Plan Review Details - Permit 19120578
Plan Review Stops For Permit 19120578
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-01-22 Cont ID  
Sent By pvalenti Date 2020-01-22 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2020-01-22 Time 15:47 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2020-01-07 Time 07:42 Sent To  
Notes
2020-01-07 13:55:18ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By rmcphers Date 2020-02-04 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2020-02-04 Time 10:15 Sent To  
Notes
2020-02-04 11:19:29TAKEN TO ELEC BIN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2020-01-07 Time 07:42 Sent To  
Notes
2020-01-07 13:54:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120578
 ADD: 2500 METROCENTRE BLVD. SUITE: 06
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 07/2020
 ACTION: DENIED
  
 1) SHEET A-6.00:
 1A) DETAIL # 2 THE HEIGHT OF THE MIRROR IS INDICATED TO
 BE 40 INCHES FROM THE BOTTOM OF THE MIRROR FRAME.
 PLEASE NOTE THE 40 INCHES MAXIMUM HEIGHT IS TAKEN FROM
 FINISH FLOOR TO THE BOTTOM OF THE REFLECTIVE SURFACE.
 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 1B) DETAIL # 3 IS OF THE SIDE WALL OF THE RESTROOM. THE
 ISSUE HERE IS THE DIMENSIONS FOR THE TOILET PAPER
 HOLDER. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2) SHEET M101 & M501:
  
 2A) UNDER THE HEADING FOR NEW ROOF TOP EXHAUST FANS
 EF-1 THE PLANS STATE THAT A NEW CURB AND EXHAUST FAN
 ARE TO BE INSTALLED. SHEET M501 NOTES 5 & 6 THAT THE
 NEW ROOFTOP ARE TO ADHERE TO HURRICANE CODE
 REQUIREMENTS REQUIRING ROOF TIE-INS AND WIND
 RESISTANCE. HOW DO YOU KNOW WHAT IS REQUIRED SINCE
 THERE IS NO WIND DESIGN CRITERIA, WIND SPEED ETC.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2B) SHEET M101. NOTES FOR THE RTU-1 UNDER REMARKS STATE
 THE NEW RTU CURB IS TO BE FACTORY PROVIDED 14 INCH WIND
 LOAD RATED CURB.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS,
 (G) PRE-ENGINEERED A/C STANDS
  
 2C) SHEET M501 DETAIL #6 SHOWS A ROOF FRAMING DETAIL
 BUT THE DETAIL IS GENERIC. THE PLAN DOES NOT STATE THE
 SIZE OF THE INFILL FRAMING STEEL NOR DOES THE PLAN
 INDICATE IF THE STEEL L-ANGLE IS TO BE WELDED TO THE
 TOP CHORD OF THE BAR JOIST.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FRAMING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2D) SHEET M501 DETAIL # 2 ALSO NOTES FOR THE NEW STEEL
 INFILL FRAMING SEE STRUCTURAL DRAWINGS, THERE ARE NO
 STRUCTURAL DRAWING WITHIN THE SUBMITTED SET OF PLANS.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FRAMING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2E) SHEET M501 DETAIL # 2 INDICATES THE USE OF 2 INCH
 STEEL STRAPS TO ANCHOR THE RTU TO THE CURB, GENERIC
 DETAIL, FOR THE 170 VULT WIND HOW MANY ANCHORS WILL BE
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, RTUS, FANS OR A/C
 STANDS, AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF
 FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND
 TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By jleahy Date 2020-02-05 Time 12:18 Rev Time 0.00
Received By jleahy Date 2020-02-05 Time 12:16 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-30 Cont ID  
Sent By jpearson Date 2019-12-30 Time 15:55 Rev Time 0.00
Received By jpearson Date 2019-12-30 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-31 Cont ID  
Sent By pleduc Date 2020-01-31 Time   Rev Time 0.00
Received By pleduc Date 2020-01-31 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-31 Cont ID  
Sent By pleduc Date 2019-12-31 Time   Rev Time 0.00
Received By pleduc Date 2019-12-31 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-18 Cont ID  
Sent By rmcphers Date 2020-02-18 Time 16:33 Rev Time 0.00
Received By rmcphers Date 2020-02-13 Time 13:27 Sent To  
Notes
2020-02-18 16:34:00PLANS TAKEN TO PERMIT LIBRARY
2020-02-14 13:28:12IMPACT ROUTED TO RMCPHERSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-02-11 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-28 Time 15:35 Sent To  
Notes
2020-02-04 11:20:31TAKEN TO ELEC BIN
2020-01-29 15:35:56B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-13 Time 13:02 Sent To  
Notes
2019-12-16 13:02:26B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2020-02-18 Cont ID  
Sent By rmcphers Date 2020-02-18 Time 16:30 Rev Time 0.00
Received By rmcphers Date 2020-02-18 Time 16:30 Sent To  
Notes
2020-02-18 16:33:27NO FEES REQUIRED - NO CHANGE OF USE PER FEE
 QUESTIONNAIRE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2020-01-07 Time 07:42 Sent To  
Notes
2020-01-07 13:56:17IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-11 Cont ID  
Sent By ccole Date 2020-02-11 Time 17:00 Rev Time 0.00
Received By ccole Date 2020-02-10 Time 10:29 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-31 Cont ID  
Sent By ccole Date 2019-12-31 Time 12:45 Rev Time 0.00
Received By ccole Date 2019-12-31 Time 11:53 Sent To  
Notes
2019-12-31 12:53:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120578
 12/31/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) M101: AN AUTOMATIC O/A SHUTOFF DAMPER- EITHER
 MOTORIZED OR GRAVITY- SHALL BE PROVIDED FOR THE RTU-
 SECTION C403.2.4.3 FBC EC.
  
 3) M101: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE 5-TON RTU PER SECTION 606.2.1
 FBC M. ALTHOUGH THESCHEDULE INDICATES 1750 CFM'S OF
 SUPPLY AIR, TRANE PERFORMANCE DATA FOR THE UNIT
 INDICATES IT CAN PRODUCE OVER 2000 CFMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By jesmith Date 2020-02-06 Time 13:33 Rev Time 0.00
Received By jesmith Date 2020-02-06 Time 07:53 Sent To  
Notes
2020-02-06 13:33:09PLUMBING COMMENTS: APPROVED W/PROVISO
  
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE FOLLOWING:
  
 A. A MANUFACTURER?S SPECIFICATION/CUT SHEET FOR THE
 WATER HEATER; TO INCLUDE MODEL, STORAGE CAPACITY AND
 ELECTRICAL CHARACTERISTICS.
 B. A MANUFACTURER?S SPECIFICATION/CUT SHEET FOR
 EXPANSION CONTROL DEVICE; TO INCLUDE MODEL AND SIZE.
  
 THE DOCUMENTS SHALL BE SUBMITTED AS A SUPPORTING
 DOCUMENT WITH REQUIRED ARCHITECT?S STAMP AND SIGNATURE,
 APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK.
  
 2. PROVIDE THERMAL EXPANSION CONTROL FOR THE WATER
 HEATER COMPLYING WITH FBC PL 607.3; SEE PROVISO NOTE
 #1.B
  
 3. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW AND ONCE
 APPROVED HAVE TWO (2) COPIES AT THE JOB SITE PRIOR TO
 THE FIRST INSPECTION. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRTETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT INTO THE EXISTING
 SLAB, THE ANCHORING MATERIAL FOR THE DOWELS AND THE
 SPACING OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR THE FINAL
 INSPECTION
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-31 Cont ID  
Sent By jesmith Date 2019-12-31 Time 15:11 Rev Time 0.00
Received By jesmith Date 2019-12-31 Time 14:33 Sent To  
Notes
2019-12-31 15:11:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER FBC PL 403.3.1, THE ROUTE TO THE PUBLIC TOILET
 FACILITIES REQUIRED BY SECTION 403.3 SHALL NOT PASS
 THROUGH KITCHENS, STORAGE ROOMS OR CLOSETS.
 2. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 SANITARY AND WATER RISER DIAGRAMS REFLECTING THE SCOPE
 OF WORK
 3. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A
 DETAIL FOR THE WATER HEATER SHOWING COMPLIANCE WITH THE
 REQUIREMENTS OF FBC PL 503.1, 504.1/504.2, 504.4,
 504.6, 504.7.2 AND 607.3. SPECIFICALLY PROVIDE ROUTING
 AND TERMINATION OF THE PAN DRAIN, IF DISCHARGING TO
 SANITARY THEN MAKE PROVISION IN THE SANITARY DRAWINGS,
 PROVIDING A TRAPPED AND VENTED OPEN RECEPTACLE PER FBC
 PL 802.3; PROVIDE TRAP SEAL PROTECTION TO COMPLY WITH
 FBC PL 1002.4.1 THROUGH 1002.4.1.4. WATER HEATER SHALL
 BE LOCATED AND CONNECTED SO AS TO PROVIDE ACCESS FOR
 OBSERVATION, MAINTENANCE, SERVICING AND REPLACEMENT PER
 FBC PL 501.4.
 4. PER FBC PL 416.5, TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070
 5. PROVIDE WATER HAMMER ARRESTOR CONFORMING TO ASSE
 1010 FOR REFRIGERATOR WATER CONNECTION PER FBC PL
 604.9.
 6. PROVIDE INDIVIDUAL SHUT OFF FOR EACH, SINK AND
 REFRIGERATOR PER FBC PL 606.2.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120578 2500 METROCENTRE BLVD W # 6