Plan Review Details - Permit 19120637
Plan Review Stops For Permit 19120637
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By lcrespo Date 2020-02-06 Time 18:19 Rev Time 0.00
Received By lcrespo Date 2020-02-06 Time 18:19 Sent To  
Notes
2020-02-06 18:19:5202/06/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-12-20 Cont ID  
Sent By lcrespo Date 2019-12-20 Time 17:17 Rev Time 0.00
Received By lcrespo Date 2019-12-20 Time 17:17 Sent To  
Notes
2019-12-20 17:30:0712/20/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS FINAL. A FULL INSPECTION OF ALL GAS
 EQUIPMENT WILL BE DONE AT FIELD, IF NOT TO CODE, IT MAY
 NEED TO BE BOUT UP TO CODE COMPLIANCE AT THE OWNER IS
 RESPONSIBLE FOR INSPECTION PER THE 2017 WPB A TO FBC
 SECTION 105.1 PERMITS REQUIRED AND 114 VIOLATION.
 2. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS. THE CITY RECORDS
 INDICATE AN EXISTING GAS METER AND THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM ON AN
 ISOMETRIC. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION PER THE 2017 FBC
 RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 4. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS,
 BTU'S OF GENERATOR AND REGULATORS (IF NEEDED) ON
 ISOMETRIC PER THE 2017 FBC FG SEC. 409.4.
 5. SUBMIT COPIES OF THE CORRECT SIZING TABLE USED IN
 THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH
 SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES
 OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF
 THIS SYSTEM PER THE 2017 FBC FG SEC. 402.
 6. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
 7. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND THEY SHALL BE ONSITE FOR FINAL GAS
 INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED.
 NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE
 REQUIREMENTS OF UL 2200.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-06 Cont ID  
Sent By lcrespo Date 2020-02-06 Time 18:19 Rev Time 0.00
Received By lcrespo Date 2020-02-05 Time 16:33 Sent To  
Notes
2020-02-06 16:33:31RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-20 Cont ID  
Sent By lcrespo Date 2019-12-20 Time 17:18 Rev Time 0.00
Received By lcrespo Date 2019-12-20 Time 17:18 Sent To  
Notes