| 2020-01-07 07:37:40 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120428 |
| | ADD: 1540 PALM BEACH LAKES BLVD. SUITE: 100 |
| | CONT: L & L INTERIOR & REMODELING INC. |
| | TEL: 561-686-5853 |
| | E-MAIL: METRODESIGNGROUP.COM |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY JAN. 06/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1.6A/ LIFE SAFETY SHEET: |
| | |
| | 1A) THE LIFE SAFETY NOTE # 11 INDICATES A SIGN WILL BE |
| | PLACED AT ENTRY STATING A MAXIMUM OF 88 OCCUPANTS. WHEN |
| | TOTALING THE INTERIOR SEATING, KITCHEN HELP AND OFFICE |
| | I GET 145 TOTAL OCCUPANTS FOR THE INTERIOR WITH ANOTHER |
| | 24 SEASONAL SEATING. 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1OF THE |
| | ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1B) THE AMOUNT AND LOCATION OF THE EMERGENCY LIGHT |
| | BETWEEN THE LIFE SAFETY PLAN AND 2.1E VARY BETWEEN THE |
| | PLANS, IT WOULD APPEAR ON THE LIFE SAFETY PLAN |
| | ADDITIONAL EMERGENCY BATTERY BACKUP LIGHTS ARE |
| | REQUIRED. 2017 FBC-B SECTION 1008.3.1. IN THE EVENT OF |
| | POWER SUPPLY FAILURE IN ROOMS AND SPACES THAT REQUIRE |
| | TWO OR MORE MEANS OF EGRESS, AN EMERGENCY ELECTRICAL |
| | SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE |
| | FOLLOWING AREAS: 1.AISLES. 2. CORRIDORS. & 3.EXITS. |
| | |
| | 1C) UNDER THE HEADING OF OCCUPANT LOAD THE KITCHEN |
| | OCCUPANT LOAD FACTOR IS TAKEN AT 100 GROSS, PLEASE |
| | REVIEW THE 2017 FBC-B TABLE 1004.1.2 COMMERCIAL KITCHEN |
| | OCCUPANT LOAD FACTOR IS TAKEN AT 200 GROSS OR 1711 S. |
| | F. /200 = 9 OCCUPANTS NOT 18. |
| | |
| | 1D) THE LIFE SAFETY SHEET SHOWS A BAR WITH 10 SEATS AND |
| | AN ACCESSIBLE LOCATION FOR WHEELCHAIR USERS WHICH IS |
| | NOT PART OF THE MAIN BAR AND AWAY BACK IN THE CORNER. |
| | THIS LOCATION IS NOT TO BE CONSIDERED EQUIVALENT |
| | FACILITATION. THE WHEELCHAIR USER IS NOT TO FEEL |
| | SLIGHTED, THE LOCATION IS IN A SERVICE AISLE, NOR CAN A |
| | GUEST OF THE WHEELCHAIR BOUND PERSON BE WITH THEM. 2017 |
| | FBC-ACC. SECTION 103 & 226.2 DISPERSION. DINING |
| | SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902 |
| | SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY |
| | CONTAINING DINING SURFACES AND WORK SURFACES. |
| | |
| | 1E) THE LIFE SAFETY PLAN DOES HAVE ENOUGH ACCESSIBLE |
| | SEATING LOCATIONS, BUT THE LOCATIONS ARE TO BE |
| | DISPERSED THROUGHOUT THE RESTAURANT, THERE ARE NO |
| | ACCESSIBLE SEATING LOCATIONS ON THE EXTERIOR OF THE |
| | BUILDING FOR SEASONAL SEATING. 2017 FBC-ACCESSIBILITY |
| | CODE SECTION 226.2 DISPERSION. DINING SURFACES REQUIRED |
| | TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE |
| | SPACE OR FACILITY CONTAINING DINING SURFACES. |
| | |
| | 1F) THE LIFE SAFETY PLAN SHOWS WHAT APPEARS TO BE 4 |
| | ROUND COLUMNS, SHEET 1.5A HAS TO ELEVATIONS OF THESE |
| | PROPOSED COLUMNS/ PILING/ POST. IN THE DETAILS 2 & 4 OF |
| | THIS PAGE THEY ARE LABELED POST AND PILING, PENETRATE |
| | THE FLOOR BY 2 FEET. IF THESE 4 PILING ARE TO SUPPORT |
| | SOMETHING PLEASE EXPLAIN THEIR USAGE AND HOW THEY ARE |
| | TO BE INSTALLED AND OF WHAT MATERIAL THEY ARE TO BE |
