Plan Review Details - Permit 19120254
Plan Review Stops For Permit 19120254
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-10-05 Cont ID  
Sent By cthroop Date 2020-10-05 Time 10:08 Rev Time 0.00
Received By cthroop Date 2020-10-05 Time 10:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-08-19 Cont ID  
Sent By jwitmer Date 2020-08-19 Time 12:02 Rev Time 0.00
Received By jwitmer Date 2020-08-19 Time 10:59 Sent To  
Notes
2020-08-19 12:01:47CONTRACTOR PLEASE PROVIDE LETTER.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-05-24 Cont ID  
Sent By jwitmer Date 2020-05-24 Time 07:15 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-05-24 07:15:22PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 16:09 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-01-03 16:09:23ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-10-05 Cont ID  
Sent By cthroop Date 2020-10-05 Time 10:36 Rev Time 0.00
Received By cthroop Date 2020-10-05 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-08-19 Cont ID  
Sent By jwitmer Date 2020-08-19 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2020-08-19 Time 11:15 Sent To  
Notes
2020-08-19 11:59:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120254
 ADD: 101 N. CLEMATIS ST. SUITE 417
 CONT: TOWN MANAGEMENT SERVICES
 TEL: 954-292-2956
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. AUGUST 194TH/ 2020
 ACTION: DENIED
  
 1-2) COMPLIED. COMP2ND REVIEW, SEMI-COMPLIED. THE
 SUBMITTED PLANS ARE THE WORK OF EDGAR V. DUENAS P. E. #
 57831. PLEASE NOTE THE SGNATURE AND SEAL ON THESE PLANS
 WOULD BE FOR A PAAER SET OF PLANS, NOT DIGITAL PLANS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1ST ROUND COMMENTS. 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION 107.3.4.3. CERTIFICATION BY CONTRACTOR.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE
 YOU CANNOT CREATE PLANS YOU AREN?T LICENSED IN.
  
  
 3) SEMI-COMPLIED. THIS REVIEW A PROFLEX PRODUCT MSC A
 SALES BROCHURE WAS YP LOADED NOT ACTUAL TEST REPORTS.
 PLEASE NOTE ON THE SALES BROCHURE UNDER THE TEST DATA
 THE RESULTS ARE GIVEN FOR A 8 INCH CONCRETE SLAB WITH
 DROPPED CEILING WITH INSULATION.
  
 THE CITY OF W. P. B. BUILDING DIVISION DOES HAVE ACTUAL
 TEST REPORTS FOR A SIMILAR PROFLEX PRODUCT SUPER SIM 90
 ON A 6 INCH CONCRETE SLAB, NO DROPPED CEILING:
 IIC=50 ASTM -E492
 STC=52 ASTM E-90
 FLAME=0 ASTM E-84
 SMOKE= ASTM E-84
 IF THIS PRODUCTIS SOMETHING YOU WOULD LIKE TO USE STATE
 SO ON THE PLANS, NO TEST REPORTS REQUIRED SINCE THE
 CITY HAS THESE REPORTS.
  
 . SHEET A-1 DOES INDICATE 1/2 INCH DURAROCK TO BE
 SECURED TO THE CONCRETE DECK AND THERE IS A NOTE SEE
 ATTACHMEENTS FOR SOUND PROOFING BUT THERE IS NO FILES
 ATTACHED IN ANY FOLDERS OR TO THE SUBMITTED PLANS. YOU
 MAY WANT TO CALL THE LIBRIAN LAURA MARCHANT TO DISCUSS
 HOW TO ATTACH THESE DOCUMENTS, 561-805-6658.
 THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD AND
 TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR THE
 INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS, WOOD
 AND TILE FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 3A 2ND REQUEST. ) FBC-B 2017 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 3B) 2ND REQUEST. FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2017 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-24 Cont ID  
Sent By jwitmer Date 2020-05-24 Time 07:13 Rev Time 0.00
Received By jwitmer Date 2020-05-24 Time 06:32 Sent To  
Notes
2020-05-24 07:13:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120254
 ADD: 101 N. CLEMATIS ST. SUITE 417
 CONT: TOWN MANAGEMENT SERVICES
 TEL: 954-292-2956
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUNDAY MAY 24TH/ 2020
 ACTION: DENIED
  
