
 HEATERS IF THE GAS PRESSURE TO THE HEATERS EXCEEDS 10.5
 INCHES WATER COLUMN. SEE WATER HEATER SPECIFICATIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By tklarge Date 2020-01-29 Time 13:08 Rev Time 0.00
Received By tklarge Date 2020-01-29 Time 12:44 Sent To  
Notes
2020-01-29 13:08:541) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE FLOOR
 FRYER. 2017 FBC-FUEL GAS SEC. 304.1. WHERE COMBUSTION
 AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS
 SEC.304.9.3.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3.GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1,
 3) SHT. P1.3 - SUBMIT A LEGEND FOR THE IDENTIFIERS G/1,
 G/2 G/3, ETC.WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE MINIMUM SIZE PIPE TO THE GAS WATER HEATERS AT 45
 FEET DEVELOPED LENGTH IS 1 1/4 INCHES BASED ON TABLE
 402.4 (2). A MAXIMUM OF 284 MBTU CAN BE INSTALLED ON A
 ONE INCH LINE.
 5) THE MINIMUM SIZE PIPE TO THE LAST GAS WATER HEATERS
 AT 45 FEET DEVELOPED LENGTH IS 1 INCH BASED ON TABLE
 402.4 (2). A MAXIMUM OF 151 MBTU CAN BE INSTALLED ON A
 ONE INCH LINE.
 6) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC. 410.2 (7).
 7) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. NFPA
 96-14. SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1.
 8) VENTS SHALL COMPLY WITH THE INSTALLATION MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-11 Cont ID  
Sent By lmarchan Date 2020-03-11 Time 08:43 Rev Time 0.00
Received By lmarchan Date 2020-03-02 Time 10:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-19 Cont ID  
Sent By lmarchan Date 2020-02-19 Time 09:31 Rev Time 0.00
Received By lmarchan Date 2019-12-30 Time 12:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-01-22 Cont ID  
Sent By jwitmer Date 2020-01-22 Time 14:41 Rev Time  
Received By jwitmer Date 2020-01-22 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-02-05 Cont ID  
Sent By ccole Date 2020-02-04 Time 10:57 Rev Time 0.00
Received By ccole Date 2020-02-03 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By tklarge Date 2020-03-11 Time 08:00 Rev Time 0.00
Received By tklarge Date 2020-03-11 Time 05:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By tklarge Date 2020-01-29 Time 12:43 Rev Time 0.00
Received By tklarge Date 2020-01-28 Time 14:28 Sent To  
Notes
2020-01-29 09:33:231) THE ARCHITECTURAL PLANS ARE REQUIRED TO BE
 ELECTRONICALLY SIGNED AND SEALED PER FL. ADMIN. CODE
 RULE 61G1-16.005.
 2) SUBMIT A KITCHEN EQUIPMENT SCHEDULE FOR THE KITCHEN
 EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1.
 3) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE
 RESTROOMS. ALL OTHER SINKS SHALL HAVE HOT WATER. THE
 PLUMBING FIXTURE CONNECTION SCHEDULE CALLS OUT THE
 TEMPERING DEVICES FOR THE LAVATORIES. 2017 FBC-PLUMBING
 SEC.416.5.
 4) THE EXISTING CONCRETE GREASE INTERCEPTOR SHALL BE
 PUMPED OUT AND INSPECTED FOR INTEGRITY BY THE PLUMBING
 INSPECTOR. 2017 FBC SEC. 1003.10.
 5) THE HOT WATER RECIRCULATION LINE SHALL BE INSULATED
 WITH A MINIMUM OF 1 INCH THICK INSULATION PER THE 2017
 FBC- ENERGY SEC.C403.2.10.
 6) THE SANITARY RISER DIAGRAM SHOWS CONDENSATE LINES
 AND ICEMAKERS DISCHARGING INTO THE GREASY WASTER
 SYSTEM. WASTES THAT DO NOT REQUIRE SEPARATION SHALL NOT
 DISCHARGE TO GREASE INTERCEPTOR.
 7) SHT. P2.1 - SHOW THE SIZE OF THE THERMAL EXPANSION
 TANK ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-07 Cont ID  
Sent By shill Date 2020-03-07 Time 10:13 Rev Time 0.00
Received By shill Date 2020-03-03 Time 12:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-02-10 Cont ID  
Sent By shill Date 2020-02-10 Time 17:21 Rev Time 0.00
Received By shill Date 2020-02-10 Time 17:19 Sent To  
Notes
2020-02-10 17:21:17SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ARCH PAGES ARE NOT DIGITALLY SIGNED, FS481.
  
 2. S, MEP OK
  
  
  
2020-01-29 12:49:31THE ARCHITECTURAL PLANS ARE REQUIRED TO BE
 ELECTRONICALLY SIGNED AND SEALED PER FL. ADMIN. CODE
 RULE 61G1-16.005. T. LARGE.
2020-01-22 14:55:57ARCHITECTURAL SHEETS ARE NOT ELECTRONICALLY SIGNED AND
 SEALED. 61G15-23.003 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS. 01/22/2020 JW

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By elevesqu Date 2020-03-10 Time 10:48 Rev Time 0.00
Received By elevesqu Date 2020-03-10 Time 10:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-19 Cont ID  
Sent By aaponte Date 2020-02-19 Time 09:22 Rev Time 0.00
Received By elevesqu Date 2020-02-19 Time 09:22 Sent To  
Notes
***NONE***