Plan Review Details - Permit 19120428
Plan Review Stops For Permit 19120428
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-03-05 Cont ID  
Sent By pvalenti Date 2020-03-05 Time 07:56 Rev Time 0.00
Received By pvalenti Date 2020-03-05 Time 07:56 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-02-12 Cont ID  
Sent By pvalenti Date 2020-02-12 Time 13:23 Rev Time 0.00
Received By pvalenti Date 2020-02-12 Time 09:15 Sent To  
Notes
2020-02-12 13:24:17***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS COMMENTS:
  
 FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 13:51 Sent To  
Notes
2020-01-07 06:25:00ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-12 Cont ID  
Sent By pvalenti Date 2020-02-12 Time 13:24 Rev Time 0.00
Received By pvalenti Date 2020-02-12 Time 09:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 13:51 Sent To  
Notes
2020-01-07 07:37:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120428
 ADD: 1540 PALM BEACH LAKES BLVD. SUITE: 100
 CONT: L & L INTERIOR & REMODELING INC.
 TEL: 561-686-5853
 E-MAIL: METRODESIGNGROUP.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JAN. 06/ 2020
 ACTION: DENIED
  
 1) SHEET 1.6A/ LIFE SAFETY SHEET:
  
 1A) THE LIFE SAFETY NOTE # 11 INDICATES A SIGN WILL BE
 PLACED AT ENTRY STATING A MAXIMUM OF 88 OCCUPANTS. WHEN
 TOTALING THE INTERIOR SEATING, KITCHEN HELP AND OFFICE
 I GET 145 TOTAL OCCUPANTS FOR THE INTERIOR WITH ANOTHER
 24 SEASONAL SEATING. 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1OF THE
 ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) THE AMOUNT AND LOCATION OF THE EMERGENCY LIGHT
 BETWEEN THE LIFE SAFETY PLAN AND 2.1E VARY BETWEEN THE
 PLANS, IT WOULD APPEAR ON THE LIFE SAFETY PLAN
 ADDITIONAL EMERGENCY BATTERY BACKUP LIGHTS ARE
 REQUIRED. 2017 FBC-B SECTION 1008.3.1. IN THE EVENT OF
 POWER SUPPLY FAILURE IN ROOMS AND SPACES THAT REQUIRE
 TWO OR MORE MEANS OF EGRESS, AN EMERGENCY ELECTRICAL
 SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE
 FOLLOWING AREAS: 1.AISLES. 2. CORRIDORS. & 3.EXITS.
  
 1C) UNDER THE HEADING OF OCCUPANT LOAD THE KITCHEN
 OCCUPANT LOAD FACTOR IS TAKEN AT 100 GROSS, PLEASE
 REVIEW THE 2017 FBC-B TABLE 1004.1.2 COMMERCIAL KITCHEN
 OCCUPANT LOAD FACTOR IS TAKEN AT 200 GROSS OR 1711 S.
 F. /200 = 9 OCCUPANTS NOT 18.
  
 1D) THE LIFE SAFETY SHEET SHOWS A BAR WITH 10 SEATS AND
 AN ACCESSIBLE LOCATION FOR WHEELCHAIR USERS WHICH IS
 NOT PART OF THE MAIN BAR AND AWAY BACK IN THE CORNER.
 THIS LOCATION IS NOT TO BE CONSIDERED EQUIVALENT
 FACILITATION. THE WHEELCHAIR USER IS NOT TO FEEL
 SLIGHTED, THE LOCATION IS IN A SERVICE AISLE, NOR CAN A
 GUEST OF THE WHEELCHAIR BOUND PERSON BE WITH THEM. 2017
 FBC-ACC. SECTION 103 & 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 1E) THE LIFE SAFETY PLAN DOES HAVE ENOUGH ACCESSIBLE
 SEATING LOCATIONS, BUT THE LOCATIONS ARE TO BE
 DISPERSED THROUGHOUT THE RESTAURANT, THERE ARE NO
 ACCESSIBLE SEATING LOCATIONS ON THE EXTERIOR OF THE
 BUILDING FOR SEASONAL SEATING. 2017 FBC-ACCESSIBILITY
 CODE SECTION 226.2 DISPERSION. DINING SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES.
  
