| 2020-01-03 10:29:35 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19120396 |
| | REVIEWED: JANUARY 3, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | - PLEASE ADD SIGNATURE OF RESPONSIBLE PARTY TO ALL |
| | PLANS. ALSO, PROVIDE A SECOND SET OF PLANS. |
| | |
| | 2) 107.5.3 FBC[AMENDED] ADD CODE EDITION TO STATE |
| | CURRENT BUILDING CODE THAT APPLIES TO NEW WORK. (2017 |
| | FLORIDA BUILDING CODE 6TH EDITION) |
| | - |
| | |
| | 3) 107.3.5 FBC[AMENDED]DEMO SHEET A-001. |
| | - SHOW AREA WHERE DEMO OR IN-FILL IS OCCURING. FOR |
| | EXAMPLE THE MASTER BEDROOM WALL LOOKS LIKE IT IS BEING |
| | REMOVED TO ADD A ADDITIONAL FRENCH DOORS. HIGHLIGHT |
| | SECTION OF WALL TO REMOVE, ADD NOTE AND PROVIDE DETAIL |
| | OF HOW THE STRUCTURE ABOVE IS SUPPORTED. |
| | |
| | 4) 107.3.5 FBC[AMENDED]DEMO SHEET A-001. |
| | - PROVIDE DETAILS OF HOW WALL IS BEING IN-FILLED AND |
| | HOW OPENINGS ARE BEING ENLARGED TO ACCOMMODATE NEW |
| | WINDOWS. |
| | |
| | 5) 107.3.5 FBC[AMENDED]DEMO SHEET A-001. |
| | - IS THERE ANY WORK PERFORMED IN THE AREA LABELED |
| | EFFICIENCY? IF NO WORK IS BEING PERFORMED IN THE |
| | EFFICIENCY, HATCH THAT AREA AND STATE NO WORK BEING |
| | PERFORMED. |
| | |
| | 6) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE |
| | METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | - WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA COMPLIANCE OR PERFORMANCE) |
| | |
| | 7) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | - IF WORK AREA COMPLIANCE PLEASE ADD LEVEL OF |
| | ALTERATION TO DESIGN DATA. THIS WOULD BE A LEVEL 3 |
| | ALTERATION. |
| | |
| | 8) R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | - SHOW LOCATIONS OF SMOKE ALARMS TO MEET REQUIREMENTS |
| | FOR NEW CONSTRUCTION. |
| | |
| | R314.3 FBC[R] LOCATION. SMOKE ALARMS SHALL BE INSTALLED |
| | IN THE FOLLOWING LOCATIONS: |
| | |
| | A. IN EACH SLEEPING ROOM. |
| | |
| | B. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | |
| | C. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | D. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3. |
| | |
| | R314.3.1 FBC[R] INSTALLATION NEAR COOKING APPLIANCES. |
| | SMOKE ALARMS SHALL NOT BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS UNLESS THIS WOULD PREVENT PLACEMENT OF A |
| | SMOKE ALARM IN A LOCATION REQUIRED BY SECTION R314.3. |
| | |
| | A. IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED LESS |
| | THAN 20 FEET (6096 MM) HORIZONTALLY FROM A PERMANENTLY |
| | INSTALLED COOKING APPLIANCE. |
| | |
| | B. IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING |
| | SWITCH SHALL NOT BE INSTALLED LESS THAN 10 FEET (3048 |
| | MM) HORIZONTALLY FROM A PERMANENTLY INSTALLED COOKING |
| | APPLIANCE. |
| | |
| | C. PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED |
| | LESS THAN 6 FEET (1828 MM) HORIZONTALLY FROM A |
| | PERMANENTLY INSTALLED COOKING APPLIANCE. |
| | |
| | R314.4 FBC[R] INTERCONNECTION. WHERE MORE THAN ONE |
| | SMOKE ALARM IS REQUIRED TO BE INSTALLED WITHIN AN |
| | INDIVIDUAL DWELLING UNIT IN ACCORDANCE WITH SECTION |
| | R314.3, THE ALARM DEVICES SHALL BE INTERCONNECTED IN |
| | SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL |
| | ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL DWELLING |
| | UNIT. PHYSICAL INTERCONNECTION OF SMOKE ALARMS SHALL |
| | NOT BE REQUIRED WHERE LISTED WIRELESS ALARMS ARE |
| | INSTALLED AND ALL ALARMS SOUND UPON ACTIVATION OF ONE |
| | ALARM. EXCEPTION: INTERCONNECTION OF SMOKE ALARMS IN |
| | EXISTING AREAS SHALL NOT BE REQUIRED WHERE ALTERATIONS |
| | OR REPAIRS DO NOT RESULT IN REMOVAL OF INTERIOR WALL OR |
| | CEILING FINISHES EXPOSING THE STRUCTURE, UNLESS THERE |
| | IS AN ATTIC, CRAWL SPACE OR BASEMENT AVAILABLE THAT |
| | COULD PROVIDE ACCESS FOR INTERCONNECTION WITHOUT THE |
| | REMOVAL OF INTERIOR FINISHES. |
| | |
| | R314.5 FBC[R] COMBINATION ALARMS. COMBINATION SMOKE AND |
| | CARBON MONOXIDE ALARMS SHALL BE PERMITTED TO BE USED IN |
| | LIEU OF SMOKE ALARMS. |
| | |
| | 9) R315.1.1 FBC[R] CARBON MONOXIDE ALARM. THE |
| | REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY |
| | PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS: |
| | |
| | A. A HARD-WIRED CARBON MONOXIDE ALARM. |
| | |
| | B. A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| | |
| | C. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| | ALARM. |
| | |
| | D. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| | SMOKE ALARM. |
| | |
| | R315.1.2 FBC[R] COMBINATION ALARMS. COMBINATION |
| | SMOKE/CARBON MONOXIDE ALARMS SHALL BE LISTED AND |
| | LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | |
| | 10) R609.7.2.1 MASONRY, CONCRETE OR OTHER STRUCTURAL |
| | SUBSTRATE. WHERE THE WOOD SHIM OR BUCK THICKNESS IS |
| | LESS THAN 11/2 INCHES (38 MM), WINDOW AND GLASS DOOR |
| | ASSEMBLIES SHALL BE ANCHORED THROUGH THE JAMB, OR BY |
| | JAMB CLIP AND ANCHORS SHALL BE EMBEDDED DIRECTLY INTO |
| | THE MASONRY, CONCRETE OR OTHER SUBSTANTIAL SUBSTRATE |
| | MATERIAL. ANCHORS SHALL ADEQUATELY TRANSFER LOAD FROM |
| | THE WINDOW OR DOOR FRAME INTO THE ROUGH OPENING |
| | SUBSTRATE [SEE FIGURES R609.7.2(1) AND R6097.2(2)]. |
| | - PROVIDE DETAIL OF DOOR/WINDOW BUCK. |
| | |
| | WHERE THE WOOD SHIM OR BUCK THICKNESS IS 11/2 INCHES |
| | (38 MM) OR MORE, THE BUCK IS SECURELY FASTENED TO THE |
| | MASONRY, CONCRETE OR OTHER SUBSTANTIAL SUBSTRATE, AND |
| | THE BUCK EXTENDS BEYOND THE INTERIOR FACE OF THE WINDOW |
| | OR DOOR FRAME, WINDOW AND GLASS DOOR ASSEMBLIES SHALL |
| | BE ANCHORED THROUGH THE JAMB, OR BY JAMB CLIP, OR |
| | THROUGH THE FLANGE TO THE SECURED WOOD BUCK. ANCHORS |
| | SHALL BE EMBEDDED INTO THE SECURED WOOD BUCK TO |
| | ADEQUATELY TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME |
| | ASSEMBLY [SEE FIGURES R609.7.2(3), R6097.2(4) AND |
| | R609.7.2(5)]. |
| | - PROVIDE DETAIL OF WINDOW INSTALL, OR REFER TO PRODUCT |
| | APPROVAL INSTALLATION INSTRUCTIONS. |
| | |
| | 11) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | |
| | 12) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT |
| | ARE PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| | R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| | R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5 |
| | |
| | 13) 807.2 FBC[E]NEW STRUCTURAL ELEMENTS. NEW STRUCTURAL |
| | ELEMENTS IN ALTERATIONS, INCLUDING CONNECTIONS AND |
| | ANCHORAGE, SHALL COMPLY WITH THE FLORIDA BUILDING CODE, |
| | BUILDING. |
| | |
| | 14) PROVIDE WINDOW AND DOOR SCHEDULES TO SHOW WINDOW |
| | LOCATIONS AND SIZES. SCHEDULE CAN CORESPOND WITH MARKS |
| | ON PLAN VIEW. |
| | |
| | 15) 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS. |
| | |
| | 16) ASCE 7-10 26.7.1 PLEASE ADD PROJECT DATA TO PLANS. |
| | OCCUPANCY = R3 |
| | TYPE OF WALL CONSTRUCTION = ARE THE WALLS MASONRY, |
| | CONCRETE OR WOOD FRAMED? |
| | RISK CATEGORY = II |
| | EXPOSURE CATEGORY = B |
| | BUILDING CLASSIFICATION = ENCLOSED |
| | MEAN BLDG. HGT. = 0?-0? THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| | PEAK. |
| | WIND SPEED V ULT = 170 |
| | WIND SPEED V ASD = 132 |
| | ALSO, STATE THE EXISTING SQ. FOOTAGE CONDITIONED AND |
| | NON CONDITIONED. STATE THE NEW SQ. FOOTAGE CONDITIONED |
| | AND NON CONDITIONED. |
| | |
| | 17) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | FOR WINDOWS, MULL BETWEEN FRENCH DOORS AND DOORS. |
| | - THE NOA'S ARE LISTED ON THE SALES SHEETS, BUT WE NEED |
| | THE ACTUAL NOA'S PRINTED OUT WITH TWO COPIES. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |