Plan Review Details - Permit 19120777
Plan Review Stops For Permit 19120777
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-01-14 Cont ID  
Sent By hmtribou Date 2020-01-14 Time 09:31 Rev Time 0.00
Received By jgomez Date 2020-01-14 Time 15:16 Sent To P
Notes
2020-01-10 08:01:1201/14/2020 TALKED TO JIM (CONTRACTOR) ATTACHING PANELS
 TO ROOF SHEATHING OR TRUSSES NOT TO THE CONCRETE TILE.
 JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-14 Cont ID  
Sent By jleahy Date 2020-01-14 Time 11:49 Rev Time 0.00
Received By jleahy Date 2020-01-14 Time 11:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-03 Cont ID  
Sent By ccarvaja Date 2020-02-03 Time 08:21 Rev Time 0.00
Received By ccarvaja Date 2020-01-29 Time 14:02 Sent To  
Notes
2020-01-30 14:02:54RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-22 Cont ID  
Sent By tklarge Date 2020-01-22 Time 08:27 Rev Time 0.00
Received By tklarge Date 2020-01-22 Time 08:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-14 Cont ID  
Sent By lcrespo Date 2020-01-14 Time 07:22 Rev Time 0.00
Received By lcrespo Date 2019-12-17 Time 13:56 Sent To  
Notes
2019-12-18 13:55:28ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-22 Cont ID  
Sent By tklarge Date 2020-01-22 Time 08:27 Rev Time 0.00
Received By tklarge Date 2020-01-22 Time 08:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-14 Cont ID  
Sent By jgomez Date 2020-01-14 Time 16:04 Rev Time 0.00
Received By lcrespo Date 2020-01-13 Time 07:21 Sent To  
Notes
2020-01-14 07:28:181/14/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW A TEMPERATURE RELIEF IN ACCORDANCE WITH
 2017 FBC M 1402.5.1.
 2. THE SYSTEM REQUIRES A FREEZE PROTECTION IN
 ACCORDANCE WITH 2017 FBC M 1402.5.3.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-31 Cont ID  
Sent By hmtribou Date 2020-01-31 Time 10:19 Rev Time 0.00
Received By hmtribou Date 2020-01-31 Time 10:19 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By hmtribou Date 2019-12-24 Time 09:31 Rev Time 0.00
Received By hmtribou Date 2019-12-24 Time 09:31 Sent To B
Notes
2019-12-20 14:44:07PLEASE CLARIFY SOLAR PANEL LAYOUT.THE PANEL LAYOUT
 DIFFERS ON SITE PLAN FROM SHEET S-1.ALSO, PLEASE NOTE
 THAT SOLAR PANELS SHALL BE INSTALLED PARALLEL TO THE
 ROOFS SURFACE NO GREATER THEN 12 INCHES. QUESTIONS CALL
 HEATHER AT 561-822-1562
  