Plan Review Details - Permit 19120391
Plan Review Stops For Permit 19120391
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By cpuell Date 2020-03-23 Time 14:50 Rev Time 0.00
Received By cpuell Date 2020-03-23 Time 14:50 Sent To  
Notes
2020-03-23 14:51:21ADDRESS CHANGED TO 4850 RYNA GREENBAUM DR - MAIN
 ENTRANCE FROM THE EXISTING BUILDING, NO NEW ADDRESS
 NEEDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-05-13 Cont ID  
Sent By shill Date 2020-05-13 Time 10:56 Rev Time 0.00
Received By shill Date 2020-05-13 Time 10:56 Sent To  
Notes
2020-05-13 10:58:16***REMOVED PROVISO #2; APPLICANT ELECTED TO UTILIZE
 CITY INSPECTORS, SENT EMAIL CORRESPONDENCE BETWEEN JIM
 WITMER AND ANTHONY MAROTTA TO PERMIT RECORD**
 S.HILL 561-805-6724 [email protected]
  
  
  
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120391
 ADD: 4850 FRED GLADSTONE DR.
 CONT: THE WHITING-TURNER CO.
 TEL: 954-536-9251
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 4TH REVIEW
 DATE: MON. MAY 04TH/2020
 ACTION: BUILDING PROVISO
  
 1) PROVISO: ART IN PUBLIC PLACES.
  
 2) PROVISO RESIDENT INSPECTOR FORMS TO BE SUBMITTED TO
 THE BUILDING DEPARTMENT, REVIEWED AND APPROVED . THE
 RESPONSE LETTER INDICATES THE CONTRACTOR WOULD LIKE TO
 USE A RESIDENT INSPECTOR FOR THIS PROJECT. FORMS FOR A
 RESIDENT INSPECTOR ARE TO BE FILED OUT AND RETURNED TO
 WEST PALM BEACH CITY HALL AND PUT ATTENTION TO SAMANTHA
 HILL AND OR DYLAN BATTLES. THANK YOU FOR YOUR HELP IN
 THIS MATTER. FORMS ARE TO BE E-MAILED TO:
  
 [email protected] SENT: 4/13/2020
 12:22 PM.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-05-04 Cont ID  
Sent By jwitmer Date 2020-05-04 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2020-05-04 Time 07:48 Sent To  
Notes
2020-05-04 08:22:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120391
 ADD: 4850 FRED GLADSTONE DR.
 CONT: THE WHITING-TURNER CO.
 TEL: 954-536-9251
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 4TH REVIEW
 DATE: MON. MAY 04TH/2020
 ACTION: BUILDING PROVISO
  
 1) PROVISO: ART IN PUBLIC PLACES.
  
 2) PROVISO RESIDENT INSPECTOR FORMS TO BE SUBMITTED TO
 THE BUILDING DEPARTMENT, REVIEWED AND APPROVED . THE
 RESPONSE LETTER INDICATES THE CONTRACTOR WOULD LIKE TO
 USE A RESIDENT INSPECTOR FOR THIS PROJECT. FORMS FOR A
 RESIDENT INSPECTOR ARE TO BE FILED OUT AND RETURNED TO
 WEST PALM BEACH CITY HALL AND PUT ATTENTION TO SAMANTHA
 HILL AND OR DYLAN BATTLES. THANK YOU FOR YOUR HELP IN
 THIS MATTER. FORMS ARE TO BE E-MAILED TO:
  
 [email protected] SENT: 4/13/2020
 12:22 PM.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-04-13 Cont ID  
Sent By jwitmer Date 2020-04-13 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2020-04-13 Time 09:32 Sent To  
Notes
2020-04-13 11:54:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120391
 ADD: 4850 FRED GLADSTONE DR.
 CONT: THE WHITING-TURNER CO.
 TEL: 954-536-9251
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 3RD REVIEW
 DATE: MON.APRIL 13TH/2020
 ACTION: DENIED
  
 1) PROVISO: ART IN PUBLIC PLACES.
  
 2) COMPLIED. ADJUSTED PERMIT VALUE TO $2,384,500.00.
  
 3) SEMI-COMPLIED. HE RESPONSE LETTER INDICATES THE
 CONTRACTOR WOULD LIKE TO USE A RESIDENT INSPECTOR FOR
 THIS PROJECT. FORMS FOR A RESIDENT INSPECTOR ARE TO BE
 FILED OUT AND RETURNED TO WEST PALM BEACH CITY HALL AND
 PUT ATTENTION TO SAMANTHA HILL AND OR DYLAN BATTLES.
 THANK YOU FOR YOUR HELP IN THIS MATTER. FORMS ARE TO BE
 E-MAILED TO:
  
 [email protected] SENT: 4/13/2020
 12:22 PM.
  
 4) COMPLIED. SOILS REPORT DATED 08/14/19 BY TERRACON.
  
 5)COMPLIED. NO ACTION REQUIRED. SHEET S-4 WIND
 PRESSURES ARE GOOD FOR ROOF ZONES FOR FLAT 1,2,3,
 SLOPED 6,7,8 AND WALL ZONES 4 & 5.
  
 6A-C) COMPLIED. PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING TO BE 107.3.4.2 DEFERRED SUBMITTALS.
  
