Plan Review Details - Permit 19120590
Plan Review Stops For Permit 19120590
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-01-31 Cont ID  
Sent By pvalenti Date 2020-01-31 Time 13:49 Rev Time 0.00
Received By pvalenti Date 2020-01-31 Time 13:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-01-28 Cont ID  
Sent By pvalenti Date 2020-01-28 Time 15:23 Rev Time 0.00
Received By pvalenti Date 2020-01-28 Time 15:23 Sent To  
Notes
2020-01-28 15:24:45***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 4TH BUILDING REVIEW DENIED:
  
 PLEASE REVIEW:
  
 FBC B 107.2.1, AS PER SECTION "D" OF THE SUBMITTED
 ROOFING FORM 100, THE ENHANCED NAILING PATTERNS NEEDS
 TO BE SIGNED AND SEALED BY AN ENGINEER. PLEASE SEE
 PRODUCT APPROVAL #18?0919.07 GENERAL LIMITATION # 7.
  
 NOTE: IF THE ENGINEER?S SIGNED AND SEALED SHEETS ARE TO
 BE SUBMITTED DIGITALLY, THEY WILL NEED A THIRD PARTY
 VERIFICATION OR YOU MAY SUBMIT THE ORIGINAL SIGNED
 SEALED "PAPER" SHEETS TO THE BUILDING DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-21 Cont ID  
Sent By pvalenti Date 2020-01-21 Time 10:11 Rev Time 0.00
Received By pvalenti Date 2020-01-21 Time 10:11 Sent To  
Notes
2020-01-21 10:13:39***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD BUILDING REVIEW DENIED:
  
 PLEASE REVIEW:
  
 FBC B 107.2.1, AS PER SECTION "D" OF THE SUBMITTED
 ROOFING FORM 100, THE ENHANCED NAILING PATTERNS NEEDS
 TO BE SIGNED AND SEALED BY AN ENGINEER. PLEASE SEE
 PRODUCT APPROVAL #18?0919.07 GENERAL LIMITATION # 7.
  
 NOTE: IF THE ENGINEER?S SIGNED AND SEALED SHEETS ARE TO
 BE SUBMITTED DIGITALLY, THEY WILL NEED A THIRD PARTY
 VERIFICATION OR YOU MAY SUBMIT THE ORIGINAL SIGNED
 SEALED "PAPER" SHEETS TO THE BUILDING DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By pvalenti Date 2020-01-13 Time 15:09 Rev Time 0.00
Received By pvalenti Date 2020-01-13 Time 15:09 Sent To  
Notes
2020-01-13 15:17:47***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, AS PER SECTION "D" OF THE SUBMITTED
 ROOFING FORM 100, THE ENHANCED NAILING PATTERNS NEEDS
 TO BE SIGNED AND SEALED BY AN ENGINEER. PLEASE SEE
 PRODUCT APPROVAL #18-0919.07 GENERAL LIMITATION # 7.
  
 NOTE: IF THE ENGINEER'S SIGNED AND SEALED SHEETS ARE TO
 BE SUBMITTED DIGITALLY, THEY WILL NEED A THIRD PARTY
 VERIFICATION OR YOU MAY SUBMIT THE ORIGINAL SIGNED
 SEALED "PAPER" SHEETS TO THE BUILDING DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By pvalenti Date 2019-12-24 Time 09:02 Rev Time 0.00
Received By pvalenti Date 2019-12-24 Time 08:37 Sent To  
Notes
2019-12-24 09:10:44***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE FLAT ROOF CORNER AND PERIMETER
 ENHANCED FASTENER SPACING NEEDS TO BE APPROVED (SIGNED
 AND SEALED BY ENGINEER AS PER THE FLAT ROOF NOA
 LIMITATION # 7.
 NOTE: IN LIEU OF HAVING A THIRD PARTY VERIFICATION OF
 THE ENGINEER'S DIGITAL SIGNATURE YOU MAY SUBMIT
 ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO THE
 BUILDING DEPARTMENT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-28 Cont ID  
Sent By pvalenti Date 2020-01-28 Time 15:29 Rev Time 0.00
Received By pvalenti Date 2020-01-27 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-21 Cont ID  
Sent By pvalenti Date 2020-01-21 Time 10:18 Rev Time 0.00
Received By pvalenti Date 2020-01-14 Time 11:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-13 Cont ID  
Sent By pvalenti Date 2020-01-13 Time 15:20 Rev Time 0.00
Received By pvalenti Date 2020-01-06 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-24 Cont ID  
Sent By pvalenti Date 2019-12-24 Time 09:17 Rev Time 0.00
Received By pvalenti Date 2019-12-19 Time 14:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-01-31 Cont ID  
Sent By pvalenti Date 2020-01-31 Time 14:04 Rev Time 0.00
Received By pvalenti Date 2020-01-31 Time 14:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-01-28 Cont ID  
Sent By pvalenti Date 2020-01-28 Time 15:27 Rev Time 0.00
Received By pvalenti Date 2020-01-28 Time 15:27 Sent To  
Notes
2020-01-28 15:28:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 4TH SIGNATURE REVIEW DENIED:
  
 PLEASE REVIEW:
  
 FBC B 107.2.1/F.S. 471/F.A.C. 61G15?23.001 ? .003:
 PROVIDE ENGINEER?S SIGNED AND SEALED APPROVAL OF
 ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD
 PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR
 SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO
 THE BUILDING DEPARTMENT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-01-21 Cont ID  
Sent By pvalenti Date 2020-01-21 Time 10:15 Rev Time 0.00
Received By pvalenti Date 2020-01-21 Time 10:13 Sent To  
Notes
2020-01-21 10:18:40***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD SIGNATURE REVIEW DENIED:
  
 PLEASE REVIEW:
  
 FBC B 107.2.1/F.S. 471/F.A.C. 61G15-23.001 - .003:
 PROVIDE ENGINEER'S SIGNED AND SEALED APPROVAL OF
 ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD
 PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR
 SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO
 THE BUILDING DEPARTMENT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By pvalenti Date 2020-01-13 Time 15:19 Rev Time 0.00
Received By pvalenti Date 2020-01-13 Time 15:19 Sent To  
Notes
2020-01-13 15:20:47***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1/F.S. 471/F.A.C. 61G15?23.001 ? .003:
  
 PROVIDE ENGINEER?S SIGNED AND SEALED APPROVAL OF
 ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD
 PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR
 SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO
 THE BUILDING DEPARTMENT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By pvalenti Date 2019-12-24 Time 09:11 Rev Time 0.00
Received By pvalenti Date 2019-12-24 Time 09:11 Sent To  
Notes
2019-12-24 09:17:28***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1/F.S. 471/F.A.C. 61G15-23.001 - .003:
 PROVIDE ENGINEER'S SIGNED AND SEALED APPROVAL OF
 ENHANCED FASTENING PATTERN FOR FLAT ROOF WITH THIRD
 PARTY SIGNATURE VERIFICATION FOR DIGITAL PLANS OR
 SUBMIT ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS TO
 THE BUILDING DEPARTMENT.