Plan Review Details - Permit 19120794
Plan Review Stops For Permit 19120794
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-03-04 Cont ID  
Sent By pvalenti Date 2020-03-04 Time 16:59 Rev Time 0.00
Received By pvalenti Date 2020-03-04 Time 16:59 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By jgomez Date 2020-01-30 Time 17:16 Rev Time 0.00
Received By jgomez Date 2020-01-30 Time 17:16 Sent To  
Notes
2020-01-30 17:16:20PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 16:02 Rev Time 0.00
Received By jgomez Date 2020-03-26 Time 11:24 Sent To  
Notes
2020-03-26 14:57:37 
 03/10/2020 TALKED TO DWAYNE (CONTRACTOR). HE AGREED TO
 APPROVE BUILDING REVIEW WITH PROVISO. JG.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTION TO AVOID CONFLICTS/DELAYS):
  
 1- PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90.
 2- PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492.
 3- PROVIDE COMPLETE PRODUCT APPROVAL FOR OUTSIDE
 ELECTRICAL CLOSET. INCLUDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE.
 4- DESIGNER OF RECORD TO APPROVE PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-10 Cont ID  
Sent By jgomez Date 2020-03-10 Time 09:13 Rev Time 0.00
Received By jgomez Date 2020-03-10 Time 09:09 Sent To P
Notes
2020-03-10 09:11:5703/10/2020 TALKED TO DWAYNE (CONTRACTOR). HE AGREED TO
 APPROVE BUILDING REVIEW WITH PROVISO. JG.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTION TO AVOID CONFLICTS/DELAYS):
  
 1- PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90.
 2- PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492.
 3- PROVIDE COMPLETE PRODUCT APPROVAL FOR OUTSIDE
 ELECTRICAL CLOSET. INCLUDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE.
 4- DESIGNER OF RECORD TO APPROVE PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-09 Cont ID  
Sent By jgomez Date 2020-03-09 Time 18:27 Rev Time 0.00
Received By jgomez Date 2020-03-09 Time 17:40 Sent To  
Notes
2020-03-09 18:27:52RESIDENTIAL (R2) SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- PLANS CALL FOR INSTALLATION OF TILE IN KITCHENS AND
 BATHROOMS. NEED TO PROVIDE SOUND INSULATION ON SECOND
 FLOOR UNITS WHERE WORK IS PERFORMED. SEC. 702.6
 FBC-EXISTING BUILDING AND SEC. 1207 FBC-BUILDING.
 PLEASE PROVIDE THE FOLLOWING:
  
 A) OK
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT PROVIDED.
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT PROVIDED.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH.
  
  
 ORIGINAL COMMENT:
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE PAIR OF EXTERIOR DOOR TO BE
 REPLACED AS SPECIFIED ON OUTSIDE OF UNIT #4 ON FIRST
 FLOOR PLAN ON SHEET A-1.
  
 RESPONSE:
 DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED TO
 PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL (2 COPIES),
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA
 PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF
 PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By jgomez Date 2020-01-30 Time 17:34 Rev Time 0.00
Received By jgomez Date 2020-01-30 Time 15:18 Sent To  
Notes
2020-01-30 17:35:18RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- PLANS CALL FOR INSTALLATION OF TILE IN KITCHENS AND
 BATHROOMS. NEED TO PROVIDE SOUND INSULATION ON SECOND
 FLOOR UNITS WHERE WORK IS PERFORMED. SEC. 702.6
 FBC-EXISTING BUILDING AND SEC. 1207 FBC-BUILDING.
 PLEASE PROVIDE THE FOLLOWING:
  
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE PAIR OF EXTERIOR DOOR TO BE
 REPLACED AS SPECIFIED ON OUTSIDE OF UNIT #4 ON FIRST
 FLOOR PLAN ON SHEET A-1.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COPY OF SIGNED CONTRACTS INCLUDING DESIGN
 PROFESSIONAL FEES.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-03 Cont ID  
Sent By jleahy Date 2020-03-03 Time 12:48 Rev Time 0.00
Received By jleahy Date 2020-03-03 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-23 Cont ID  
Sent By jpearson Date 2020-01-23 Time 15:06 Rev Time 0.00
Received By jpearson Date 2020-01-23 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-03-23 Cont ID  
Sent By pleduc Date 2020-03-23 Time   Rev Time 0.00
Received By pleduc Date 2020-03-23 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By pleduc Date 2020-02-14 Time   Rev Time 0.00
Received By pleduc Date 2020-02-14 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-03 Cont ID  
Sent By pleduc Date 2020-01-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-03 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 16:31 Rev Time 0.00
Received By jgomez Date 2020-03-20 Time 16:19 Sent To I
Notes
2020-03-20 16:19:37C10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-12 Cont ID  
Sent By jesmith Date 2020-03-12 Time 11:12 Rev Time 0.00
Received By jesmith Date 2020-03-12 Time 11:12 Sent To  
Notes
2020-02-12 14:25:58C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-30 Cont ID  
Sent By jgomez Date 2020-01-30 Time 17:35 Rev Time 0.00
Received By jgomez Date 2019-12-18 Time 14:37 Sent To I
Notes
2019-12-19 14:37:07C10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 15:59 Rev Time 0.00
Received By jgomez Date 2020-03-26 Time 14:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-02 Cont ID  
Sent By ccole Date 2020-03-02 Time 09:06 Rev Time 0.00
Received By ccole Date 2020-03-02 Time 08:55 Sent To  
Notes
2020-03-02 09:09:09 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-15 Cont ID  
Sent By ccole Date 2020-01-15 Time 14:21 Rev Time 0.00
Received By ccole Date 2020-01-15 Time 11:45 Sent To  
Notes
2020-01-15 14:30:04 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120794
 1/15/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED. PLEASE
 CLARIFY IF ANY ALTERATIONS TO THE EXISTING HVAC SYSTEMS
 ARE PROPOSED INCLUDING KITCHEN AND BATTH EXHAUST
 SYSTEMS, AC SYSTEM REPLACEMENTS, OR DUCT ALTETRATIONS-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT MECHANICAL
 EXHAUST IS REQUIRED FOR THE BATHS AT AN INTERMITTENT
 RATE OF 50 CFMS, AND FOR THE KITCHENS AT AN
 INTERMITTENT RATE OF 100 CFMS- TABLE 403.3.1.1 FBC M.
  
 2) SUBMIT PRODUCT DATA SHEETS FOR ALL NEW KITCHEN
 APPLIANCES AND EXHAUST SYSTEMS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-26 Cont ID  
Sent By jgomez Date 2020-03-26 Time 16:02 Rev Time 0.00
Received By jgomez Date 2020-03-26 Time 14:56 Sent To  
Notes
2020-03-26 16:11:05PROVISO:
 1-NEW PLUMBING AND FIXTURES IN ALL UNITS. COMPLY WITH
 FBC PL 424.3. PROVIDE SHOWER AND TUB/SHOWER ANTI SCALD
 VALVES CONFORMING TO ASME A112.18/CSA B125.1.

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jesmith Date 2020-03-12 Time 11:07 Rev Time 0.00
Received By jesmith Date 2020-03-12 Time 09:37 Sent To  
Notes
2020-03-12 11:05:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. SECOND REQUEST. PLAN SHEET A-1: SCOPE OF WORK; NOTE
 8 CALLS FOR REMOVAL OF BATHTUBS AND REPLACE WITH
 SHOWERS. THIS IS REINFORCED BY THE ENLARGED FLOOR PLANS
 AND ELEVATION PLANS ON PLAN SHEET A-3. PLAN SHEETS A-1,
 E-1, P-1, P-2 AND P-3 INDICATE SOME UNITS WITH SHOWERS
 AND SOME WITH BATHTUBS. PER WPB FBC 107.2.1, CLARIFY
 AND RECONCILE ALL PLANS. SEE SCOPE OF WORK NOTE 8. ADD
 VERBAGE "AS INDICATED ON PLAN"
 2. SECOND REQUEST. VALUE OF WORK APPEARS TO BE LOW. PER
 WPB FBC 109.3, PROVIDE DETAILED QUANTITY ESTIMATES
 AND/OR BONA FIDE SIGNED CONTRACTS TO MEET THE BUILDING
 OFFICIALS APPROVAL. VALUATION SHALL BE FOR THE TOTAL
 REPLACEMENT VALUE OF STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISHES, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES.
 3. PLAN SHEET A-1 SCOPE OF WORK NOTE 13 CALLS FORNEW
 PLUMBING AND FIXTURES IN ALL UNITS. COMPLY WITH FBC PL
 424.3. PROVIDE SHOWER AND TUB/SHOWER ANTI SCALD VALVES
 CONFORMING TO ASME A112.18/CSA B125.1.
 4.PLAN SHEET A-1, P-1, P-2, E-1 AND M-1 BATHROOM VANITY
 AND WATER CLOSETS IN UNITS #2, #3, #5, #6, #7 AND #8
 ARE REVERSED FROM WHAT IS SHOWN ON A-2 DEMO PLAN. PER
 WPB FBC 107.2.1, CLARIFY AND RECONCILE ALL PLANS.
 5. PLAN SHEET P-1 PLAN VIEW: INDICATE LOCATION OF
 EXISTING PLUMBING STACKS IN THE WALL(S). INDICATE WHICH
 SERVES THE FIRST FLOOR AND WHICH SERVES THE SECOND
 FLOOR. PROVIDE RISER DIAGRAM (S) FOR RELOCATED KITCHEN
 SINK IN UNITS #2, #3, #5, #6 AND #7 SHOWING WHICH STACK
 IT IS CONNECTED TO AND PROVIDE REVENT IF REQUIRED.
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120794 710 10TH STREET

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jesmith Date 2020-01-07 Time 11:40 Rev Time 0.00
Received By jesmith Date 2020-01-07 Time 11:37 Sent To  
Notes
2020-01-07 11:37:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PLAN SHEET A-1: SCOPE OF WORK; NOTE 8 CALLS FOR
 REMOVAL OF BATHTUBS AND REPLACE WITH SHOWERS. THIS IS
 REINFORCED BY THE ENLARGED FLOOR PLANS AND ELEVATION
 PLANS ON PLAN SHEET A-3. PLAN SHEETS A-1, E-1, P-1, P-2
 AND P-3 INDICATE SOME UNITS WITH SHOWERS AND SOME WITH
 BATHTUBS. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE
 ALL PLANS.
 2. PER WPB FBC 107.2.1, PROVIDE ASSEMBLIES COMPLYING
 WITH FBC CHAPTER 7, FOR ANY PIPE PENETRATIONS THROUGH
 FIRE RATED FLOORS AND WALLS.
 3. PLAN SHEET P-2: SELECTED WATER HEATER PROVIDES A
 MAXIMUM OF 2.7 GPM. THIS APPEARS NOT TO SATISFY THE
 REQUIREMENTS FOR HOT WATER FOR THE FIXTURES REQUIRING
 HOT WATER. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS
 FOR THE HOT WATER DEMAND AND SELECT A WATER HEATER
 BASED ON THE CALCULATIONS THAT WILL SATISFY THE HOT
 WATER REQUIREMENTS. PROVIDE MANUFACTURER'S
 SPECIFICATION FOR SAID WATER HEATER. PROVIDE LOCATION
 ON PLAN FOR THE UNIT WHICH IS ACCESSIBLE AS REQUIRED BY
 FBC PL 501.4.
 4. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTIURE
 SCHEDULE INDICATING TYPE, WATER DEMAND/WATER SUPPLY
 SIZE, SANITARY FIXTURE UNIT LOAD/TRAP SIZE
 5. PER WPB FBC 107.2.1, PROVIDE NOTE "SHUT OFF VALVES
 FOR WASHER/ DRYER COMBO SHALL BE ACCESSIBLE PER FBC PL
 606.3".
 6. PLAN SHEET P-1 PLAN VIEW AND P-3 SANITARY RISERS;
 FIXTURE DRAIN FOR WASHER IS NOTED AS 3 INCH SIZE. PER
 FBC 2308.5.10, THIS IS PROHIBITED. FIXTURE DRAIN AND
 TRAP SHALL BE SIZED 2 INCH IN ACCORDANCE WITH THE
 MINIMUM REQUIREMENTS OF FBC PL 709.1.
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE ON THE
 SANITARY RISER DIAGRAMS THE EXISTING UNDERGROUND
 DRAINAGE AND VENTING SO THAT A COMPREHENSIVE REVIEW OF
 THE PROJECT CAN BE COMPLETED. I NOTE THAT UNIT 6 AND
 UNIT 7 ARE DISCHARGING INTO THE VENT STACK AND THROUGH
 THE VENT FOR THE GROUND FLOOR FIXTURES WHICH IS
 PROHIBITED. ADDITIONALLY, I NOTE THAT THERE IS NO VENT
 STACK SHOWN FOR UNITS 1/5 AND 4/8 WHICH IS A
 REQUIREMENT. WHEN ADDRESSING ALSO NOTE THAT PER FBC PL
 912.2 THAT ONLY BATHROOM GROUP FIXTURES AS DEFINED IN
 FBC PL CHAPTER 2 MAY CONNECT TO THE WET VENT AND ONLY
 ON THE SAME FLOOR.
 8. VALUE OF WORK APPEARS TO BE LOW. PER WPB FBC 109.3,
 PROVIDE DETAILED QUANTITY ESTIMATES AND/OR BONA FIDE
 SIGNED CONTRACTS TO MEET THE BUILDING OFFICIALS
 APPROVAL. VALUATION SHALL BE FOR THE TOTAL REPLACEMENT
 VALUE OF STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISHES, RELATIVE SITE WORK, ARCHITECTURAL
 AND DESIGN FEES.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120794 710 10TH ST
  
  
  