 1) 2ND REVIEW, SEMI-COMPLIED. THE SUBMITTED PLANS ARE
 THE WORK OF EDGAR V. DUENAS P. E. # 57831. PLEASE NOTE
 THE SGNATURE AND SEAL ON THESE PLANS WOULD BE FOR A
 PAAER SET OF PLANS, NOT DIGITAL PLANS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1ST ROUND COMMENTS. 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION 107.3.4.3. CERTIFICATION BY CONTRACTOR.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE
 YOU CANNOT CREATE PLANS YOU AREN?T LICENSED IN.
  
 2)2ND REQUEST, SEMI-COMPLIED. FLOOR PLANA1 NOTE 3
 INDICATES MINOR FRAMING. IDENTIFY THE MINIMUM BUILDING
 TYPE OF CONSTRUCTION TABLE 504.3, TABLE 504.4 & 506.2
 OF THE 2017 FBC-B. THERE IS NO PLANS IDENTIFYING THE
 LOCATION OF THE NEW DROPPED CEILINGS ETC. PLEASE
 IDENTIFY THE FRAMING MEMBERS BY USAGE FOR DROPPED
 CEILINGS SIZE OF MATERIAL, C-STUDS, JOIST, TRACK,
 CHANNEL AND OR FURRING CHANNEL (HIGH HAT), GAUGE OF
 MATERIAL/ THICKNESS, FLANGE WIDTH, SPACING C/C, FOR
 WALLS LENGTH OF STUD, AND FOR WALLS THE DEFLECTION
 LIMITATION SEE TABLE 1604.3.OF THE 2017 FBC-B AND
 THICKNESS OF DRYWALL, IS THE WALL FIRE RATED. FOR
 DROPPED CEILINGS AND SOFFITS, TYPE OF MATERIALS
 C-STUDS, JOIST, TRACK, CHANNEL AND OR FURRING CHANNEL
 (HIGH HAT), GAUGE OF MATERIAL/ THICKNESS, FLANGE WIDTH,
 SPACING C/C, SPAN, MID-POINT SUPPORT, THICKNESS OF
 DRYWALL.
  
 3) 2ND REQUEST. SHEET A-1 DOES INDICATE 1/2 INCH
 DURAROCK TO BE SECURED TO THE CONCRETE DECK AND THERE
 IS A NOTE SEE ATTACHMEENTS FOR SOUND PROOFING BUT THERE
 IS NO FILES ATTACHED IN ANY FOLDERS OR TO THE SUBMITTED
 PLANS. YOU MAY WANT TO CALL THE LIBRIAN LAURA MARCHANT
 TO DISCUSS HOW TO ATTACH THESE DOCUMENTS, 561-805-6658.
 THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD AND
 TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR THE
 INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS, WOOD
 AND TILE FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 3A 2ND REQUEST. ) FBC-B 2017 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 3B) 2ND REQUEST. FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2017 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 06:35 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 06:00 Sent To  
Notes
2020-01-06 06:35:152017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120254
 ADD: 101 N. CLEMATIS ST. SUITE 417
 CONT: TOWN MANAGEMENT SERVICES
 TEL: 954-292-2956
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY, JAN.6TH/ 2020
 ACTION: DENIED
  
 1) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION
 107.3.4.3. CERTIFICATION BY CONTRACTOR. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DRAWN THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE YOU CANNOT
 CREATE PLANS YOU AREN?T LICENSED IN.
  
