| Plan Review Stops For Permit 19120590 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-31 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-31 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-28 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-28 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2020-01-28 15:24:45 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 4TH BUILDING REVIEW DENIED: | | | | | | PLEASE REVIEW: | | | | | | FBC B 107.2.1, AS PER SECTION "D" OF THE SUBMITTED | | | ROOFING FORM 100, THE ENHANCED NAILING PATTERNS NEEDS | | | TO BE SIGNED AND SEALED BY AN ENGINEER. PLEASE SEE | | | PRODUCT APPROVAL #18?0919.07 GENERAL LIMITATION # 7. | | | | | | NOTE: IF THE ENGINEER?S SIGNED AND SEALED SHEETS ARE TO | | | BE SUBMITTED DIGITALLY, THEY WILL NEED A THIRD PARTY | | | VERIFICATION OR YOU MAY SUBMIT THE ORIGINAL SIGNED | | | SEALED "PAPER" SHEETS TO THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-21 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-21 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2020-01-21 10:13:39 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 3RD BUILDING REVIEW DENIED: | | | | | | PLEASE REVIEW: | | | | | | FBC B 107.2.1, AS PER SECTION "D" OF THE SUBMITTED | | | ROOFING FORM 100, THE ENHANCED NAILING PATTERNS NEEDS | | | TO BE SIGNED AND SEALED BY AN ENGINEER. PLEASE SEE | | | PRODUCT APPROVAL #18?0919.07 GENERAL LIMITATION # 7. | | | | | | NOTE: IF THE ENGINEER?S SIGNED AND SEALED SHEETS ARE TO | | | BE SUBMITTED DIGITALLY, THEY WILL NEED A THIRD PARTY | | | VERIFICATION OR YOU MAY SUBMIT THE ORIGINAL SIGNED | | | SEALED "PAPER" SHEETS TO THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-13 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-13 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2020-01-13 15:17:47 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, AS PER SECTION "D" OF THE SUBMITTED | | | ROOFING FORM 100, THE ENHANCED NAILING PATTERNS NEEDS | | | TO BE SIGNED AND SEALED BY AN ENGINEER. PLEASE SEE | | | PRODUCT APPROVAL #18-0919.07 GENERAL LIMITATION # 7. | | | | | | NOTE: IF THE ENGINEER'S SIGNED AND SEALED SHEETS ARE TO | | | BE SUBMITTED DIGITALLY, THEY WILL NEED A THIRD PARTY | | | VERIFICATION OR YOU MAY SUBMIT THE ORIGINAL SIGNED | | | SEALED "PAPER" SHEETS TO THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-24 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-24 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2019-12-24 09:10:44 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE FLAT ROOF CORNER AND PERIMETER | | | ENHANCED FASTENER SPACING NEEDS TO BE APPROVED (SIGNED | | | AND SEALED BY ENGINEER AS PER THE FLAT ROOF NOA | | | LIMITATION # 7. | | | NOTE: IN LIEU OF HAVING A THIRD PARTY VERIFICATION OF | | | THE ENGINEER'S DIGITAL SIGNATURE YOU MAY SUBMIT | | | ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO THE | | | BUILDING DEPARTMENT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-28 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-27 |
Time |
11:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-21 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-14 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-13 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-06 |
Time |
14:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-24 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-19 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-31 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-31 |
Time |
14:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-28 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-28 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2020-01-28 15:28:57 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 4TH SIGNATURE REVIEW DENIED: | | | | | | PLEASE REVIEW: | | | | | | FBC B 107.2.1/F.S. 471/F.A.C. 61G15?23.001 ? .003: | | | PROVIDE ENGINEER?S SIGNED AND SEALED APPROVAL OF | | | ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD | | | PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR | | | SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO | | | THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-21 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-21 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2020-01-21 10:18:40 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 3RD SIGNATURE REVIEW DENIED: | | | | | | PLEASE REVIEW: | | | | | | FBC B 107.2.1/F.S. 471/F.A.C. 61G15-23.001 - .003: | | | PROVIDE ENGINEER'S SIGNED AND SEALED APPROVAL OF | | | ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD | | | PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR | | | SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO | | | THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-13 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-13 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2020-01-13 15:20:47 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND SIGNATURE REVIEW DENIED: | | | | | | FBC B 107.2.1/F.S. 471/F.A.C. 61G15?23.001 ? .003: | | | | | | PROVIDE ENGINEER?S SIGNED AND SEALED APPROVAL OF | | | ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD | | | PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR | | | SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO | | | THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-24 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-24 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2019-12-24 09:17:28 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | SIGNATURE REVIEW DENIED: | | | | | | FBC B 107.2.1/F.S. 471/F.A.C. 61G15-23.001 - .003: | | | PROVIDE ENGINEER'S SIGNED AND SEALED APPROVAL OF | | | ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD | | | PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR | | | SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO | | | THE BUILDING DEPARTMENT. |
|
|