Plan Review Details - Permit 19120503
Plan Review Stops For Permit 19120503
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-25 Cont ID  
Sent By jgomez Date 2020-03-25 Time 09:28 Rev Time 0.00
Received By jgomez Date 2020-03-25 Time 08:56 Sent To  
Notes
2020-03-25 09:01:36SIGN BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 1- OK. ENGINEER REVISED THE BUILDING EXPOSURE AS
 REQUESTED.
  
 NOTE:
 BUILDING REVIEW WILL BE APPROVED WHEN THE ZONING
 COMMENTS AND ELECTRICAL COMMENTS ARE ADDRESSED.
 (VALUATION DECLARED IN THE PERMIT APPLICATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY
 OF SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL
 FEES).
  
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-20 Cont ID  
Sent By jgomez Date 2020-02-20 Time 16:26 Rev Time 0.00
Received By jgomez Date 2020-02-20 Time 16:06 Sent To  
Notes
2020-02-20 16:09:21SIGN BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 1- OK. ENGINEER REVISED THE BUILDING EXPOSURE AS
 REQUESTED.
  
 NOTE:
 BUILDING REVIEW WILL BE APPROVED WHEN THE ZONING
 COMMENTS AND ELECTRICAL COMMENTS ARE ADDRESSED.
 (VALUATION DECLARED IN THE PERMIT APPLICATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY
 OF SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL
 FEES).
  
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-30 Cont ID  
Sent By jgomez Date 2019-12-30 Time 11:09 Rev Time 0.00
Received By jgomez Date 2019-12-30 Time 11:00 Sent To E
Notes
2019-12-30 11:12:45SIGN BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- ACCORDING TO SEC. 1609.4 FBC-BUILDING, THIS BUILDING
 IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". ENGINEER
 TO REVISE THE SIGN DESIGN CALCULATIONS AS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 13:21 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 13:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-02-20 Cont ID  
Sent By jleahy Date 2020-02-20 Time 13:36 Rev Time 0.00
Received By jleahy Date 2020-02-20 Time 13:36 Sent To  
Notes
2020-02-20 13:37:42FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR PROPOSED WORK IS TOO LOW. PLEASE SUBMIT A
 SIGNED CONTRACT WITH YOU AND THE OWNER.
  
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jgomez Date 2020-01-03 Time 13:02 Rev Time 0.00
Received By jleahy Date 2020-01-03 Time 15:37 Sent To  
Notes
2020-01-03 15:39:13FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR PROPOSED WORK IS TOO LOW. PLEASE SUBMIT A
 SIGNED CONTRACT WITH YOU AND THE OWNER.
  
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-25 Cont ID  
Sent By jgomez Date 2020-03-25 Time 09:28 Rev Time 0.00
Received By jgomez Date 2020-03-20 Time 14:46 Sent To I
Notes
2020-03-24 09:32:573/24 ROUTED TO ELECTRICAL INBOX
2020-03-20 14:46:57RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-20 Cont ID  
Sent By jgomez Date 2020-02-20 Time 16:26 Rev Time 0.00
Received By jgomez Date 2020-02-12 Time 14:15 Sent To I
Notes
2020-02-18 07:46:24RESUB ROUTED TO JLEAHY IN BOX
2020-02-13 14:15:14RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By jleahy Date 2020-01-03 Time 15:39 Rev Time 0.00
Received By jleahy Date 2019-12-12 Time 14:09 Sent To  
Notes
2019-12-13 14:09:53ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By rfalcone Date 2020-03-24 Time 08:48 Rev Time 0.00
Received By rfalcone Date 2020-03-24 Time 08:48 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-02-14 Cont ID  
Sent By rfalcone Date 2020-02-14 Time 10:17 Rev Time 0.00
Received By rfalcone Date 2020-02-14 Time 10:17 Sent To I
Notes
2020-02-14 10:19:212/14/2020 FAILED.
  
 BASED ON THE TOTAL SQUARE FOOTAGE OF THE FRONTAGE OF
 THE STRUCTURE THE MAXIMUM ALLOWED SIGN SQAURE FOOTAGE
 IS 12.53 SQ FT (ONE PERCENT OF THE BUILDING FRONTAGE).
  
 PLEASE REVISE THE SIZE OF THE PROPOSED SIGN AND
 RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By rfalcone Date 2019-12-24 Time 11:42 Rev Time 0.00
Received By rfalcone Date 2019-12-24 Time 11:42 Sent To B
Notes
2019-12-24 11:45:1512/24/19 FAILED.
  
 PLEASE PROVIDE THE SQUARE FOOTAGE OF THE BUILDING
 FRONTAGE INCLUDING THE SMALLER PORTION OF THE FIRST
 FLOOR OF THE STRUCTURE. PROVIDE THE SQUARE FOOTAGE OF
 THE PROPOSED SIGNAGE, KEEP IN MIND THE WALL SIGN SHALL
 NOT EXCEED THE LESSER OF ONE PERCENT OF GROSS WALL AREA
 OR 16 SQUARE FEET (WHICHEVER IS SMALLER).
  
 PURUSUANT ZLDR SEC. 94-148(13)(B).WALL, FACADE, CANOPY,
 MARQUEE, AND RELATED BUILDING-MOUNTED SIGNS: ONE SIGN,
 LOCATED ON ANY BUILDING SIDE SHALL BE PERMITTED, NOT TO
 EXCEED THE LESSER OF ONE PERCENT OF GROSS WALL AREA OR
 16 SQUARE FEET.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME
 NTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved