Plan Review Details - Permit 19120396
Plan Review Stops For Permit 19120396
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By cpuell Date 2021-08-11 Time 13:08 Rev Time 0.00
Received By cpuell Date 2021-08-11 Time 13:08 Sent To  
Notes
2021-08-11 13:09:20WHICH UNIT IS THE WORK TO BE DONE ON, NORTH OR SOUTH?
 THE NORTH UNIT HAS A HALF ADDRESS WHICH WILL NEED TO BE
 READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6559 TO READDRESS THE
 HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-10 Cont ID  
Sent By rmcphers Date 2020-08-10 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 15:28 Sent To  
Notes
2020-08-10 08:01:51SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED EXTERIOR WALL
 INFILL DETAILS FROM AN ARCHITECT OR ENGINEER FBC
 R301.1.3 (SHOW THE WIND DESIGN CRITERIA ON THE DETAILS
 FBC R301.2.1)
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR THE
 EXTERIOR WALL INFILL ON THE DETAILS FBC R301.2.1
 3) SMOKE DETECTORS ARE REQUIRED OUTSIDE OF EACH BEDROOM
 AREA SUCH AS 1 IN THE HALLWAY AND 1 IN THE LIVING ROOM
 PER FBC R314.3(2).
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ENGINEER OR ARCHITECT DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY
 HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST
 FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT
 OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY E MAILING [email protected] AND ASKING FOR THE FORM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By dbattles Date 2020-01-03 Time 10:29 Rev Time 0.00
Received By dbattles Date 2020-01-03 Time 08:07 Sent To  
Notes
2020-01-03 10:29:35BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120396
 REVIEWED: JANUARY 3, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 - PLEASE ADD SIGNATURE OF RESPONSIBLE PARTY TO ALL
 PLANS. ALSO, PROVIDE A SECOND SET OF PLANS.
  
 2) 107.5.3 FBC[AMENDED] ADD CODE EDITION TO STATE
 CURRENT BUILDING CODE THAT APPLIES TO NEW WORK. (2017
 FLORIDA BUILDING CODE 6TH EDITION)
 -
  
 3) 107.3.5 FBC[AMENDED]DEMO SHEET A-001.
 - SHOW AREA WHERE DEMO OR IN-FILL IS OCCURING. FOR
 EXAMPLE THE MASTER BEDROOM WALL LOOKS LIKE IT IS BEING
 REMOVED TO ADD A ADDITIONAL FRENCH DOORS. HIGHLIGHT
 SECTION OF WALL TO REMOVE, ADD NOTE AND PROVIDE DETAIL
 OF HOW THE STRUCTURE ABOVE IS SUPPORTED.
  
 4) 107.3.5 FBC[AMENDED]DEMO SHEET A-001.
 - PROVIDE DETAILS OF HOW WALL IS BEING IN-FILLED AND
 HOW OPENINGS ARE BEING ENLARGED TO ACCOMMODATE NEW
 WINDOWS.
  
 5) 107.3.5 FBC[AMENDED]DEMO SHEET A-001.
 - IS THERE ANY WORK PERFORMED IN THE AREA LABELED
 EFFICIENCY? IF NO WORK IS BEING PERFORMED IN THE
 EFFICIENCY, HATCH THAT AREA AND STATE NO WORK BEING
 PERFORMED.
  
 6) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA COMPLIANCE OR PERFORMANCE)
  
 7) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 - IF WORK AREA COMPLIANCE PLEASE ADD LEVEL OF
 ALTERATION TO DESIGN DATA. THIS WOULD BE A LEVEL 3
 ALTERATION.
  
 8) R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 - SHOW LOCATIONS OF SMOKE ALARMS TO MEET REQUIREMENTS
 FOR NEW CONSTRUCTION.
  
 R314.3 FBC[R] LOCATION. SMOKE ALARMS SHALL BE INSTALLED
 IN THE FOLLOWING LOCATIONS:
  
 A. IN EACH SLEEPING ROOM.
  
 B. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 C. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 D. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 R314.3.1 FBC[R] INSTALLATION NEAR COOKING APPLIANCES.
 SMOKE ALARMS SHALL NOT BE INSTALLED IN THE FOLLOWING
 LOCATIONS UNLESS THIS WOULD PREVENT PLACEMENT OF A
 SMOKE ALARM IN A LOCATION REQUIRED BY SECTION R314.3.
  
 A. IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED LESS
 THAN 20 FEET (6096 MM) HORIZONTALLY FROM A PERMANENTLY
 INSTALLED COOKING APPLIANCE.
  
 B. IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING
 SWITCH SHALL NOT BE INSTALLED LESS THAN 10 FEET (3048
 MM) HORIZONTALLY FROM A PERMANENTLY INSTALLED COOKING
 APPLIANCE.
  
 C. PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED
 LESS THAN 6 FEET (1828 MM) HORIZONTALLY FROM A
 PERMANENTLY INSTALLED COOKING APPLIANCE.
  
 R314.4 FBC[R] INTERCONNECTION. WHERE MORE THAN ONE
 SMOKE ALARM IS REQUIRED TO BE INSTALLED WITHIN AN
 INDIVIDUAL DWELLING UNIT IN ACCORDANCE WITH SECTION
 R314.3, THE ALARM DEVICES SHALL BE INTERCONNECTED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL
 ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL DWELLING
 UNIT. PHYSICAL INTERCONNECTION OF SMOKE ALARMS SHALL
 NOT BE REQUIRED WHERE LISTED WIRELESS ALARMS ARE
 INSTALLED AND ALL ALARMS SOUND UPON ACTIVATION OF ONE
 ALARM. EXCEPTION: INTERCONNECTION OF SMOKE ALARMS IN
 EXISTING AREAS SHALL NOT BE REQUIRED WHERE ALTERATIONS
 OR REPAIRS DO NOT RESULT IN REMOVAL OF INTERIOR WALL OR
 CEILING FINISHES EXPOSING THE STRUCTURE, UNLESS THERE
 IS AN ATTIC, CRAWL SPACE OR BASEMENT AVAILABLE THAT
 COULD PROVIDE ACCESS FOR INTERCONNECTION WITHOUT THE
 REMOVAL OF INTERIOR FINISHES.
  
 R314.5 FBC[R] COMBINATION ALARMS. COMBINATION SMOKE AND
 CARBON MONOXIDE ALARMS SHALL BE PERMITTED TO BE USED IN
 LIEU OF SMOKE ALARMS.
  
 9) R315.1.1 FBC[R] CARBON MONOXIDE ALARM. THE
 REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
  
 A. A HARD-WIRED CARBON MONOXIDE ALARM.
  
 B. A BATTERY-POWERED CARBON MONOXIDE ALARM.
  
 C. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
  
 D. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 R315.1.2 FBC[R] COMBINATION ALARMS. COMBINATION
 SMOKE/CARBON MONOXIDE ALARMS SHALL BE LISTED AND
 LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 10) R609.7.2.1 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE. WHERE THE WOOD SHIM OR BUCK THICKNESS IS
 LESS THAN 11/2 INCHES (38 MM), WINDOW AND GLASS DOOR
 ASSEMBLIES SHALL BE ANCHORED THROUGH THE JAMB, OR BY
 JAMB CLIP AND ANCHORS SHALL BE EMBEDDED DIRECTLY INTO
 THE MASONRY, CONCRETE OR OTHER SUBSTANTIAL SUBSTRATE
 MATERIAL. ANCHORS SHALL ADEQUATELY TRANSFER LOAD FROM
 THE WINDOW OR DOOR FRAME INTO THE ROUGH OPENING
 SUBSTRATE [SEE FIGURES R609.7.2(1) AND R6097.2(2)].
 - PROVIDE DETAIL OF DOOR/WINDOW BUCK.
  
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS 11/2 INCHES
 (38 MM) OR MORE, THE BUCK IS SECURELY FASTENED TO THE
 MASONRY, CONCRETE OR OTHER SUBSTANTIAL SUBSTRATE, AND
 THE BUCK EXTENDS BEYOND THE INTERIOR FACE OF THE WINDOW
 OR DOOR FRAME, WINDOW AND GLASS DOOR ASSEMBLIES SHALL
 BE ANCHORED THROUGH THE JAMB, OR BY JAMB CLIP, OR
 THROUGH THE FLANGE TO THE SECURED WOOD BUCK. ANCHORS
 SHALL BE EMBEDDED INTO THE SECURED WOOD BUCK TO
 ADEQUATELY TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME
 ASSEMBLY [SEE FIGURES R609.7.2(3), R6097.2(4) AND
 R609.7.2(5)].
 - PROVIDE DETAIL OF WINDOW INSTALL, OR REFER TO PRODUCT
 APPROVAL INSTALLATION INSTRUCTIONS.
  
 11) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
  
 12) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT
 ARE PART OF THE ALTERATION SHALL COMPLY WITH SECTION
 R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH
 R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5
  
 13) 807.2 FBC[E]NEW STRUCTURAL ELEMENTS. NEW STRUCTURAL
 ELEMENTS IN ALTERATIONS, INCLUDING CONNECTIONS AND
 ANCHORAGE, SHALL COMPLY WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 14) PROVIDE WINDOW AND DOOR SCHEDULES TO SHOW WINDOW
 LOCATIONS AND SIZES. SCHEDULE CAN CORESPOND WITH MARKS
 ON PLAN VIEW.
  
 15) 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS.
  
 16) ASCE 7-10 26.7.1 PLEASE ADD PROJECT DATA TO PLANS.
 OCCUPANCY = R3
 TYPE OF WALL CONSTRUCTION = ARE THE WALLS MASONRY,
 CONCRETE OR WOOD FRAMED?
 RISK CATEGORY = II
 EXPOSURE CATEGORY = B
 BUILDING CLASSIFICATION = ENCLOSED
 MEAN BLDG. HGT. = 0?-0? THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF
 PEAK.
 WIND SPEED V ULT = 170
 WIND SPEED V ASD = 132
 ALSO, STATE THE EXISTING SQ. FOOTAGE CONDITIONED AND
 NON CONDITIONED. STATE THE NEW SQ. FOOTAGE CONDITIONED
 AND NON CONDITIONED.
  
 17) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR WINDOWS, MULL BETWEEN FRENCH DOORS AND DOORS.
 - THE NOA'S ARE LISTED ON THE SALES SHEETS, BUT WE NEED
 THE ACTUAL NOA'S PRINTED OUT WITH TWO COPIES.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-20 Cont ID  
Sent By fgiaquin Date 2020-07-20 Time 20:52 Rev Time 0.00
Received By fgiaquin Date 2020-07-20 Time 19:48 Sent To  
Notes
2020-07-20 20:48:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS NOT SIGNED BY ELECTRICAL CONTRACTOR
 QUALIFIER PER LAST PLAN REVIEW COMMENTS. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. FEEDER SIZE FROM 200AMP SERVICE DISCONNECT MB PANEL
 TO NEW 200A MB PANEL IS OF INSUFFICIENT SIZE. NEC
 240.4B, NEC 315.B7(2)
  
 3. SHOW LOCATION OF EXISTING SERVICE ON ELECTRICAL PLAN
 AND SHOW LOCATION OF NEW INTERIOR 200A MB PANEL. FBC
 107.2.1
  
 4. SERVICE RISER DIAGRAM SHOWS A PARALLEL PATH TO
 EARTH. THERE IS A GEC IN BOTH METERCAN AND SERVICE DISC
 MEANS. PROVIDE CORRECTION. NEC 250.24A1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By jleahy Date 2019-12-24 Time 11:34 Rev Time 0.00
Received By jleahy Date 2019-12-24 Time 11:34 Sent To  
Notes
2019-12-24 11:35:49FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLAN NEEDS TO BE SIGNED
  
 2) ALL NEW LIGHTING? PANEL SCHEDULE REQUIRED
  
 3) RISER DIAGRAM SHOWING LOCATION OF PANEL AND MAIN.
  
 4) NEW AC REQUIRES A LOAD CALCULATION FOR SERVICE SIZE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By lcrespo Date 2020-07-27 Time 10:28 Rev Time 0.00
Received By lcrespo Date 2020-07-27 Time 10:28 Sent To  
Notes
2020-07-27 10:56:5807/27/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM, WHAT IS THE DRYERS, STOVE AND
 HEATER, LABEL ON ISOMETRIC. REFER TO THE 2017 FBC-RES.
 SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 5. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS AND OR
 INSTALLATION INSTRUCTIONS FOR THE GAS DRYER, HEATER AND
 STOVE. THE GAS APPLIANCE SHALL BE LISTED AND LABELED
 PER THE 2017 FBC FG RES. SEC. G2404.3. THE
 MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT
 ARE BEING EXHAUSTED BY THE DRYER AND BTU FOR EACH
 APPLIANCE.
  
 6. A SUB GAS PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT STOVE,
 TANKLESS AND DRYER) TO VERIFY COMPLIANCE WITH 2017 FBC
 RES. SEC. G2408.1.
  
 8. PLACE A NOTE ON BOTH SETS OF PLANS LISTING THE
 SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT
 WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.3.
  
