Plan Review Details - Permit 19120723
Plan Review Stops For Permit 19120723
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-11 Cont ID  
Sent By jgomez Date 2020-03-11 Time 09:14 Rev Time 0.00
Received By jgomez Date 2020-03-11 Time 09:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-27 Cont ID  
Sent By jleahy Date 2020-02-26 Time 16:11 Rev Time 0.00
Received By jgomez Date 2020-02-26 Time 17:55 Sent To  
Notes
2020-02-27 08:17:45SIGN BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- ENGINEER REVISED THE ULTIMATE WIND SPEED BUT HE ALSO
 REVISED THE BUILDING CATEGORY TO III-IV. ENGINEER TO
 CLARIFY WHY THE RISK CATEGORY WAS CHANGED FROM II TO
 III-IV. THIS WAS NOT NECESSARY. BUT IF THE ENGINEER
 WANTS TO DESIGN FOR THE III-IV RISK CATEGORY , THEN
 NEEDS TO REVISE THE ULTIMATE WIND SPEED AS REQUIRED BY
 FIGURE 1609.3(2) FBC-BUILDING. (180 MPH).
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 3- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
 -ENGINEERS-ARCHITECTS-
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-02 Cont ID  
Sent By pvalenti Date 2020-01-02 Time 14:35 Rev Time 0.00
Received By pvalenti Date 2020-01-02 Time 14:35 Sent To  
Notes
2020-01-02 14:36:30***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 109.5, THE VALUE IS TOO LOW. ACCORDING TO THE
 MARSHALL VALUATION SERVICES, THE VALUE SHOULD BE ABOUT
 FIVE TO SIX TIMES THE SUBMITTED VALUE OF $1250.00

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-10 Cont ID  
Sent By jleahy Date 2020-03-10 Time 14:13 Rev Time 0.00
Received By jleahy Date 2020-03-10 Time 14:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-02-26 Cont ID  
Sent By jleahy Date 2020-02-19 Time 14:44 Rev Time 0.00
Received By jleahy Date 2020-02-19 Time 14:44 Sent To B
Notes
2020-02-26 16:11:48WRONG PERMIT APPLICATION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jleahy Date 2020-01-03 Time 08:16 Rev Time 0.00
Received By jleahy Date 2020-01-03 Time 08:16 Sent To  
Notes
2020-01-03 08:18:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE TO LOW
  
 2) DISCONNECT PER 600.6(A)(1) REQUIRED
  
 3) LIGHTING CONTROL REQUIRED PER FBC ECC

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-11 Cont ID  
Sent By jgomez Date 2020-03-11 Time 09:14 Rev Time 0.00
Received By jgomez Date 2020-03-09 Time 15:50 Sent To I
Notes
2020-03-09 15:50:08RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-27 Cont ID  
Sent By jgomez Date 2020-02-27 Time 09:29 Rev Time 0.00
Received By jgomez Date 2020-02-04 Time 13:43 Sent To I
Notes
2020-02-13 07:13:26ROUTED TO JLEAHY INBOX
2020-02-05 13:44:02RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By jleahy Date 2020-01-03 Time 08:16 Rev Time 0.00
Received By jleahy Date 2019-12-17 Time 13:59 Sent To  
Notes
2019-12-18 13:59:29ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-11 Cont ID  
Sent By rfalcone Date 2020-02-11 Time 15:33 Rev Time 0.00
Received By rfalcone Date 2020-02-11 Time 15:33 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-24 Cont ID  
Sent By rfalcone Date 2019-12-24 Time 15:20 Rev Time 0.00
Received By rfalcone Date 2019-12-24 Time 15:20 Sent To B
Notes
***NONE***