 2) FLOOR PLAN NOTE 3 INDICATES MINOR FRAMING. IDENTIFY
 THE MINIMUM BUILDING TYPE OF CONSTRUCTION TABLE 504.3,
 TABLE 504.4 & 506.2 OF THE 2017 FBC-B. THERE IS NO
 PLANS IDENTIFYING THE LOCATION OF THE NEW FRAMING,
 WALLS, DROPPED CEILINGS ETC. FOR WALLS ARE THEY BEARING
 OR NON-BEARING WALLS. PLEASE IDENTIFY THE FRAMING
 MEMBERS BY USAGE, (WALL OR DROPPED CEILING) SIZE OF
 MATERIAL, C-STUDS, JOIST, TRACK, CHANNEL AND OR FURRING
 CHANNEL (HIGH HAT), GAUGE OF MATERIAL/ THICKNESS,
 FLANGE WIDTH, SPACING C/C, FOR WALLS LENGTH OF STUD,
 AND FOR WALLS THE DEFLECTION LIMITATION SEE TABLE
 1604.3.OF THE 2017 FBC-B AND THICKNESS OF DRYWALL, IS
 THE WALL FIRE RATED. FOR DROPPED CEILINGS AND SOFFITS,
 TYPE OF MATERIALS C-STUDS, JOIST, TRACK, CHANNEL AND OR
 FURRING CHANNEL (HIGH HAT), GAUGE OF MATERIAL/
 THICKNESS, FLANGE WIDTH, SPACING C/C, SPAN, MID-POINT
 SUPPORT, THICKNESS OF DRYWALL.
  
 3) THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD
 AND TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR
 THE INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS,
 WOOD AND TILE FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-10-06 Cont ID  
Sent By ppetty Date 2020-10-06 Time 11:37 Rev Time 0.00
Received By ppetty Date 2020-10-06 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-20 Cont ID  
Sent By ppetty Date 2020-08-20 Time 10:47 Rev Time 0.00
Received By ppetty Date 2020-08-20 Time 10:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-03 Cont ID  
Sent By jpearson Date 2020-06-03 Time 09:50 Rev Time 0.00
Received By jpearson Date 2020-06-03 Time 08:10 Sent To  
Notes
2020-06-03 09:50:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PANEL IS NOT PERMITTED IN BATHROOM OR
 CLOSET. PROVIDE CORRECTION. NEC 240.24(D)(E)
 2. PLAN REFERENCES THE FBC RESIDENTIAL CODE, WHICH IS
 NOT APPLICABLE TO THIS BUILDING. THE 2014 NEC IS TO BE
 USED. PROVIDE CORRECTION. FBC RE R101.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By jpearson Date 2019-12-27 Time 13:09 Rev Time 0.00
Received By jpearson Date 2019-12-27 Time 13:09 Sent To  
Notes
2019-12-27 13:09:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-10-07 Cont ID  
Sent By pleduc Date 2020-10-07 Time   Rev Time 0.00
Received By pleduc Date 2020-10-07 Time 14:39 Sent To  
Notes
2020-10-07 14:39:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-08-13 Cont ID  
Sent By pleduc Date 2020-08-13 Time   Rev Time 0.00
Received By pleduc Date 2020-08-13 Time 13:09 Sent To  
Notes
2020-08-13 13:23:53THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-19 Cont ID  
Sent By pleduc Date 2020-05-19 Time   Rev Time 0.00
Received By pleduc Date 2020-05-19 Time 13:03 Sent To  
Notes
2020-05-19 13:15:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-12-13 Cont ID  
Sent By pleduc Date 2019-12-13 Time   Rev Time 0.00
Received By pleduc Date 2019-12-13 Time 15:14 Sent To  
Notes
2019-12-13 15:20:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF MINOR FRAMING; HOWEVER, IT
 IS UNCLEAR WHERE AND WHAT THE FRAMING IS.
  
 PLEASE PROVIDE GREATER DETAIL.
  
  
 2) IT IS UNCLEAR WHAT IS EXISTING AND WHAT IS NEW.
  
 IT APPEARS THAT THERE IS WORK UNDER THE STAIRWAY. IS
 THIS WORK NEW OR EXISTING?
  
  
 3) THERE IS AN EXISTING FIRE SPRINKLER PROTECTION IN
 THE BUILDING.
  
 THE EXISTING SPRINKLER PROTECTION IN THIS UNIT MAY
 REQUIRE MODIFICATION FOR CODE COMPLIANT COVERAGE.
  
 PLEASE PROVIDE AND APPLICABLE NOTE THAT THE SPRINKLER
 PROTECTION SHALL BE REVIEWED BY A FIRE SPRINKLER
 CONTRACTOR AND THAT ALL SPRINKLER WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-10-08 Cont ID  
Sent By shill Date 2020-10-08 Time 08:26 Rev Time 0.00
Received By shill Date 2020-10-05 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-20 Cont ID  
Sent By ppetty Date 2020-08-20 Time 10:48 Rev Time 0.00
Received By ppetty Date 2020-08-04 Time 10:16 Sent To  
Notes
2020-08-12 18:43:51CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-03 Time   Rev Time 0.00
Received By jgomez Date 2020-05-13 Time 12:40 Sent To  
Notes
2020-05-18 12:15:51CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-06 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-06 Time 14:36 Sent To  
Notes
2019-12-09 14:37:06B11

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-10-05 Cont ID  
Sent By medwards Date 2020-10-05 Time 10:58 Rev Time 0.00
Received By medwards Date 2020-10-05 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-08-14 Cont ID  
Sent By hmoser Date 2020-08-14 Time 08:47 Rev Time 0.00
Received By medwards Date 2020-08-14 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-21 Cont ID  
Sent By hmoser Date 2020-05-21 Time 10:04 Rev Time 0.00
Received By hmoser Date 2020-05-21 Time 08:15 Sent To  
Notes
2020-05-21 10:04:40PLAN DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN FOR NEW AIR
 CONDITIONING.
 SECTION 107 FBC 2017
 2) REFER TO SECTION 307 FBC (M) 2017 SHOW CONDENSATE
 LINE FOR
 AIR CONDITIONING ON PLAN.
 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES EXCEPTION
 #1
 (DRYER SUBDUCT) FBC (M) 2017
 4) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 INCLUDING
 DOORS 2017 FBC(M)
 5) REFER TO SECTION 402 OR 403 FBC(M) 2017 PROVIDE
 CALCULATIONS
 FOR OUTSIDE AIR.
 6) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS. OUTDOOR
 AIR INTAKE
 AND EXHAUST DAMPERS. 2017 FLORIDA ENERGY CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By ccole Date 2019-12-27 Time 08:11 Rev Time 0.00
Received By ccole Date 2019-12-24 Time 15:21 Sent To  
Notes
2019-12-27 08:46:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL PLAN SHOWING ALL ALTERATIONS TO
 THE EXISTING HVAC SYSTEMS. THE DEMO PERMIT #18111262
 INDICATES THAT THE AIR HANDLER AND DRYER HAVE BEEN
 RELOCATED- SECTION 107.2.1 WPB.
  
 A) SHOW POINTS OF AC SUPPLY AND RETURN DUCT CONNECTIONS
 AND NEW DUCT RUNS- SECTION 603 FBC M.
 B) SHOW THE NEW DRYER EXHAUST DUCT RUN AND INDICATE THE
 TOTAL RUN LENGTH- SECTION 504.8.4.FBC M. PLEASE NOTE
 THAT MAKEUP AIR MAY BE REQUIRED- SECTION 504.6.
 C) SHOW NEW O/A DUCT CONNECTION AND REQUIRED DAMPER
 (NOT APPLICABLE IF NATURAL VENTILATION OPENINGS ARE
 BEING USED)- SECTIONS 402 & 403 FBC M, & SECTION
 C403.2.4.3 FBC EC.
 D) SHOW A FRONT VIEW OF THE AIR HANDLER IN THE NEW
 CLOSET INDICATING REQUIRED CLEARANCES AROUND THE UNIT,
 AND NEW CONDENSATE PIPING RUN. PLEASE NOTE THAT IF A
 NEW LOUVERED DOOR IS BEING INSTALLED FOR RETURN AIR, IT
 SHALL BE NONCOMBUSTIBLE- 602.1 FBC M.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER
 PER SECTION 504.1 FBC M, AND THE NEW COOKING
 APPLIANCES- SECTION 917.1 FBC M.
  
