Plan Review Details - Permit 19120727
Plan Review Stops For Permit 19120727
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-11 Cont ID  
Sent By jgomez Date 2020-03-11 Time 08:57 Rev Time 0.00
Received By jgomez Date 2020-03-11 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By jgomez Date 2020-02-26 Time 16:56 Rev Time 0.00
Received By jgomez Date 2020-02-26 Time 16:42 Sent To  
Notes
2020-02-26 16:50:34SIGN SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- ENGINEER'S DESIGN SPECIFIES A BASIC WIND SPEED OF
 160 MPH. ENGINEER NEEDS TO CLARIFY IF THIS WIND SPEED
 IS THE ULTIMATE WIND SPEED OR THE NOMINAL WIND SPEED.
 IF THIS IS THE ULTIMATE WIND SPEED, THEN ENGINEER NEEDS
 TO REVISE IT. THE ULTIMATE DESIGN WIND SPEED FOR THE
 CITY OF WEST PALM BEACH IS 170 MPH NOT 160MPH.
 SEC. 1609.1.1 FBC-BUILDING AND SEC. 120 CITY
 AMENDMENTS.
  
 RESPONSE:
 ENGINEER REVISED THE ULTIMATE WIND SPEED BUT HE ALSO
 REVISED THE BUILDING CATEGORY TO III-IV. ENGINEER TO
 CLARIFY WHY THE RISK CATEGORY WAS CHANGED FROM II TO
 III-IV. THIS WAS NOT NECESSARY. BUT IF THE ENGINEER
 WANTS TO DESIGN FOR THE III-IV RISK CATEGORY , THEN
 NEEDS TO REVISE THE ULTIMATE WIND SPEED AS REQUIRED BY
 FIGURE 1609.3(2) FBC-BUILDING. (180 MPH).
  
 2- OK.
  
 3- OK.
  
 ORIGINAL COMMENT:
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
 -ENGINEERS-ARCHITECTS-
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By jgomez Date 2020-01-08 Time 13:48 Rev Time 0.00
Received By jgomez Date 2020-01-08 Time 11:36 Sent To E
Notes
2020-01-08 13:48:31SIGN BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- ENGINEER'S DESIGN SPECIFIES A BASIC WIND SPEED OF
 160 MPH. ENGINEER NEEDS TO CLARIFY IF THIS WIND SPEED
 IS THE ULTIMATE WIND SPEED OR THE NOMINAL WIND SPEED.
 IF THIS IS THE ULTIMATE WIND SPEED, THEN ENGINEER NEEDS
 TO REVISE IT. THE ULTIMATE DESIGN WIND SPEED FOR THE
 CITY OF WEST PALM BEACH IS 170 MPH NOT 160MPH.
 SEC. 1609.1.1 FBC-BUILDING AND SEC. 120 CITY
 AMENDMENTS.
  
 2- ENGINEER NEEDS TO PROVIDE THE WIND SPEED CONVERSION
 FROM ULTIMATE WIND SPEED TO NOMINAL WIND SPEED AS
 REQUIRED BY SEC. 1609.3.1 FBC-BUILDING.
 NOTE: ENGINEER NEEDS TO REVISE THE DESIGN WIND PRESSURE
 FOR EXTERIOR COMPONENTS AND CLADDING. COORDINATE WITH
 ITEM #1 ABOVE. AND CLEARLY SPECIFY IF THE DESIGN
 PRESSURES ARE GIVEN AS ULTIMATE WIND SPEED OR NOMINAL
 WIND SPEED.
  
 3- SPECIFICATIONS FOR SIGN LETTERS INSTALLATION ARE
 INCOMPLETE. ENGINEER NEEDS TO CLEARLY SPECIFY THE
 ANCHOR SIZE, ANGLE FISH PLATE SIZE, NUMBER OF ANCHORS
 REQUIRED PER LETTER, ETC. PROVIDE COMPLETE INFORMATION.
 SEC. 1609.1 FBC-BUILDING AND SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF SIGNED
 CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 5- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-10 Cont ID  
Sent By jleahy Date 2020-03-10 Time 14:15 Rev Time 0.00
Received By jleahy Date 2020-03-10 Time 14:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By jleahy Date 2020-02-26 Time 16:12 Rev Time 0.00
Received By jleahy Date 2020-02-26 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By fgiaquin Date 2020-01-09 Time 06:35 Rev Time 0.00
Received By fgiaquin Date 2020-01-09 Time 05:41 Sent To I
Notes
2020-01-09 06:17:27ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE OF $1250 FOR 3 ILLUMINATED SIGNS IS EXTREMELY
 LOW. PROVIDE AN ACCURATE VALUE FOR WORK SHOWN OR VALUE
 WILL BE SET BY BUILDING OFFICIAL.
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. UNDER THE "ELECTRICAL INFORMATION" SECTION ON THE
 PLAN PROVIDED THE NOTES SAY " NEON (2) ROW OF 15MM
 VOLTARC 6500 SNOW WHITE COATED". BUT DIAGRAM SHOWS AN
 L.E.D. SIGN. PROVIDE CORRECTION/CLARIFICATION. FBC
 107.2.1
  
 3. 120V DISCONNECT (WITHIN SIGHT OF SIGNS) CAPABLE OF
 DISCONNECTING BRANCH CIRCUIT CONDUCTORS AT THE POINT OF
 WHICH IT ENTERS SIGN ARE REQUIRED ON ALL SIGNS PER NEC
 600.6A1. PROVIDE CORRECTION.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-11 Cont ID  
Sent By jgomez Date 2020-03-11 Time 09:05 Rev Time 0.00
Received By jgomez Date 2020-03-09 Time 15:52 Sent To I
Notes
2020-03-09 15:52:12RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-26 Cont ID  
Sent By jgomez Date 2020-02-26 Time 17:51 Rev Time 0.00
Received By jgomez Date 2020-02-04 Time 13:45 Sent To  
Notes
2020-02-18 07:43:37ROUTED TO FGIAQUINTO INBOX
2020-02-05 13:45:46RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-09 Cont ID  
Sent By fgiaquin Date 2020-01-09 Time 06:35 Rev Time 0.00
Received By fgiaquin Date 2019-12-17 Time 13:58 Sent To  
Notes
2019-12-18 13:59:07ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By rfalcone Date 2020-02-14 Time 10:31 Rev Time 0.00
Received By rfalcone Date 2020-02-14 Time 10:31 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-24 Cont ID  
Sent By rfalcone Date 2019-12-24 Time 15:22 Rev Time 0.00
Received By rfalcone Date 2019-12-24 Time 15:22 Sent To B
Notes
***NONE***