 7) 3RD REQUEST, SEMI-COMPLIED. THIS REVIEW THE S SHEETS
 S-6, S-7 & S-8 NOW INDICATE 5/8 INCH PLYWOOD OVER FIRE
 RETARDANT TREATED METAL DECKING! THE ARCHITECTURAL
 SHEETS HAVE BEEN CORRECTED. THE STRUCTURAL SHEETS S-6,
 S-7 & S-8 ALL SLOPED ROOF SECTIONS STILL SHOW THE USE
 OF 5/8 INCH CDX PLYWOOD. PLEASE REFER BACK TO THE 2017
 FBC-B SECTION 603.1.1.1.3 ROOF CONSTRUCTION INCLUDING
 GIRDERS, TRUSSES FRAMING & DECKING NEED TO BE
 FIRE-RETARDANT TREATED WOOD. THIS IS FOR BOTH TYPE I &
 TYPE II CONSTRUCTION. SECTION 718.5 FOR CONCEALED
 SPACES, EXCEPTION 1 REFERS BACK TO COMBUSTIBLE
 MATERIALS IN ACCORDANCE WITH SECTION 603.
  
 8-13) COMPLIED.
  
 14) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jwitmer Date 2020-03-12 Time 11:42 Rev Time 0.00
Received By jwitmer Date 2020-03-12 Time 08:39 Sent To  
Notes
2020-03-12 11:42:112017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120391
 ADD: 4850 FRED GLADSTONE DR.
 CONT: THE WHITING-TURNER CO.
 TEL: 954-536-9251
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2ND REVIEW
 DATE: THURS. MARCH 12TH/2020
 ACTION: DENIED
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) RESPONSE IS THE CONTRACTOR TO PROVIDE. THE PERMIT
 APPLICATION INDICATES THE DOLLAR AMOUNT OF
 $2,500,000.00 DOLLARS IN VALUE. THIS MAIN BUILDING
 PERMIT WILL INCLUDE THE FEES FOR THE MECHANICAL,
 ELECTRICAL, PLUMBING & ROOFING PERMITS. WHEN THE
 GENERAL CONTRACTOR COMES IN FOR A BUILDING PERMIT WITH
 THE SIGNED PERMIT APPLICATION FORM BY THE QUALIFIER AND
 OWNER AND BRINGS IN THE LISTED SUB-PERMITS M-E-P &
 ROOFING PERMITS SIGNED BY THE QUALIFIER OF EACH
 COMPANY, THEIR INSURANCES AND LICENSURE UP TO DATE, THE
 M-E-P AND ROOFING PERMITS ARE FREE OF CHARGE. IF THE
 M-E-P & ROOFING PERMITS COME IN LATER THERE WILL BE AN
 $80.00 ADMINISTRATIVE FEE FOR EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) RESPONSE IS CONTRACTOR TO PROVIDE DIRECTION. THIS
 BUILDING DOES NOT QUALIFY AS A THRESHOLD BUILDING BUT
 COULD BE CONSIDERED FOR THE RESIDENT INSPECTOR PROGRAM
 UNDER SECTION 110.3.9 OF THE WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, 6TH EDITION (2017)
 CHAPTER 1 OF THE ADMINISTRATION CODE. THE ALTERNATIVE
 IS USING THE CITY INSPECTORS FOR INSPECTIONS, I?VE
 SPOKEN KEN CONRAD CHIEF BUILDING INSPECTOR IF HE HAD
 ANY PREFERENCE. IF THE CONTRACTOR WAS PUSHED WITH
 MULTIPLE BUILDING INSPECTIONS EACH DAY BECAUSE OF TIME
 CONSTRAINTS THE RESIDENT INSPECTOR MAYBE PREFERRED. IF
 YOU WOULD PREFER TO USE THE CITY INSPECTORS FOR THE
 STRUCTURAL PORTION OF THE BUILDING PLEASE REVIEW THE
 LIMITATIONS OF OUR STAFF FOR WELDED OR BOLTED
 CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 FOR THESE TYPES OF CONNECTIONS A 3RD PARTY
 CERTIFICATION WOULD BE REQUIRED. IF THERE IS ANY
 QUESTIONS ABOUT THE CODE REQUIREMENTS FOR THIS SECTION,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666. PLEASE LET US KNOW YOUR INTENTIONS, IF
 YOU DECIDE TO USE A RESIDENT INSPECTOR WE WILL SEND THE
 FORMS TO YOU BY E-MAIL, WE JUST NEED TO KNOW YOUR
 INTENTIONS. THANK YOU.
  
 4) COMPLIED. SOILS REPORT DATED 08/14/19 BY TERRACON.
  
 5)COMPLIED. NO ACTION REQUIRED. SHEET S-4 WIND
 PRESSURES ARE GOOD FOR ROOF ZONES FOR FLAT 1,2,3,
 SLOPED 6,7,8 AND WALL ZONES 4 & 5.
  
 6A-C) COMPLIED. PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING TO BE 107.3.4.2 DEFERRED SUBMITTALS.
  
 7) 2ND REQUEST, SEMI-COMPLIED. THE ARCHITECTURAL SHEETS
 HAVE BEEN CORRECTED. THE STRUCTURAL SHEETS S-6, S-7 &
 S-8 ALL SLOPED ROOF SECTIONS STILL SHOW THE USE OF 5/8
 INCH CDX PLYWOOD. PLEASE REFER BACK TO THE 2017 FBC-B
 SECTION 603.1.1.1.3 ROOF CONSTRUCTION INCLUDING
 GIRDERS, TRUSSES FRAMING & DECKING NEED TO BE
 FIRE-RETARDANT TREATED WOOD. THIS IS FOR BOTH TYPE I &
 TYPE II CONSTRUCTION. SECTION 718.5 FOR CONCEALED
 SPACES, EXCEPTION 1 REFERS BACK TO COMBUSTIBLE
 MATERIALS IN ACCORDANCE WITH SECTION 603.
  
 8) SEMI-COMPLIED. THERE STILL IS AN ISSUE WITH HOW THE
 DESIGNER OF RECORD IS GETTING THE 2 HOUR FIRE RATING
 FOR THE CEILING. SEE COMMENT # 9 ON THE FIRE RATING OF
 CEILING.
 ORIGINAL COMMENT. SHEET A-5.2 WALL SECTION B, THE LIFE
 SAFETY SHEET DECLARES THIS SECTION OF THE ADDITION AS
 TYPE I-B CONSTRUCTION. IN THE 2017 FBC-B TABLE 601 FOR
 TYPE I-B CONSTRUCTION, THE ROOF CONSTRUCTION AND
 ASSOCIATED SECONDARY MEMBERS REQUIRES A 1 HOUR FIRE
 RATING OF THE LIGHT GAUGE METAL TRUSSES BEING INSTALLED
 IN THIS AREA.
  
 9) 2ND REQUEST. SHEET A5.2 DETAIL A HAS A NOTE WITHIN
 THE DETAIL REV. # 1, FOR A 2 HOUR FIRE RATED CEILING
 CONSTRUCT PER UL DESIGN U-450. REFER TO P-9 ON SHEET
 A-9 FOR ADDITIONAL INFORMATION. SHEET A9 HAS NOT BEEN
 REVISED, NO REVISION MARKER IN DETAIL # 5 P-9, STILL
 SHOWS UL DESIGN U415 SYSTEM B. PLEASE NOTE UL U-450
 WILL NOT WORK EITHER, IN BOTH CASES THESE ARE VERTICAL
 WALL PARTITIONS. THEY WERE TESTED IN THE VERTICAL
 POSITION, NEVER INTENDED TO BE USED LAID ON ITS SIDE.
 THE INTENT IS TO MAKE A 2 HOUR FIRE ASSEMBLY
 (HORIZONTAL FIRE BARRIER) FROM THE CEILING ASSEMBLY.
 THE FIRE BARRIER WOULD NEED TO SHOW COMPLIANCE WITH
 707.5 CONTINUITY. SUCH FIRE BARRIERS SHALL BE
 CONTINUOUS THROUGHOUT THE CONCEALED SPACE, SUCH AS
 ABOVE A SUSPENDED CEILING. THE UL ASSEMBLY HAS TO BE
 TESTED FOR IN THE END USE. A WALL ASSEMBLY CANNOT BE
 PUT ON ITS SIDE AND SAY THAT IT IS AN EQUIVALENT. CALL
 UL ON THAT ONE, THEY WILL NOT STAND BEHIND AN ASSEMBLY
 IF IT HAS NOT BEEN TESTED FOR THE TYPE OF END USE AS
 DESCRIBED FOR U-415 OR U-450 WALL ASSEMBLIES.
 ORIGINAL COMMENT. SHEET A-5.2 WALL SECTION B HAS A NOTE
 FOR THE 2 HOUR RATED CEILING SEE A-9.0 DETAIL # 5. THIS
 DETAIL IS FOR A 2 HOUR FIRE RATED SHAFT WALL DESIGN, UL
 DESIGN U-415 SYSTEM B. THIS SYSTEM U-415 IS A TESTED
 WALL ASSEMBLY, TO BE USED VERTICALLY, THAT IS HOW IT
 WAS TESTED. YOU WILL NEED TO FIND A CEILING ASSEMBLY
 WITH A 2 HOUR FIRE RATING.
  
 10) SEMI-COMPLIED. SUBMITTED FOR THIS REVIEW IS THE
 ESR-1172 REPORT FOR THE USE OF 500 SPRAY-APPLIED
 POLYURETHANE FOAM SPRAY. INCLUDED WITH THE REPORT IS A
 DESCRIPTION FOR DC 315 INTRUMESCENT COATINGS TO GO
 ALONG WITH THE USE OF THE FOAM SPRAY FOAM. WHAT IS
 MISSING IS THE ERS 3702 SHOWING THE TESTING AND USE FOR
 THE DC 315 INTRUMESCENT COATING. SHOW COMPLIANCE WITH
 2603.4.1.6 FOAM PLASTICS SHALL BE PROTECTED AGAINST
 IGNITION.
  
 ORIGINAL COMMENT. SHEET A-5.2 DETAIL B INDICATES THE
 INSTALLATION OF ICYNENE SPRAY INSULATION. PLEASE SUBMIT
 THE ICC-ES OR ERS REPORT AND CIRCLE WHICH APPLICATION
 WILL BE USED SEE 4.0 DESIGN AND INSTALLATION. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED. SHOW COMPLIANCE
 WITH 2603.4.1.6 ATTICS, THE FOAM INSULATION SHALL BE
 PROTECTED AGAINST IGNITION. THIS BARRIER IS TO COVER
 THE FOAM INSULATION.
  
 11) RESPONSE INDICATES SEE THE HEIGHT OF THE
 MID-LANDING SHEET A8.0 DETAIL A. THE FLOOR PLAN A1.0
 STATES THE STAGE IS 1-0 FOOT HIGHER THAN THE FLOOR
 LEVEL OF THE AUDITORIUM. THE 2 DETAILS ARE NOT CLEAR AS
 TO THE TOTAL DIFFERENCE IN HEIGHT FOR THE MID-LANDING,
 IN NEITHER DETAIL A OR B DOES THE PLAN INDICATE THIS IS
 FINISH FLOOR OR HEIGHT OF THE FLOOR STAGE? THE 3 ?
 INCHES + 8 ? INCHES MAKES UP ONE FOOT BUT THERE IS NO
 REFERENCE TO FINISH FLOOR STAGE AND FINISH FLOOR FOR
 FLOOR LEVEL, IT IS CONFUSING. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. THANK YOU FOR THE HELP ON THIS
 ONE.
 ORIGINAL COMMENT. SHEET A-1.0 SHOWS THE STAGE 1 FOOT
 HIGHER THAN THE FLOOR AUDITORIUM. IT APPEARS IN THE
 DETAIL 7/ A-8.1 THE STAGE IS CONCRETE BASED. NEITHER
 THE ARCHITECTURAL NOR STRUCTURAL SHEETS PROVIDE THE
 HEIGHT OF THE MID-LANDING OF THE ACCESSIBLE RAMP. 2017
 FBC-ACCESSIBILITY CODE SECTION 405.2. RAMP RUNS SHALL
 HAVE A SLOPE NOT STEEPER THAN 1:12.
  
 12) 2ND REQUEST. SHEET A6.3, DETAIL 3A & 3B PANTRY WALL
 104 WITH A MICROWAVE ON A SHELF. THE TOP OF THE SHELF
 IS AT 48 INCHES ABOVE THE FLOOR. CALIBRATE THE PLANS
 AND AS SHOWN ON THE PLAN THE MICROWAVE DOES NOT MEET
 THE REACH RANGES FOR OPERABLE PARTS OR REACH RANGES.
 MUST COMPLY WITH THE 2017 ACCESSIBILITY CODE SECTIONS:
 12A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 12B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 13) FOR THE 2ND REVIEW CYCLE THE ENERGY REPORT WAS
 SUBMITTED.
  
 13A) SHEET 27 OF 27 STATES THE ROOF SYSTEM HAS AN R
 VALUE OF 30.3. I DIDN?T SEE WHERE THE ENERGY REPORT
 PROVIDED THE BREAK DOWN OF HOW THE R-30.3 WAS ACHIEVED
 FOR THE VARIOUS ROOF TYPES. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 13B) PAGE 27/27 ALSO STATES 1058 SOLID CORE FLUSH DOORS
 AS 2.25 SOLID CORE DOORS. NONE OF THE DOORS IN THE DOOR
 SCHEDULE ON SHEET A7.0 SHOW 2.25 INCH SOLID CORE DOORS
 ON THE EXTERIOR OF THE BUILDING.
  
 14) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-28 Cont ID  
Sent By jwitmer Date 2020-01-28 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2020-01-28 Time 06:04 Sent To  
Notes
2020-01-28 12:54:082017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120391
 ADD: 4850 FRED GLADSTONE DR.
 CONT: THE WHITING-TURNER CO.
 TEL: 954-536-9251
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: TUES. JAN. 28TH/2020
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) THE PERMIT APPLICATION INDICATES THE DOLLAR AMOUNT
 OF $2,500,000.00 DOLLARS IN VALUE. THIS MAIN BUILDING
 PERMIT WILL INCLUDE THE FEES FOR THE MECHANICAL,
 ELECTRICAL, PLUMBING & ROOFING PERMITS. WHEN THE
 GENERAL CONTRACTOR COMES IN FOR A BUILDING PERMIT WITH
 THE SIGNED PERMIT APPLICATION FORM BY THE QUALIFIER AND
 OWNER AND BRINGS IN THE LISTED SUB-PERMITS M-E-P &
 ROOFING PERMITS SIGNED BY THE QUALIFIER OF EACH
 COMPANY, THEIR INSURANCES AND LICENSURE UP TO DATE, THE
 M-E-P AND ROOFING PERMITS ARE FREE OF CHARGE. IF THE
 M-E-P & ROOFING PERMITS COME IN LATER THERE WILL BE AN
 $80.00 ADMINISTRATIVE FEE FOR EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) THIS BUILDING DOES NOT QUALIFY AS A THRESHOLD
 BUILDING BUT COULD BE CONSIDERED FOR THE RESIDENT
 INSPECTOR PROGRAM UNDER SECTION 110.3.9 OF THE WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, 6TH
 EDITION (2017) CHAPTER 1, ADMINISTRATION CODE. THE
 ALTERNATIVE IS USING THE CITY INSPECTORS FOR
 INSPECTIONS, I?VE SPOKEN KEN CONRAD CHIEF BUILDING
 INSPECTOR IF HE HAD ANY PREFERENCE. IF THE CONTRACTOR
 WAS PUSHED WITH MULTIPLE BUILDING INSPECTIONS EACH DAY
 BECAUSE OF TIME CONSTRAINTS THE RESIDENT INSPECTOR
 MAYBE PREFERRED. IF YOU WOULD PREFER TO USE THE CITY
 INSPECTORS FOR THE STRUCTURAL PORTION OF THE BUILDING
 PLEASE REVIEW THE LIMITATIONS OF OUR STAFF FOR WELDED
 OR BOLTED CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 FOR THESE TYPES OF CONNECTIONS A 3RD PARTY
 CERTIFICATION WOULD BE REQUIRED. IF THERE IS ANY
 QUESTIONS ABOUT THE CODE REQUIREMENTS FOR THIS SECTION,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666. PLEASE LET US KNOW YOUR INTENTIONS, IF
 YOU DECIDE TO USE A RESIDENT INSPECTOR WE WILL SEND THE
 FORMS TO YOU BY E-MAIL, WE JUST NEED TO KNOW YOUR
 INTENTIONS. THANK YOU.
  
 4) SHEET S-3 UNDER THE HEADING FOUNDATION NOTE 1.A
 INDICATES THERE IS A SOILS REPORT DATED 08/14/19 BY
 TERRACON. IF THEY CAN UPLOAD THE REPORT WITH ELECTRONIC
 SIGNATURES WITH THE NEXT SUBMITTAL GREAT. IF THEY NEED
 TO SUBMIT PAPER REPORT WITH ORIGINAL SIGNATURE AND SEAL
 THAT WILL WORK ALSO. 2017 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 5) NO ACTION REQUIRED. SHEET S-4 WIND PRESSURES ARE
 GOOD FOR ROOF ZONES FOR FLAT 1,2,3, SLOPED 6,7,8 AND
 WALL ZONES 4 & 5.
  
 6) THIS REVIEW THERE WERE NO PRODUCT APPROVALS
 SUBMITTED. IF EITHER THE DESIGNER OF RECORD OR THE
 GENERAL CONTRACTOR WOULD PREFER TO HAVE THE BAR JOIST &
 PRODUCT APPROVAL FOR COMPONENTS AND CLADDING DEFERRED
 PLEASE NOTE SO FOR THE NEXT SUBMITTAL. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 6B) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6C) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 7) ON BOTH ARCHITECTURAL SHEETS A-5.2 & A-5.3 AND THE
 STRUCTURAL SHEETS S-6, S-7 & S-8 ALL SLOPED ROOF
 SECTIONS SHOW THE USE OF 5/8 INCH CDX PLYWOOD. PLEASE
 REFER BACK TO THE 2017 FBC-B SECTION 603.1.1.1.3 ROOF
 CONSTRUCTION INCLUDING GIRDERS, TRUSSES FRAMING &
 DECKING NEED TO BE FIRE-RETARDANT TREATED WOOD. THIS IS
 FOR BOTH TYPE I & TYPE II CONSTRUCTION. SECTION 718.5
 FOR CONCEALED SPACES, EXCEPTION 1 REFERS BACK TO
 COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION 603.
  
 8) SHEET A-5.2 WALL SECTION B, THE LIFE SAFETY SHEET
 DECLARES THIS SECTION OF THE ADDITION AS TYPE I-B
 CONSTRUCTION. IN THE 2017 FBC-B TABLE 601 FOR TYPE I-B
 CONSTRUCTION, THE ROOF CONSTRUCTION AND ASSOCIATED
 SECONDARY MEMBERS REQUIRES A 1 HOUR FIRE RATING OF THE
 LIGHT GAUGE METAL TRUSSES BEING INSTALLED IN THIS AREA.
  
 9) SHEET A-5.2 WALL SECTION B HAS A NOTE FOR THE 2 HOUR
 RATED CEILING SEE A-9.0 DETAIL # 5. THIS DETAIL IS FOR
 A 2 HOUR FIRE RATED SHAFT WALL DESIGN, UL DESIGN U-415
 SYSTEM B. THIS SYSTEM U-415 IS A TESTED WALL ASSEMBLY,
 TO BE USED VERTICALLY, THAT IS HOW IT WAS TESTED. YOU
 WILL NEED TO FIND A CEILING ASSEMBLY WITH A 2 HOUR FIRE
 RATING.
  
 10) SHEET A-5.2 DETAIL B INDICATES THE INSTALLATION OF
 ICYNENE SPRAY INSULATION. PLEASE SUBMIT THE ICC-ES OR
 ERS REPORT AND CIRCLE WHICH APPLICATION WILL BE USED
 SEE 4.0 DESIGN AND INSTALLATION. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. SHOW COMPLIANCE WITH
 2603.4.1.6 ATTICS, THE FOAM INSULATION SHALL BE
 PROTECTED AGAINST IGNITION. THIS BARRIER IS TO COVER
 THE FOAM INSULATION.
  
 11) SHEET A-1.0 SHOWS THE STAGE 1 FOOT HIGHER THAN THE
 FLOOR AUDITORIUM. IT APPEARS IN THE DETAIL 7/ A-8.1 THE
 STAGE IS CONCRETE BASED. NEITHER THE ARCHITECTURAL NOR
 STRUCTURAL SHEETS PROVIDE THE HEIGHT OF THE MID-LANDING
 OF THE ACCESSIBLE RAMP. 2017 FBC-ACCESSIBILITY CODE
 SECTION 405.2. RAMP RUNS SHALL HAVE A SLOPE NOT STEEPER
 THAN 1:12.
  
 12) SHEET A-1. SHOWS A DETAIL 3A & 3B /A-6.3 PANTRY
 WALL 104 WITH A MICROWAVE ON A SHELF. THE TOP OF THE
 SHELF IS AT 48 INCHES ABOVE THE FLOOR. MUST COMPLY WITH
 THE 2017 ACCESSIBILITY CODE SECTIONS:
  
 12A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 12B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 13) THIS REVIEW CYCLE THERE WAS NO ENERGY CODE REPORTS
 SUBMITTED. 2017 FBC-ENERGY CODE. C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 14) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-08 Cont ID  
Sent By jleahy Date 2020-05-08 Time 12:31 Rev Time 0.00
Received By jleahy Date 2020-05-08 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By jleahy Date 2020-03-10 Time 14:50 Rev Time 0.00
Received By jleahy Date 2020-03-10 Time 14:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-15 Cont ID  
Sent By jleahy Date 2020-01-15 Time 14:12 Rev Time 0.00
Received By jleahy Date 2020-01-15 Time 11:23 Sent To  
Notes
2020-01-16 13:18:41FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.2 SEVERAL GFCI PROTECTED OUTLETS ARE NOTED ON
 PLANS
  
 PAGE E5.1 GROUND SHOWN FOR TRANSFORMER GOING TO AV
 RACK, IS THIS WHERE YOU ARE PICKING UP YOUR GEC OR ARE
 YOU RUNNING IT TO THE AV RACK?
 TRANSFORMER NEEDS GEC
  
 PAGE E5.2, AND E5.3 AV, LOW VOLTAGE AND FIRE ALARM WILL
 REQUIRE SEPARATE PERMIT AND PLANS.
  
 PAGE E-7 LIGHTNING PROTECTION NEEDS A PERMIT AND PLANS
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2020-03-16 Cont ID  
Sent By rrossano Date 2020-03-16 Time   Rev Time 0.00
Received By rrossano Date 2020-03-16 Time   Sent To I
Notes
2020-03-16 08:46:31REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E20010004.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By rrossano Date 2020-02-04 Time   Rev Time  
Received By rrossano Date 2020-02-04 Time   Sent To  
Notes
2020-02-04 07:54:53PLEASE ADDRESS ZONING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-05-01 Cont ID  
Sent By pleduc Date 2020-05-01 Time   Rev Time 0.00
Received By pleduc Date 2020-05-01 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-04-13 Cont ID  
Sent By pleduc Date 2020-04-13 Time   Rev Time 0.00
Received By pleduc Date 2020-04-09 Time 09:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-02 Cont ID  
Sent By pleduc Date 2020-03-02 Time   Rev Time 0.00
Received By pleduc Date 2020-03-02 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-14 Cont ID  
Sent By pleduc Date 2020-01-14 Time   Rev Time 0.00
Received By pleduc Date 2020-01-09 Time 15:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-05-11 Cont ID  
Sent By lmarchan Date 2020-05-11 Time 13:23 Rev Time 0.00
Received By lmarchan Date 2020-04-30 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-14 Cont ID  
Sent By lmarchan Date 2020-04-14 Time 08:27 Rev Time 0.00
Received By lmarchan Date 2020-04-08 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-23 Cont ID  
Sent By cpuell Date 2020-03-23 Time 14:51 Rev Time 0.00
Received By cpuell Date 2020-02-27 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-05 Cont ID  
Sent By lmarchan Date 2020-02-05 Time 16:52 Rev Time 0.00
Received By lmarchan Date 2019-12-17 Time 09:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-04-17 Cont ID  
Sent By lmarchan Date 2020-04-17 Time 10:35 Rev Time 0.00
Received By lmarchan Date 2020-04-16 Time 08:50 Sent To  
Notes
2020-04-17 10:36:03NO FEES DUE
2020-04-16 08:50:414/16/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-28 Cont ID  
Sent By jwitmer Date 2020-01-28 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2020-01-28 Time 06:04 Sent To  
Notes
2020-01-28 12:54:42DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-05-06 Cont ID  
Sent By ccole Date 2020-05-06 Time 15:54 Rev Time 0.00
Received By ccole Date 2020-05-05 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-04-09 Cont ID  
Sent By ccole Date 2020-04-09 Time 15:54 Rev Time 0.00
Received By ccole Date 2020-04-09 Time 13:13 Sent To  
Notes
2020-04-09 16:42:083RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19120391
 4/9/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2 & M0.3: THE AC CALCULATIONS ARE
 INDICATING THE SPACES REQUIRE 389.0 MBH COOLING, 40 KW
 HEATING, AND 8207 CFMS OF COOLING AIRFLOW. THE AHU AND
 VAV SCHEDULES INDICATE THE COOLING, HEATING, AND
 AIRFLOW CAPACITIES ARE DEFICIENT- 315.0 MBH, 27.3 KW,
 AND 7800 CFMS. PLEASE PROVIDE AN EXPLANATION FOR THE
 DEFICIENCIES- SECTION 312.1 FBC M, AND SECTION C403.2.1
 FBC EC.
  