 9. LABEL SHUTOFF VALVE, DRIP LEG, REGULATOR AND UNIONS
 ON GAS ISOMERIC PER THE 2017 FBC RES. SEC. G2401.1.3.
  
 10. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLANS THIS A 2 LBS SYSTEM OR .5 LBS SYSTEM (12?
 W.C.) PLEASE LABEL ON ISOMETRIC PER THE WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 11. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 12. MOST TANKLESS UNITS CALL FOR 10.5? WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS AND STROVE) OR
 2017 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 14. IF LOUVER ARE BEING USED FOR COMBUSTION AIR PLEASE
 SHOW THE SIZE OF THE LOUVER(S) AND LOCATION ON THE
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 16. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-10 Cont ID  
Sent By rmcphers Date 2020-08-10 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2020-07-08 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-06 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-10 Time 14:52 Sent To  
Notes
2019-12-11 14:53:03R10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-07-13 Cont ID  
Sent By hmoser Date 2020-07-13 Time 13:12 Rev Time 0.00
Received By hmoser Date 2020-07-13 Time 11:39 Sent To  
Notes
2020-07-13 13:12:24PLAN DENIED
 1) PROVIDE DUCT SIZE, GRILL SIZE AND CFM ON ALL SUPPLY
 DUCT AND
 GRILL SIZE AND DUCT SIZE ON ALL RETURN AIR DUCT.SECTION
 107 FBC 2017
 2) PLEASE PROVIDE MORE INFORMATION ON AIR CONDITIONING
 EQUIPMENT
 IF EXISTING MARK EXISTING ON PLAN BY EQUIPMENT. IF NEW
 EQUIPMENT
 PROVIDE EQUIPMENT SCHEDULE ON PLAN.SECTION 107 FBC 2017
 3) PROVIDE EXHAUST FOR BATHROOMS TABLE M1507.4
 RESIDENTIAL CODE 2017
 4) RETURN AIR IS NOT REQUIRED IN LAUNDRY ROOMS OR
 CLOSETS SECTION M 1602.3
 BALANCED RETURN AIR EXCEPTION # 3 RESIDENTIAL CODE 2017
 5) PROVIDE MASTER RETURN AIR FOR AIR CONDITIONING 1 AND
 2
 6) SIGNATURE IS REQUIRED ON THE PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By ccole Date 2020-01-06 Time 14:31 Rev Time 0.00
Received By ccole Date 2020-01-06 Time 14:31 Sent To I
Notes
2020-01-06 14:50:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120396
 1/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIX COPIES OF AN ARCHITECTURAL FLOOR PLAN DRAWING
 HAVE BEEN MARKED UP IN PENCIL AND SUBMITTED EACH
 BEARING SHEET NUMBER A-001. PLANS DRAWN IN PENCIL ARE
 NOT ACCEPTABLE, AND EACH PLAN SHEET SHALL BE NUMBERED
 DIFFERENTLY- SECTION 107.2.1 WPB.
  
 2) THE SUBMITTED MECHANICAL PLAN HAS NUMEROUS
 DEFICIENCIES.THE RESUBMITTED, CORRECTED MECHANICAL PLAN
 SHALL BE DRAWN LEGIBLY, SHALL BEAR THE SIGNATURE OF THE
 PERSON WHO PREPARED THE DRAWING- SECTION 107.2.1 WPB.
 PLEASE INCLUDE THE FOLLOWING INFORMATION AND DETAILS ON
 THE DRAWINGS:
  
 A) A CLEARLY WRITTEN SCOPE OF WORK FOR MECHANICAL
 ALTERATIONS. IT APPEARS ALL NEW SYSTEMS AND DUCTWORK
 HAVE BEEN INSTALLED- SECTION 107.2.1.2 WPB.
  
 B) SUPPLY AND RETURN DUCT SIZES- SECTION M1601.1 &
 M1602.3 FBC RES.
  
 C) DIFFUSER AND RETURN GRILL SIZES AND CFMS BEING
 SUPPLIED AT EACH DIFFUSER- SECTION M1601.1 FBC RES.
  
 D) AC EQUIPMENT SCHEDULES- M1401.3 FBC RES.
  
 E) AIR HANDLER AND CONDENSER LOCATIONS AND INSTALLATION
 DETAILS- M1401.1 & M1305.1.4.1 FBC RES.
  
 F) CONDENSATE DISPOSAL DETAILS- PRIMARY CONDENSATE
 PIPING RUNS AND DISCHARGE LOCATIONS. SECONDARY
 CONDENSATE DISPOSAL DETAILS- SECTION M1411.3.1 FBC RES
  
 3) SUBMIT AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH ACCA MANUAL J- SECTION R403.6.1 FBC EC.
  
 4) SUBMIT AHRI CERTIFICATES FOR THE NEW AC SYSTEMS-
 SECTION R501.7 FBC EC.
  
 5) A FL. LICENSED MECHANICAL CONTRACTOR SHALL SUBMIT A
 SUB-PERMIT FOR THE WORK PER FL. STATUE 489. PLEASE NOTE
 THAT ANY PERSON INSTALLATING OR SERVICING AC EQUIPMENT
 SHALL BE EPA CERTIFIED TO HANDLE REFRIGERANTS- SECTION
 608 USEPA.
  