 3) SUBMIT MANUFACTUTRER'S SPECIFICATIONS FOR THE
 RECIRCULATING KITCHEN HOOD- SECTION 505.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-10-06 Cont ID  
Sent By ccole Date 2020-10-06 Time 12:22 Rev Time 0.00
Received By ccole Date 2020-10-06 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-14 Cont ID  
Sent By ccole Date 2020-08-14 Time 14:47 Rev Time 0.00
Received By ccole Date 2020-08-14 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-06-01 Cont ID  
Sent By ccole Date 2020-06-01 Time 12:51 Rev Time 0.00
Received By ccole Date 2020-06-01 Time 11:14 Sent To  
Notes
2020-06-01 12:53:222ND REVIEW FBC-2017 PLUMBING
 PERMIT- 19120254
 6/1/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW REQUESTING FAIR
 HOUSING ACT GUIDELINES BATHROOM DESIGN SPECIFICATIONS
 WAS NOT ADDRESSED. AS STATED IN THE COMMENT, BATHROOMS
 CONSTRUCTED UNDER THE FAIR HOUSING ACT SHALL BE
 DESIGNED AS EITHER TYPE A OR B. REVISE THE NOTES AND
 DETAILS ON SHEET A.2/P.1 TO CLARIFY THE SCOPE OF WORK
 PERTAINING TO THE SHOWER IN THE MASTER BATH AND THE NEW
 WATER HEATER. BASED ON THE DEMO PLAN AND THE NEW
 DRAWINGS, THE PROJECT APPEARS TO BE A CONVERSION OF A
 TUB AND SHOWER COMPARTMENT INTO A SHOWER COMPARTMENT,
 AND A NEW WATER HEATER AT A NEW LOCATION.
 FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE
 BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED. THE PLAN IS INDICATING THE CONVERSION OF A
 BATHTUB TO A SHOWER IN THE MASTER BATH. PROVIDE AN
 ENLARGED DIMENSIONED DRAWING OF THE BATHROOM SHOWING
 THE REQUIRED CLEAR FLOOR SPACE DIAGRAM FOR THE NEW
 SHOWER. PLEASE SEE REQUIREMENT 7 CONTAINED IN THE
 GUIDELINES AND FIGURE 5, AND FIGURES 7A, 7C, & 7D FOR
 GUIDANCE. CONCERNING THE SHOWER GRAB BAR AND WALL HUNG
 BENCH SEAT REINFORCEMENTS SHALL BE INSTALLED IN THE
 SHOWER WALLS TO ACCOMMODATE FUTURE INSTALLATIONS.
 PLEASE PROVIDE DIMENSIONED ELEVATION VIEWS SHOWING THE
 LOCATIONS OF THE WALL REINFORCEMENTS.
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 2) SHEET A.2/P.1: CONCERNING THE NEW SHOWER DRAIN
 OUTLET SHOW COMPLIANCE WITH ITEMS A, B, & C LISTED
 BELOW.
 A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
 B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE
 FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING
 STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A
 NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET-
 SECTION 1-07.2.1 WPB.
 C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 3) A.2/P.1: PROVIDE COMPLETE SANITARY AND WATER RISER
 DRAWINGS FOR THE CONVERTED MASTER BATH THAT SHOWS
 POINTS OF CONNECTIONS TO THE EXISTING DWV AND WATER
 SUPPLY SYSTEMS- SECTIONS 107.2.1 & 107.3.5.1.3 WPB.
  
 4) A.2/P.1: SHOWER DETAIL: THE SLOPE OF THE SHOWER PAN
 LINER SHALL BE 1/4" PER FT., NOT 1/8" AS INDICATED IN
 THE DETAIL- SEE SECTION 417.5.2 FBC P.
  
 4) A.2/P.1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE
 ON THE PLAN AND SUBMIT MANUFACTURER?S SPECIFICATIONS
 AND INSTALLATION GUIDELINES- SECTION 502.1 FBC P, AND
 SECTION C404.2 FBC EC.
  
 5) A.2/P.1: SHOW THE TYPE AND SIZE OF PAN DRAIN PIPE
 FOR NEW WATER HEATER PAN DRAIN PIPE AND IT'S
 TERMINATION LOCATION- SECTIONS 504.7.1 & 504.7.2 FBC P.
  
 6) A.2/P.1: A 3" DRAIN IS REQUIRED FOR THE NEW WASHING
 MACHINE PER SECTION 406.2 FBC P. PLEASE CORRECT NOTE #4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected].
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-30 Cont ID  
Sent By gjohnson Date 2019-12-30 Time 11:25 Rev Time 0.00
Received By gjohnson Date 2019-12-27 Time 14:21 Sent To  
Notes
2019-12-30 11:25:371ST REVIEW: 19120254
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS BUILDING AND RESIDENTIAL UNITS WERE BUILT IN
 COMPLIANCE WITH THE FAIR HOUSING ACT AND SHALL BE
 MAINTAINED INDICATE ON THE PLAN THE DESIGN SPEC OF THE
 BATHROOMS A OR B IF THE COMPLIANCE IS NOT MAINTAINED A
 LETTER FROM THE OWNER AND DESIGNER OF RECORD ARE AWARE
 THE IT IS NOT COMPLIANT TO THE FAIR HOUSING ACT AND
 WILL BE BROUGNT INTO COMPLIANCE AT THE OWNERS EXSPENSE
 IF THE UNIT IS TO BE SOLD. PER FAIR HOUSING ACT DESIGN
 MANUAL
  
 2. PROVIDE EXISTING FLOOR PLAN . PER WPB AMEND TO FBC
 107.2.1
  
 3. IN THE NOTES THE ONLY PLUMING FIXTURE IT STATES AS
 BE RELOCATED BUT ON THE DEMO PLAN IT SHOWS THE WATER
 HEATER IN A DIFERANT LOCATION PLEASE CLARIFY.PER WPB
 AMEND TO FBC 107.2.1
  
 4. SHOW THE DIMENSIONS OF THEE RECONFIGURED BATHROOM
 SHALL COMPLY WITH FBC PL 405.3.1
  
 5. PROVIDE SHOWER PAN DETAIL AND TYPE OF MATERIAL. PER
 FBC PL 417 AND 417.5.2
  
  
  
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2020-12-12 Cont ID  
Sent By shill Date 2020-12-12 Time 06:56 Rev Time 0.00
Received By shill Date 2020-12-12 Time 06:56 Sent To  
Notes
2020-12-12 06:57:14INSPECTIONS ONLY
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-10-05 Cont ID  
Sent By cthroop Date 2020-10-05 Time 10:29 Rev Time 0.00
Received By cthroop Date 2020-10-05 Time 10:06 Sent To  
Notes
2020-10-05 10:29:51WET SEAL AND SIG VERIFIED PER DB ON 10/05/2020. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-05 Cont ID  
Sent By dbattles Date 2020-10-05 Time 09:44 Rev Time 0.00
Received By dbattles Date 2020-10-05 Time 09:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By ppetty Date 2020-08-20 Time 10:48 Rev Time 0.00
Received By ppetty Date 2020-08-20 Time 10:48 Sent To  
Notes
2020-08-13 10:24:32ENGINEER DRAWINGS SUBMITTED HAVE A COPY OF THE DIGITAL
 SIGNATURE. CHECK EMERGENCY EXTENSION THAT ALLOWS IT
 UNDER CURRENT COVID 19 EMERGENCY. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-18 Cont ID  
Sent By jgomez Date 2020-05-18 Time 12:39 Rev Time 0.00
Received By jgomez Date 2020-05-18 Time 12:39 Sent To  
Notes
2020-05-18 12:40:33CONVERTED TO DIGITAL.
 DRAWINGS WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE IN
 CITY'S FILE. JG