Plan Review Details - Permit 19120697
Plan Review Stops For Permit 19120697
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By rmcdouga Date 2020-03-12 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2020-03-12 Time 07:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-21 Cont ID  
Sent By rmcdouga Date 2020-01-21 Time 15:15 Rev Time 0.00
Received By rmcdouga Date 2020-01-21 Time 10:41 Sent To  
Notes
2020-01-21 15:32:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE STRUCTURAL DRAWINGS FOR THE EXACT
 INSTALLATION DETAILS FOR ANCHORING THE GENERATOR
 STRUCTURAL SUPPORTS TO THE CONCRETE FLOOR SLAB AS
 INDICATED ON THE GENERATOR DETAIL ON SHEET E-0.03. FBC
 107.2.1
  
 2) THE STRUCTURAL ENGINEER IS TO VERIFY THAT THE 4"
 THICK CONCRETE SLAB ON GRADE THAT IS SHOWN ON THE
 BUILDING PLANS IS ADEQUATE TO SUPPORT THE GRAVITY LOADS
 OF THE GENERATOR SET. PROVIDE CALCULATIONS. FBC
 107.2.1.2

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-02 Cont ID  
Sent By jleahy Date 2020-03-02 Time 09:22 Rev Time 0.00
Received By jleahy Date 2020-03-02 Time 08:57 Sent To  
Notes
2020-03-02 09:23:37RAISED VALUE TO MARSHALL SWIFT MINIMUM JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-01 Cont ID  
Sent By jleahy Date 2020-03-01 Time 10:34 Rev Time 0.00
Received By jleahy Date 2020-03-01 Time 10:34 Sent To  
Notes
2020-03-01 10:35:27SEE NOTES FROM FIRST REVIEW
  
 SUBMIT A SIGNED CONTRACT FOR THE GENERATOR SHOWING
 VALUE FOR GENERATOR , LABOR AND FUEL TANK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-10 Cont ID  
Sent By jleahy Date 2020-01-10 Time 09:25 Rev Time 0.00
Received By jleahy Date 2020-01-10 Time 09:11 Sent To  
Notes
2020-01-10 09:26:55FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE WORK SHOWN IS LOW PLEASE SUBMIT A
 SIGNED CONTRACT FOR THE WORK INVOLVED, INCLUDING
 GENERATOR, FUEL TANK, TRANSFER SWITCHES, ECT. ECT.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-02 Cont ID  
Sent By pleduc Date 2020-03-02 Time   Rev Time 0.00
Received By pleduc Date 2020-03-02 Time 12:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-12-31 Cont ID  
Sent By pleduc Date 2019-12-31 Time   Rev Time 0.00
Received By pleduc Date 2019-12-31 Time 10:38 Sent To  
Notes
2019-12-31 11:02:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE EXHAUST SYSTEM.
  
 PER NFPA 110.
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
 PLEASE DSPROVIDE THE EXHAUST SYSTEM DETAIL PER THE NFPA
 CODE.
  
  
  
 2) THERE IS NO INDIOCATION OF THE FUEL TANK VENTING.
  
 PER NFPA 110
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA
 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
  
 PER NFPA 30
  
 27.8.1 VENT PIPING FOR ABOVEGROUND STORAGE TANKS.
 27.8.1.1 WHERE THE OUTLETS OF VENT PIPES FOR TANKS
 STORING
 CLASS I LIQUIDS ARE ADJACENT TO BUILDINGS OR PUBLIC
 WAYS, THEY
 SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE
 POINT
 OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT (3.6 M)
 ABOVE THE
 ADJACENT GROUND LEVEL.
 27.8.1.2 VAPORS SHALL BE DISCHARGED UPWARD OR
 HORIZONTALLY
 AWAY FROM ADJACENT WALLS.
 27.8.1.3 VENT OUTLETS SHALL BE LOCATED SO THAT VAPORS
 WILL NOT BE
 TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL BE AT
 LEAST 5 FT
 (1.5 M) FROM BUILDING OPENINGS AND AT LEAST 15 FT (4.5
 M) FROM
 POWERED VENTILATION AIR INTAKE DEVICES.
  
 PLEASE PROVIDE DETAILS FO THE FUEL TANK VENT SYSTEM.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-02-28 Cont ID  
Sent By shill Date 2020-02-28 Time 11:26 Rev Time 0.00
Received By shill Date 2020-02-28 Time 11:26 Sent To  
Notes
2020-02-28 11:26:31THIS IS A DIESEL GENERATOR; NO LP/GAS
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By shill Date 2020-01-22 Time 06:49 Rev Time 0.00
Received By shill Date 2020-01-08 Time 17:32 Sent To  
Notes
2020-01-22 06:49:471ST PLUMBING/GAS REVIEW**DENIED**19120697
 1) PROVIDE A SITE PLAN CLEARLY SHOWING LOCATION OF
 GENERATOR AND GENERATOR EXHAUST FROM BUILDING, WINDOWS,
 DOORS, AND PROPERTY LINE. FBC 107.3.5
 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, AND ANCHORING DETAILS OF THE GAS
 EXHAUST VENT(S) PER 2017 FBC-FUEL GAS SECS. 502 THRU
 505.
 3) IT APPEARS THE FUEL STORAGE TANK AND GENERATOR DID
 NOT COME FROM THE FACTORY AS 1 UNIT. PLEASE CLARIFY. IF
 NOT PLEASE PROVIDE A COMPLETE TANK TO GENERATOR FUEL
 PIPING SHOWING MATERIAL BEING USED, SIZE FOR SUPPLY,
 RETURN, AND VENT. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-12 Cont ID  
Sent By lmarchan Date 2020-03-12 Time 14:21 Rev Time 0.00
Received By lmarchan Date 2020-02-26 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-22 Cont ID  
Sent By shill Date 2020-01-22 Time 06:49 Rev Time 0.00
Received By shill Date 2019-12-24 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-02 Cont ID  
Sent By hmoser Date 2020-03-02 Time 12:07 Rev Time 0.00
Received By hmoser Date 2020-03-02 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-02-28 Cont ID  
Sent By shill Date 2020-02-28 Time 11:26 Rev Time 0.00
Received By shill Date 2020-02-28 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By shill Date 2020-01-22 Time 06:48 Rev Time 0.00
Received By shill Date 2020-01-08 Time 17:32 Sent To  
Notes
2020-01-22 06:49:27REVIEWED REMOTELY BY TIM HUNT
 SEE GAS REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-02 Cont ID  
Sent By jleahy Date 2020-03-02 Time 09:25 Rev Time 0.00
Received By jleahy Date 2020-03-02 Time 09:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By jpearson Date 2020-01-09 Time 14:42 Rev Time 0.00
Received By jpearson Date 2020-01-09 Time 14:42 Sent To  
Notes
2020-01-09 14:42:09PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. PROVIDE CORRECTION FOR ALL SHEETS WITH THIRD
 PARTY VERIFICATION. ADDITIONALLY, SHEET A1.00 IS NOT
 DIGITALLY SIGNED. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By llouie Date 2020-03-12 Time   Rev Time 0.00
Received By llouie Date 2020-03-12 Time   Sent To  
Notes
2020-03-12 10:32:11GENERATOR LOCATED WITHIN THE BUILDING.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By llouie Date 2020-01-03 Time   Rev Time  
Received By llouie Date 2020-01-03 Time   Sent To  
Notes
2020-01-03 15:48:32** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 IT IS NOT CLEAR IN THE PLANS TO WHERE THE PROPOSED
 GENERATOR WILL BE LOCATED (I.E. IS IT EXTERIOR OR
 INTERIOR TO THE BUILDING?). THE LOCATION OF THE
 GENERATOR MUST BE CLEARLY IDENTIFIED IN THE PLANS.
  
 SHEET A1.00: NEW RED BOX DETECTED AT THE NORTHEAST
 CORNER OF THE BUILDING. PLEASE IDENTIFY AND/OR REMOVE
 THE ELEMENT FROM THE SITE PLAN, AS THIS ELEMENT IS NOT
 REFLECTED IN THE APPROVED PLANS.
  
 ANY MODIFICATIONS TO THE SITE AND/OR APPROVED
 ARCHITECTURAL ELEVATIONS WILL REQUIRE A MINOR PD
 AMENDMENT PRIOR TO ZONING APPROVAL FOR THIS PERMIT.
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * REFERENCE: PB 997C (AS-BUILT PLANS)
  
 * ZONE: RPD (GEORGIAN GARDENS APARTMENTS)
  