 6) IT APPEARS FLEX DUCTS MAY BE INSTALLED IN THE GARAGE
 WHICH IS NOT ALLOWED PER SECTION R302.5.2 FBC RES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-07-27 Cont ID  
Sent By lcrespo Date 2020-07-27 Time 10:28 Rev Time 0.00
Received By lcrespo Date 2020-07-27 Time 10:28 Sent To  
Notes
2020-07-27 10:28:2107/27/20 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SCOPE OF WORK IS NOT CLEAR OF WHAT IS BEING DONE ON
 YOU PLUMBING PAGE. PLEASE GIVE A DESCRIPTIVE NARRATIVE
 OF WHAT IS IN AND WHAT IS BEING REPLACED PER THE FBC
 WPB A 101.2.
 2. A SUB PLUMBING PERMIT IS REQUIRED FOR THE SCOPE OF
 WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
 3. PLUMBING RISER DIAGRAM REQUIRED, PLEASE SHOW VENTS
 THROUGH ROOF, CLEAN OUT OUTSIDE BUILDING AND PIPE SIZES
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11)
 RESIDENTIAL PLUMBING.
 4. A STOVE IS SHOWN ON PLANS IS IT GAS, PLEASE LABEL IF
 IT IS, A PERMIT ALONG WITH AN EVALUATION IS REQUIRED IS
 USING GAS AS THE CITY DOES NOT SHOW A PERMIT ON FILE
 FOR GAS PER THE 2017 FBC WPB A 107.1.
 5. CLEAN-OUT OUTSIDE OF BUILDING SHALL BE WITHIN 10'
 FOR EACH ENTRANCE IN ITS OWN SYSTEM PLEASE SHOW
 DISTANCE AND CLEAN OUTS AS ONE IS MISSING ON GUEST BATH
 PER THE 2017 FBC R3005.2.3.
 6. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-16 Cont ID  
Sent By lcrespo Date 2019-12-16 Time 07:29 Rev Time 0.00
Received By lcrespo Date 2019-12-16 Time 06:24 Sent To  
Notes
2019-12-16 07:29:3412/16/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SCOPE OF WORK IS NOT CLEAR OF WHAT IS BEING DONE ON
 YOU PLUMBING PAGE. PLEASE GIVE A DESCRIPTIVE NARRATIVE
 OF WHAT IS IN AND WHAT IS BEING REPLACED PER THE FBC
 WPB A 101.2.
 2. IN TITLE PLEASE SHOW THE CODE YEAR OR REFENCE TO
 WHICH YOU ARE REGULATING AS IT SHALL BE KNOWN AS THE
 FLORIDA BUILDING CODE HEREINAFTER REFERRED TO AS "THIS
 CODE" PER THE FBC WPB A 101.1.
 3. A SUB PLUMBING PERMIT IS REQUIRED FOR THE SCOPE OF
 WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
 4. PLUMBING RISER DIAGRAM REQUIRED WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING.
 5. A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN
 PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE
 DRAWING CAN BE MODIFIED/CHANGED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS.
 6. YOU HAVE SUBMITTED ONLY ONE SET OF PLANS, TWO PLANS
 ARE REQUIRED PER THE FBC WPB A 107.1.
 7. PLEASE SHOW HOT WATER HEATING EQUIPMENT ON PLUMBING
 PAGE AND IF YOU ARE USING A ANY TYPE OF GAS EQUIPMENT
 PLEASE NOTE ON PLANS AND SUBMIT MANUFACTURES
 SPECIFICATION FOR THEM PER THE 2017 FBC R 2722.2.
 8. A GAS STOVE IS SHOWN ON PLANS A GAS PERMIT ALONG
 WITH AN EVALUATION IS REQUIRED IS USING GAS AS THE CITY
 DOES NOT SHOW A PERMIT ON FILE FOR GAS PER THE 2017 FBC
 WPB A 107.1.
 9. CLEAN-OUT OUTSIDE OF BUILDING SHALL BE WITHIN 10'
 PLEASE SHOW DISTANCE PER THE 2017 FBC R3005.2.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By rmcphers Date 2020-08-10 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2020-08-10 Time 08:07 Sent To  
Notes
2020-08-10 08:08:56SIGNED AND SEALED DRAWINGS AND DOCUMENTS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. DRAWINGS AND DOCUMENTS DO NOT SHOW IN "ADOBE
 READER" AS DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF
 YOUR ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC
 OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.