 2) M0.2: I HAVE REVIEWED THE LETTER CONCERNING THE
 PROPOSED REDUCTION IN OUTDOOR VENTILATION AIR BASED ON
 USING THE CALCULATED EGRESS LOAD OF THE AUDITORIUM
 VERSUS THE CALULATED LOAD AS REQUIRED PER TABLE
 403.3.1.1 FBC M, AND IN THE PROCESS NOTICED A
 DEFICIENCY IN THE LOBBY WHICH IS BEING CALCULATED AS AN
 OFFICE LOBBY RATHER THAN AN AUDITORIUM OR THEATRE LOBBY
 PER TABLE 403.3.1.1. PLEASE CORRECT THE CALCULATIONS
 ACCORDINGLY.
 CONCERNING THE LETTER, WHAT EVIDENCE IS BEING PROVIDED
 TO SUPPORT THE STATEMENT THAT THE REDUCTION OF
 VENTILATION AIR REQUIRED FOR 526 OCCUPANTS DOWN TO THE
 REQUIREMENT FOR 256 OCCUPANTS "WOULD SATISFY THE INTENT
 OF THE CODE FOR THE HEALTH AND COMFORT OF EACH OCCUPANT
 WHILE BEING MINDFUL OF ENERGY CONSERVATION".
 CONSIDERING THAT THE THE VENTILATION TABLES IN THE FBC
 M ARE BASED ON THE TABLES IN ASHRAE 62.1, AND YOUR
 ENERGY CALCULATIONS ARE USING A METHOD FROM ASHRAE
 90.1, WOULD THERE BE ANY ALTERNATE VENTILATION METHOD
 IN THOSE STANDARDS, OR SOME OTHER ACCEPTABLE STANDARDS
 THAT WOULD SUPPORT THIS STATEMENT? THE 1ST REVIEW
 COMMENT #8 PRINTED BELOW WILL STILL APPLY AT THIS TIME.
  
 3) M1: PLEASE SHOW THE LOCATIONS OF THE THERMOSTATS FOR
 THE LOBBY, THE STAGE AREA AND TB-1 & 5- SECTION
 C403.2.4.1 FBC EC.
  
 4) M1: SHOW THE LOCATIONS OF THE CO2 SENSORS- SECTION
 107.2.1 WPB. PLEASE NOTE THAT THE SENSORS SHALL BE
 INSTALLED PER MANUFACTURER'S SPECS. THE SPECS CAN BE
 SUBMITTED PRIOR TO PERMIT ISSUANCE OR DEFERRED.
  
 5) M1 & A2: PLEASE INDICATE THE HEIGHT OF THE TB ACCESS
 PANELS FROM THE FINISH FLOOR- SEE SECTION 306.5 FBC M.
  
 COMMENTS #8 & 9 FROM THE 1ST REVIEW WILL REMAIN AT THIS
 TIME PENDING MORE INFORMATION. PLEASE NOTE THE
 ENGINEERING FOR THE CHILLER MAY BE A DEFFERED
 SUBMITTAL.
  
 8) M2: THE VENTILATION CALCULATIONS FOR AUDITORIUM ARE
 INCORRECT. TABLE 403.3.1.1 FBC M REQUIRES 150 PERSONS
 PER 1000 SF.
  
 9) PROVIDE ENGINEERING FOR INSTALLATION OF THE CHILLER-
 SECTION 301.15 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-23 Cont ID  
Sent By shill Date 2020-03-23 Time 13:43 Rev Time 0.00
Received By shill Date 2020-03-23 Time 10:25 Sent To  
Notes
2020-03-23 10:25:54COMMENTS FROM PREVIOUS REVIEW:
  
 1) JLRD RESPONSE THAT HEATING AND COOLING CALCULATIONS
 WOULD BE PROVIDED IS NOT SATISFIED AS I DID NOT FIND
 THESE CALCULATIONS IN THE UPLOADED INFORMATION. 2017
 FLORIDA ENERGY CODE C403.2.1
 3) JLRD RESPONSE THAT CX PLAN WILL PROVIDED ONCE CX
 AGENT IS SELECTED NEEDS TO IDENTIFY ON THE MECHANICAL
 DRAWINGS PER 2017 FLORIDA ENERGY CODE C408.2
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-14 Cont ID  
Sent By ccole Date 2020-01-14 Time 16:42 Rev Time 0.00
Received By ccole Date 2020-01-14 Time 16:42 Sent To  
Notes
2020-01-14 17:06:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120391
 1/14/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTIONS
 C101.2, C101.5.1 AND C401.2 FBC EC.
  