| | MADE FROM. PLEASE ALSO USE THE SAME NOMENCLATURE FOR |
| | DETAILS. IT WOULD APPEAR THE PILING ARE TO SUPPORT THE |
| | BAR JOIST SINCE THEY ARE BEING WELDED TO THE BAR JOIST, |
| | PLEASE EXPLAIN? 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED FOR THE INSTALLATION OF PILING. NO SOILS TEST |
| | WAS SUBMITTED FOR THE COEFFICIENT OF FRICTION SINCE |
| | THERE IS NO FOUNDATION BENEATH THE PILE? |
| | |
| | 1G) THE 4 COLUMNS/ PILING/ POST FOUND ON THE LIFE |
| | SAFETY PLAN SHOWN ON SHEET 1.5A SHOW WELDING TO THE BAR |
| | JOIST PLEASE SHOW COMPLIANCE WITH: |
| | WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | 2) SHEETS 1.3A, 1.4A AND 1.5A BOTH INDICATE A DROPPED |
| | CEILING OVER THE BAR, WITH THE CEILING FINISH BEING |
| | FIRE TREATED T & G. |
| | |
| | 2A) PLEASE PROVIDE THE SYSTEM & MATERIALS USED TO |
| | COMPLETE THIS DROPPED CEILING AND SOFFIT? HOW WILL THE |
| | SYSTEM BE ATTACHED TO THE BAR JOIST, TOP OR BOTTOM BAR |
| | OF THE BAR JOIST? 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 2B) THE PLAN INDICATES THE T & G WILL BE FIRE RETARDANT |
| | TREATED WOOD, WILL THERE BE COMBUSTIBLE FRAMING BEHIND |
| | THE T & G PLANKS? PLEASE PROVIDE COMPLIANCE WITH THE |
| | 2017 FBC-B SECTION: |
| | 803.13.2 SET-OUT CONSTRUCTION. WHERE WALLS AND CEILINGS |
| | ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| | NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| | CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| | IN SECTION 803.13.1, CLASS A FINISH MATERIALS, IN |
| | ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE |
| | USED. |
| | EXCEPTIONS: |
| | 1.WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON BOTH |
| | SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION 903.3.1.1 OR 903.3.1.2. |
| | 2.WHERE INTERIOR FINISH MATERIALS ARE ATTACHED TO |
| | NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS |
| | SPECIFIED IN SECTION 803.13.1.1. |
| | |
| | 3) THE COVERSHEET C-1UNDERTHE HEADING SCOPE OF WORK |
| | NOTE #6 INDICATES TO RAISE RESTROOM / KITCHEN WALLS |
| | FINISHED TO ROOF DECK. SHEET 1.5A SHOWS ALL INTERIOR |
| | WALLS NOT 1 HOUR FIRE RATED TO HAVE THE DRYWALL STOP |
| | JUST ABOVE THE DROPPED CEILING, WHERE CAN I FIND THE |
| | WALL ILLUSTRATION FORM NOTE # 6. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4) SHEET 1.6A SHOWS THE WAITING AREA WITH 120 SQ. FT. / |
| | 5= 24 OCCUPANTS. PLEASE SHOW COMPLIANCE WITH THE 2017 |
| | FBC-B. WHERE PERSONS ARE ADMITTED TO THE BUILDING AT |
| | TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL |
| | BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE, |
| | PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH |
| | UPON THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE |
| | MEANS OF EGRESS. SUCH FOYER, IF NOT DIRECTLY CONNECTED |
| | TO A PUBLIC STREET BY ALL THE MAIN ENTRANCES OR EXITS, |
| | SHALL HAVE A STRAIGHT AND UNOBSTRUCTED CORRIDOR OR PATH |
| | OF TRAVEL TO EVERY SUCH MAIN ENTRANCE OR EXIT. FBC-B |
| | 1029.4. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |