| 2019-12-20 17:30:07 | 12/20/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS FINAL. A FULL INSPECTION OF ALL GAS |
| | EQUIPMENT WILL BE DONE AT FIELD, IF NOT TO CODE, IT MAY |
| | NEED TO BE BOUT UP TO CODE COMPLIANCE AT THE OWNER IS |
| | RESPONSIBLE FOR INSPECTION PER THE 2017 WPB A TO FBC |
| | SECTION 105.1 PERMITS REQUIRED AND 114 VIOLATION. |
| | 2. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| | SEC. 107.3.5.3 (12) RESIDENTIAL GAS. THE CITY RECORDS |
| | INDICATE AN EXISTING GAS METER AND THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM ON AN |
| | ISOMETRIC. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION PER THE 2017 FBC |
| | RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | 4. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS, |
| | BTU'S OF GENERATOR AND REGULATORS (IF NEEDED) ON |
| | ISOMETRIC PER THE 2017 FBC FG SEC. 409.4. |
| | 5. SUBMIT COPIES OF THE CORRECT SIZING TABLE USED IN |
| | THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH |
| | SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES |
| | OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF |
| | THIS SYSTEM PER THE 2017 FBC FG SEC. 402. |
| | 6. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 |
| | GENERAL. |
| | 7. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR AND THEY SHALL BE ONSITE FOR FINAL GAS |
| | INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED. |
| | NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE |
| | REQUIREMENTS OF UL 2200. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |