Plan Review Details - Permit 19120514
Plan Review Stops For Permit 19120514
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-31 Cont ID  
Sent By jleahy Date 2019-12-31 Time 14:36 Rev Time 0.00
Received By jpearson Date 2019-12-31 Time 14:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-01-03 Cont ID  
Sent By tklarge Date 2020-01-03 Time 14:59 Rev Time 0.00
Received By tklarge Date 2020-01-03 Time 14:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 10:41 Rev Time 0.00
Received By tklarge Date 2020-01-03 Time 10:24 Sent To  
Notes
2020-01-03 10:41:081) THE CSST LINE TO K27 IS UNDERSIZED PER THE
 REFERENCED TABLE ON THE PLANS.
 2) SIZE THE GAS MANIFOLD IN ITS ENTIRETY TO ITEMS # K5,
 K7, & K33.
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE KITCHEN
 APPLIANCES. IF COMBUSTION AIR IS PROVIDD BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2014 FBC-FUEL
 GAS SEC.304.1, 304.9.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By tklarge Date 2020-01-03 Time 10:41 Rev Time 0.00
Received By tklarge Date 2019-12-12 Time 14:36 Sent To  
Notes
2019-12-13 14:36:48B07

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-12-18 Cont ID  
Sent By ccole Date 2019-12-18 Time 10:47 Rev Time 0.00
Received By ccole Date 2019-12-18 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 10:24 Rev Time 0.00
Received By tklarge Date 2020-01-03 Time 04:45 Sent To  
Notes
***NONE***