 1F) THE LIFE SAFETY PLAN SHOWS WHAT APPEARS TO BE 4
 ROUND COLUMNS, SHEET 1.5A HAS TO ELEVATIONS OF THESE
 PROPOSED COLUMNS/ PILING/ POST. IN THE DETAILS 2 & 4 OF
 THIS PAGE THEY ARE LABELED POST AND PILING, PENETRATE
 THE FLOOR BY 2 FEET. IF THESE 4 PILING ARE TO SUPPORT
 SOMETHING PLEASE EXPLAIN THEIR USAGE AND HOW THEY ARE
 TO BE INSTALLED AND OF WHAT MATERIAL THEY ARE TO BE
 MADE FROM. PLEASE ALSO USE THE SAME NOMENCLATURE FOR
 DETAILS. IT WOULD APPEAR THE PILING ARE TO SUPPORT THE
 BAR JOIST SINCE THEY ARE BEING WELDED TO THE BAR JOIST,
 PLEASE EXPLAIN? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED FOR THE INSTALLATION OF PILING. NO SOILS TEST
 WAS SUBMITTED FOR THE COEFFICIENT OF FRICTION SINCE
 THERE IS NO FOUNDATION BENEATH THE PILE?
  
 1G) THE 4 COLUMNS/ PILING/ POST FOUND ON THE LIFE
 SAFETY PLAN SHOWN ON SHEET 1.5A SHOW WELDING TO THE BAR
 JOIST PLEASE SHOW COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 2) SHEETS 1.3A, 1.4A AND 1.5A BOTH INDICATE A DROPPED
 CEILING OVER THE BAR, WITH THE CEILING FINISH BEING
 FIRE TREATED T & G.
  
 2A) PLEASE PROVIDE THE SYSTEM & MATERIALS USED TO
 COMPLETE THIS DROPPED CEILING AND SOFFIT? HOW WILL THE
 SYSTEM BE ATTACHED TO THE BAR JOIST, TOP OR BOTTOM BAR
 OF THE BAR JOIST? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) THE PLAN INDICATES THE T & G WILL BE FIRE RETARDANT
 TREATED WOOD, WILL THERE BE COMBUSTIBLE FRAMING BEHIND
 THE T & G PLANKS? PLEASE PROVIDE COMPLIANCE WITH THE
 2017 FBC-B SECTION:
 803.13.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS
 ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.13.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
 EXCEPTIONS:
 1.WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON BOTH
 SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 903.3.1.1 OR 903.3.1.2.
 2.WHERE INTERIOR FINISH MATERIALS ARE ATTACHED TO
 NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS
 SPECIFIED IN SECTION 803.13.1.1.
  
 3) THE COVERSHEET C-1UNDERTHE HEADING SCOPE OF WORK
 NOTE #6 INDICATES TO RAISE RESTROOM / KITCHEN WALLS
 FINISHED TO ROOF DECK. SHEET 1.5A SHOWS ALL INTERIOR
 WALLS NOT 1 HOUR FIRE RATED TO HAVE THE DRYWALL STOP
 JUST ABOVE THE DROPPED CEILING, WHERE CAN I FIND THE
 WALL ILLUSTRATION FORM NOTE # 6. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) SHEET 1.6A SHOWS THE WAITING AREA WITH 120 SQ. FT. /
 5= 24 OCCUPANTS. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-B. WHERE PERSONS ARE ADMITTED TO THE BUILDING AT
 TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL
 BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE,
 PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH
 UPON THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE
 MEANS OF EGRESS. SUCH FOYER, IF NOT DIRECTLY CONNECTED
 TO A PUBLIC STREET BY ALL THE MAIN ENTRANCES OR EXITS,
 SHALL HAVE A STRAIGHT AND UNOBSTRUCTED CORRIDOR OR PATH
 OF TRAVEL TO EVERY SUCH MAIN ENTRANCE OR EXIT. FBC-B
 1029.4.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-01 Cont ID  
Sent By jpearson Date 2020-03-01 Time 09:53 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 09:53 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-26 Cont ID  
Sent By jpearson Date 2019-12-26 Time 14:58 Rev Time 0.00
Received By jpearson Date 2019-12-26 Time 13:42 Sent To  
Notes
2019-12-26 14:58:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULAITON OF PANELS DOES
 NOT MAKE SENSE. HOW CAN THE LOAD OF PANELS B AND C BE
 EXACTLY THE SAME WHEN THEY HAVE DIFFERENT LOADS? HOW IS
 THE NUMBER SHOWN FOR THESE PANELS DIFFERENT WHEN SHOWN
 IN PANEL A? NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By pleduc Date 2020-02-14 Time   Rev Time 0.00
Received By pleduc Date 2020-02-14 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-12-16 Cont ID  
Sent By pleduc Date 2019-12-16 Time   Rev Time 0.00
Received By pleduc Date 2019-12-16 Time 15:07 Sent To  
Notes
2019-12-16 15:39:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 1 & 1.1A - THERE ARE INDICATIONS OF AN
 EXISTING HOOD SYSTEM. THE EXISTING HOOD SYSTEM SHALL
 HAVE CURRENT CERTIFICATIONS OF FUNCTION AND CLEANING AT
 THE TIME OF FIRE INSPECTION.
  
 PLEASE ENSURE COMPLIANCE AND PROPER DOCUMENTATION.
  
 PLEASE ADD A NOTE OF ACKNOWLEDGEMENT.
  
  
 2) SHEET 1.6A - IN THE OCCUPANCY LOAD TABLE THERE ARE
 INDICATION OF A BANQUET BENCH WITH 38.
  
 THERE ARE 16 SPACES OPPOSITE THE INDICATED CHAIRS
 APPROX. 8 MORE SPACES FOR SITTING FOR TOTAL OF 24.
  
 THERE ARE ALSO NO DIMENSION OF THE THE LENGHT OF THE
 BENCH.
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY ALL 38 SPACES
  
  
 3) SHEET 1.6A - IN THE OCCUPANCY LOAD TABLE THERE ARE
 INDICATION OF A BAR WITH 19.
  
 THERE ARE 10 BAR STOOLS ALONG THE BAR AREA..
  
 THERE ARE ALSO NO DIMENSION OF THE THE LENGHT OF THE
 BAR,
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY ALL 19 STOOLS.
  
  
 4) SHEET 1.6A - THE OUTSIDE AREA DOES NOT HAVE
 DIMENSION TO JUSTIFY THE SEATING ARRANGEMENT ALONG THE
 OUTSIDE WALL.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES THERE DOES
 NOT APPEAR ENOUGH ROOM FOR THIS PROPOSED ARRANGEMENT.
  
 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES.
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 PLEASE REVIEW AND PROVIDE ALL DIMENSION AND INDICATE
 AND ENSURE PROPER DIMENSION BETWEEN TABLES, CHAIRS AND
 AISLES SHOWING COMPLIANCE.
  
  
 5) SHEET 1.6A - THE INSIDE AREAS DO NOT HAVE DIMENSION
 TO JUSTIFY THE SEATING ARRANGEMENTS.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES THERE DOES
 NOT APPEAR ENOUGH ROOM FOR THIS PROPOSED ARRANGEMENT.
  
 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES.
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 PLEASE REVIEW AND PROVIDE ALL DIMENSIONS AND INDICATE
 AND ENSURE PROPER DIMENSION BETWEEN TABLES, CHAIRS AND
 AISLES SHOWING COMPLIANCE.
  
  
 6) SHEET 1.7A - DOOR # 1 WITHIN THE DOOR SCHEDULE
 INDICATES A DEAD-BOLT LOCK BUT DOES NOT INDICATE PANIC
 HARDWARE.
  
 PER NFPA 101, CH 12 ND CH 7 MEANS OF EGRESS.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
  
 PLEASE REVIEW, AND PROVIDE A NOTE OF ACKNOWLEDEMENT OF
 ALL CONDITIONS OR CORRECT.
  
  
 7) SHEET 1.7A - DOOR # 5 WITHIN THE DOOR SCHEDULE
 INDICATES PUSH/PULL/CLOSER BUT DOES NOT A LOCK/LATCH
 NOR INDICATE PANIC HARDWARE.
  
 PER NFPA 101, CH 12 ND CH 7 MEANS OF EGRESS.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT.
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-02-24 Cont ID  
Sent By jesmith Date 2020-02-24 Time 10:43 Rev Time 0.00
Received By jesmith Date 2020-02-24 Time 10:40 Sent To  
Notes
2020-02-24 10:43:03GAS COMMENTS: APPROVED WITH PROVISO
 PLEASE NOTE, GAS SYSTEM, PIPING AND EQUIPMENT IS
 EXISTING WITH NO CHANGES AND IS NOT IN THE SCOPE OF
 WORK. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR FURTHER
 INFORMATION.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-12-31 Cont ID  
Sent By jesmith Date 2019-12-31 Time 14:11 Rev Time 0.00
Received By jesmith Date 2019-12-31 Time 13:31 Sent To  
Notes
2019-12-31 14:11:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS:
 1. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE
 MANUFACTURER SPECIFICATION AND SCHEDULE FOR THE GAS
 TANKLESS WATER HEATERS. INDICATE WHETHER THEY ARE NEW
 OR EXISTING. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) FBC FG
 502 THRU 505.
 2. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE
 MANUFACTURER SPECIFICATION FOR THE COOK LINE EQUIPMENT.
 3. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE
 DETAILED PIPING FLOOR PLAN AND RISER DIAGRAM THAT ARE
 CONSISTENT WITH EACH OTHER. SHOW LOCATION OF EMERGENCY
 SHUT OFF VALVE. IDENTIFY THE APPLIANCES ON THE FLOOR
 PLAN CORRESPONDING WITH THE RISER DIAGRAM. RISER
 DIAGRAM SHOWS TWO WATER HEATERS, FLOOR PLAN SHOWS
 THREE. CLARIFY. SHOW LOCATION OF GAS METER/REGULATOR ON
 THE FLOOR PLAN.
 4. PER WPB FBC 107.2.1 AND 107.3.5.1.5, SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER FBC FG 304.1
 5. RE: GAS LOAD CALCULATIONS; PER WPB FBC 107.2.1 AND
 107.3.5.1.5, LIST THE BTU LOAD OF EACH APPLIANCE AND
 PROVIDE THE QUANTITY OF EACH.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120428 1540 PALM BEACH LAKES BLVD # 100

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-10 Cont ID  
Sent By pvalenti Date 2020-03-10 Time 07:21 Rev Time 0.00
Received By pvalenti Date 2020-03-09 Time 16:05 Sent To  
Notes
2020-03-09 16:06:03ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-07 Time 14:09 Sent To  
Notes
2020-02-10 14:09:35B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-27 Cont ID  
Sent By shill Date 2020-01-07 Time 17:19 Rev Time 0.00
Received By shill Date 2019-12-11 Time 14:43 Sent To  
Notes
2019-12-12 14:42:48B27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By pvalenti Date 2020-03-10 Time 07:17 Rev Time 0.00
Received By pvalenti Date 2020-03-10 Time 07:16 Sent To  
Notes
2020-03-10 07:20:52IMPACT FEES
  
 APPROVED:
  