 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC EC. SUBMIT A COMMISSIONING PLAN
 AS OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN
 SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY
 OF THE COMMISSIONING REPORT SHALL BE SUBMITTED FOR
 REVIEW AT FINAL INSPECTION.
  
 4) M1 & M2: CORRECT THE M5 REFERENCE FOR THE MECHANICAL
 ROOM TO M2 SECTION 107.2.1 WPB.
  
 5) M1: PROVIDE A DUCT SMOKE DETECTOR SYMBOL IN THE
 SUPPLY SYSTEM OF AHU-1- SECTION 606.2.1 FBC M.
  
 6) M1: SHOW RETURN AIR FROM STORAGE ROOMS 103 & 105-
 SECTION 601.6 FBC M.
  
 7) M1: EXHAUST VENTILATION IS REQUIRED FOR THE DRESSING
 ROOM AT A RATE OF 0.25 CFMS PER SF.- TABLE 403.3.1.1
 FBC M.
  
 8) M2: THE VENTILATION CALCULATIONS FOR AUDITORIUM ARE
 INCORRECT. TABLE 403.3.1.1 FBC M REQUIRES 150 PERSONS
 PER 1000 SF.
  
 9) PROVIDE ENGINEERING FOR INSTALLATION OF THE CHILLER-
 SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-23 Cont ID  
Sent By shill Date 2020-01-23 Time 08:28 Rev Time 0.00
Received By shill Date 2020-01-08 Time 17:34 Sent To  
Notes
2020-01-23 08:29:11REVIEWED REMOTELY BY TIM HUNT
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2020-03-12 Cont ID  
Sent By jwitmer Date 2020-03-12 Time 11:52 Rev Time 0.00
Received By jwitmer Date 2020-03-12 Time 08:54 Sent To  
Notes
2020-03-12 11:52:00THE DESIGNER OF RECORD WISHES TO DEFER THE ROOFING
 PRODUCT APPROVALS UNTIL AFTER PERMIT ISSUANCE. JW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-01-28 Cont ID  
Sent By jwitmer Date 2020-01-28 Time 12:56 Rev Time 0.00
Received By jwitmer Date 2020-01-28 Time 06:04 Sent To  
Notes
2020-01-28 12:56:03THIS REVIEW CYCLE NO ROOFING PRODUCT APPROVAL WAS
 SUBMITTED. SEE BUILDING REVIEW. JIM WITMER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-08 Cont ID  
Sent By jleahy Date 2020-05-08 Time 12:43 Rev Time 0.00
Received By jleahy Date 2020-05-08 Time 12:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By shill Date 2020-03-10 Time 09:28 Rev Time 0.00
Received By shill Date 2020-03-10 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-10 Cont ID  
Sent By shill Date 2020-02-10 Time 08:10 Rev Time 0.00
Received By shill Date 2020-02-10 Time 08:08 Sent To  
Notes
2020-01-13 13:37:14ELECTRICAL SHEETS OK.

Review Stop Z ZONING
Rev No 5 Status P Date 2020-05-11 Cont ID  
Sent By eschneid Date 2020-05-11 Time 11:56 Rev Time 0.25
Received By eschneid Date 2020-05-11 Time 11:50 Sent To  
Notes
2020-05-11 11:56:38SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. PARKING LOT
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2020-04-13 Cont ID  
Sent By eschneid Date 2020-04-13 Time 17:01 Rev Time 0.25
Received By eschneid Date 2020-04-13 Time 16:53 Sent To  
Notes
2020-04-13 17:02:07SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. PARKING LOT
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-03-23 Cont ID  
Sent By eschneid Date 2020-03-23 Time 14:40 Rev Time 1.00
Received By eschneid Date 2020-03-23 Time 10:08 Sent To  
Notes
2020-03-23 14:47:02FAILED
  
 1) PRIOR TO ZONING APPROVAL OF THE BUILDING PERMIT, A
 TREE ALTERATION PERMIT SHALL BE SUBMITTED, REVIEWED AND
 APPROVED BY THE PLANNING DIVISION. NO TREES MAY BE
 REMOVED FROM THE SITE OF THE FUTURE AUDITORIUM WITHOUT
 THE APPROVED TREE ALTERATION PERMIT.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. PARKING LOT
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2020-03-13 Cont ID  
Sent By eschneid Date 2020-03-13 Time 11:45 Rev Time 0.25
Received By eschneid Date 2020-03-13 Time 11:45 Sent To  
Notes
2020-03-13 11:45:40BUILDING DOES NOT YET HAVE SITE PLAN APPROVAL. ZONING
 WILL NOT REVIEW UNTIL IT DOES. THIS DOES NOT COUNT AS A
 REVIEW.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-14 Cont ID  
Sent By eschneid Date 2020-01-14 Time 15:41 Rev Time 0.00
Received By eschneid Date 2020-01-14 Time 15:41 Sent To  
Notes
2020-01-14 15:53:21BUILDING DOES NOT YET HAVE SITE PLAN APPROVAL. ZONING
 WILL NOT REVIEW UNTIL IT DOES. THIS DOES NOT COUNT AS A
 REVIEW.