Plan Review Details - Permit 19120503
| Plan Review Stops For Permit 19120503 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-03-25 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-03-25 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2020-03-25 09:01:36 | SIGN BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | | | | 1- OK. ENGINEER REVISED THE BUILDING EXPOSURE AS | | | REQUESTED. | | | | | | NOTE: | | | BUILDING REVIEW WILL BE APPROVED WHEN THE ZONING | | | COMMENTS AND ELECTRICAL COMMENTS ARE ADDRESSED. | | | (VALUATION DECLARED IN THE PERMIT APPLICATION TO | | | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND | | | PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY | | | OF SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL | | | FEES). | | | | | | | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-02-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-02-20 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-02-20 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2020-02-20 16:09:21 | SIGN BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | | | | 1- OK. ENGINEER REVISED THE BUILDING EXPOSURE AS | | | REQUESTED. | | | | | | NOTE: | | | BUILDING REVIEW WILL BE APPROVED WHEN THE ZONING | | | COMMENTS AND ELECTRICAL COMMENTS ARE ADDRESSED. | | | (VALUATION DECLARED IN THE PERMIT APPLICATION TO | | | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND | | | PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY | | | OF SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL | | | FEES). | | | | | | | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-12-30 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-12-30 |
Time |
11:00 |
Sent To |
E |
|
| Notes |
| 2019-12-30 11:12:45 | SIGN BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | 1- ACCORDING TO SEC. 1609.4 FBC-BUILDING, THIS BUILDING | | | IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". ENGINEER | | | TO REVISE THE SIGN DESIGN CALCULATIONS AS REQUIRED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-24 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-24 |
Time |
13:21 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-02-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-02-20 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-02-20 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2020-02-20 13:37:42 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE FOR PROPOSED WORK IS TOO LOW. PLEASE SUBMIT A | | | SIGNED CONTRACT WITH YOU AND THE OWNER. | | | | | | | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-01-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-03 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-03 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2020-01-03 15:39:13 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE FOR PROPOSED WORK IS TOO LOW. PLEASE SUBMIT A | | | SIGNED CONTRACT WITH YOU AND THE OWNER. | | | | | | | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-03-25 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-03-20 |
Time |
14:46 |
Sent To |
I |
|
| Notes |
| 2020-03-24 09:32:57 | 3/24 ROUTED TO ELECTRICAL INBOX | | 2020-03-20 14:46:57 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-02-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-02-20 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-02-12 |
Time |
14:15 |
Sent To |
I |
|
| Notes |
| 2020-02-18 07:46:24 | RESUB ROUTED TO JLEAHY IN BOX | | 2020-02-13 14:15:14 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-01-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-03 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-12 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2019-12-13 14:09:53 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-03-24 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-03-24 |
Time |
08:48 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-02-14 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-02-14 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-02-14 |
Time |
10:17 |
Sent To |
I |
|
| Notes |
| 2020-02-14 10:19:21 | 2/14/2020 FAILED. | | | | | | BASED ON THE TOTAL SQUARE FOOTAGE OF THE FRONTAGE OF | | | THE STRUCTURE THE MAXIMUM ALLOWED SIGN SQAURE FOOTAGE | | | IS 12.53 SQ FT (ONE PERCENT OF THE BUILDING FRONTAGE). | | | | | | PLEASE REVISE THE SIZE OF THE PROPOSED SIGN AND | | | RESUBMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-12-24 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-12-24 |
Time |
11:42 |
Sent To |
B |
|
| Notes |
| 2019-12-24 11:45:15 | 12/24/19 FAILED. | | | | | | PLEASE PROVIDE THE SQUARE FOOTAGE OF THE BUILDING | | | FRONTAGE INCLUDING THE SMALLER PORTION OF THE FIRST | | | FLOOR OF THE STRUCTURE. PROVIDE THE SQUARE FOOTAGE OF | | | THE PROPOSED SIGNAGE, KEEP IN MIND THE WALL SIGN SHALL | | | NOT EXCEED THE LESSER OF ONE PERCENT OF GROSS WALL AREA | | | OR 16 SQUARE FEET (WHICHEVER IS SMALLER). | | | | | | PURUSUANT ZLDR SEC. 94-148(13)(B).WALL, FACADE, CANOPY, | | | MARQUEE, AND RELATED BUILDING-MOUNTED SIGNS: ONE SIGN, | | | LOCATED ON ANY BUILDING SIDE SHALL BE PERMITTED, NOT TO | | | EXCEED THE LESSER OF ONE PERCENT OF GROSS WALL AREA OR | | | 16 SQUARE FEET. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME | | | NTS/DEVELOPMENT-SERVICES/OVERVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | |
|
|
|