 PLANS STAMPED BY COUNTY WITH NUMBER MU 2017 28979

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 13:51 Sent To  
Notes
2020-01-07 06:25:50IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By ccole Date 2020-01-06 Time 10:03 Rev Time 0.00
Received By ccole Date 2020-01-06 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-24 Cont ID  
Sent By jesmith Date 2020-02-24 Time 10:40 Rev Time 0.00
Received By jesmith Date 2020-02-24 Time 10:40 Sent To  
Notes
2020-02-24 10:40:22PLUMBING COMMENTS: APPROVED WITH PROVISO
 1. PROVIDE VENT TO BUILDING EXTERIOR TO COMPLY WITH THE
 REQUIREMENTS OF FBC PL 904.1. VENT INSTALLATION SHALL
 COMPLY WITH FBC PL 905.2, 905.3, 905.4, 905.5 AND
 906.1.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, TWO (2) COPIES OF
 MANUFACTURER?S SPECIFICATION/DATA SHEET FOR AN ASSE
 1070 COMPLIANT TANKLESS WATER HEATER.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-31 Cont ID  
Sent By jesmith Date 2019-12-31 Time 13:30 Rev Time 0.00
Received By jesmith Date 2019-12-31 Time 09:20 Sent To  
Notes
2019-12-31 13:30:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 SECTIONS 304 AND 305 INDICATE ON THE FLOOR PLAN TURNING
 SPACES AND CLEAR FLOOR SPACES FOR ALL ACCESSIBLE
 PLUMBING FIXTURES.
 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 SECTIONS 604, 606 AND 305 PROVIDE DETAILS INDICATING
 THE FOLLOWING:
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G. URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP
 MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
 TO THE BACK OF THE FIXTURE PER FBC ACC 605.2
 H. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 3. PLAN SHEET 3.0P SHOWS NEW BAR SANITARY TO CONNECT TO
 EXISTING SANITARY IN WHAT WAS PREVIOUSLY ANOTHER TENANT
 SPACE. EXAMINATION OF THE SANITARY ISOMETRIC ON PLAN
 SHEET 3.1P DOES NOT SHOW ANY BAR EQUIPMENT GOING TO THE
 SANITARY. PER WPB FBC 107.2.1 AND 107.3.5.1.3 PROVIDE
 CLARIFICATION.
 4. PLAN SHEET 3.0P STATES THAT KITCHEN PLUMBING IS
 EXISTING AND TO REMAIN. EXAMINATION OF THE WATER RISER
 ON PLAN SHEET 3.1P INDICATES PIPING THAT IS NOT
 CONSISTENT WITH THAT STATEMENT. THE MOST OUTSTANDING
 EXAMPLE IS THERE ARE TWO GAS TANKLESS WATER HEATERS ON
 THE RISER BUT THREE ON THE FLOOR PLAN. PER WPB FBC
 107.2.1 AND 107.3.5.1.3 PROVIDE DETAILED FLOOR PLAN AND
 RISER DIAGRAMS BOTH SANITARY AND WATER THAT ARE
 CONSISTENT WITH EACH OTHER. SHOW LOCATION AND SIZE OF
 GREASE INTERCEPTORS AND PROVIDE SIZING CALCULATIONS FOR
 GREASE INTERCEPTORS. SHOW WATER SERVICE SIZE AND
 LOCATION WITH BACKFLOW PREVENTER. SHOW CALCULATIONS FOR
 SIZING OF WATER DISTRIBUTION SYSTEM. PLEASE REFER TO
 PERMIT 18040846 RECORD DRAWINGS ON FILE WITH THE CITY
 OF WEST PALM BEACH BUILDING DEPARTMENT WHICH SHOW THE
 RECORDED EXISTING PLUMBING AND GAS WHEN PREPARING YOUR
 CLARIFICATIONS. PROVIDE CLEAR INDICATION AS TO WHAT IS
 EXISTING AND WHAT IS NEW.
 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 SPECIFICATION AND SCHEDULE FOR THE NEW ELECTRIC
 TANKLESS WATER HEATER
 6. PER FBC PL 416.5, TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 SPECIFICATION AND SCHEDULE FOR THE GAS TANKLESS WATER
 HEATERS. INDICATE WHETHER THEY ARE NEW OR EXISTING.
 8. WPB FBC 107.2.1 AND 107.3.5.1.3 REGARDING PLAN SHEET
 1.2A (EQUIPMENT SCHEDULE), PROVIDE ALL PLUMBING
 CONNECTIONS REQUIRED FOR ITEMS 49 THROUGH 55 INCLUDING
 BUT NOT LIMITED TO THE UNDERCOUNTER HAND SINK. INDICATE
 WHICH ITEMS ON THE SCHEDULE ARE EXISTING AND WHICH ARE
 NEW. ADD THE CO2 DISPENSER TO THE SCHEDULE AND PROVIDE
 BACKFLOW PREVENTION FOR THE WATER SUPPLY.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY VERY WELL RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120428 1540 PALM BEACH LAKES BLVD # 100
  