Plan Review Details - Permit 19120454
Plan Review Stops For Permit 19120454
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-13 Cont ID  
Sent By lcrespo Date 2019-12-13 Time 06:38 Rev Time 0.00
Received By lcrespo Date 2019-12-13 Time 06:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-13 Cont ID  
Sent By lcrespo Date 2019-12-13 Time 06:38 Rev Time 0.00
Received By lcrespo Date 2019-12-13 Time 06:38 Sent To  
Notes
2019-12-13 07:01:2012/13/19 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE SEEMS TO BE A GAS HEATER PERMIT APPLIED FOR
 THIS AS HEATER UNDER PERMIT 19091100 AND YOU ARE
 REQUESTING TO CHANGE OUT A POOL HEATER. THERE IS NO
 RECORD OF A POOL HEATER INSTALLED OR INSPECTED IN CITY
 RECORDS FOR 235 POTTER RD. IF YOU ARE TAKING OVER THE
 JOB OVER PLEASE HAVE PROVIDE EMAIL OR LETTER FROM THE
 POOL CONTRACTOR STATING THAT YOU ARE THE NEW CONTRACTOR
 OF RECORD.
 2. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 3. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS
 IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 4. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
 8. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3.
 9. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 10. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
 11. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2.
 13. SHOW THE BTU LOAD FOR THE FUTURE POOL HEATER. THIS
 VALUE MUST BE INCLUDED IN THE SIZING OF THE SYSTEM PER
 THE 2017 FBC RES. SEC G2413.2 MAXIMUM GAS DEMAND.
 14. SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE
 POOL HEATER IN RELATION TO BUILDING OPENINGS (SOFFITS)
 AND OPERABLE DOORS AND WINDOWS. THE POOL HEATER EXHAUST
 SHALL BE LOCATED PER THE POOL HEATER INSTALLATION
 MANUAL PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW