Plan Review Details - Permit 19120241
Plan Review Stops For Permit 19120241
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 14:10 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-04-19 Cont ID  
Sent By jwitmer Date 2020-04-19 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2020-04-19 Time   Sent To  
Notes
2020-04-19 08:15:433RD REIEW. THIS DOCUMENT MUST BE SUBMITTED BEFORE
 PERMIT ISSUANCE. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-06 Cont ID  
Sent By jwitmer Date 2020-04-06 Time 08:27 Rev Time 0.00
Received By jwitmer Date 2020-04-06 Time   Sent To  
Notes
2020-04-06 08:27:00. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 14:17 Rev Time  
Received By jwitmer Date 2020-02-04 Time   Sent To  
Notes
2020-02-04 14:17:07. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-19 Cont ID  
Sent By jwitmer Date 2020-04-19 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2020-04-19 Time 08:16 Sent To  
Notes
2020-04-19 08:40:452017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120241 (INTERIOR REMODEL OF COMMON
 AREAS AND CORRIDORS)
 ADD: 600 NORTHPOINT PKWY.
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN. APRIL 19TH/2020
 ACTION: BUILDING PROVISO
  
 BUILDING PROVISO: THE GENERAL CONTRACTOR SHALL
 COORDINATE PHASING PLAN AND SHALL PROVIDE THE NECESSARY
 DOCUMENTATION RELATED TO PHASING BEFORE CONSTRUCTION
 BEGINS. COPIES OF THE PHASING PLAN ARE TO BE SUBMITTED
 TO THE BUILDING & FIRE DEPARTMENTS. ALL EGRESS AND LIFE
 SAFETY FEATURES SHALL BE MAINTAINED DURING
 CONSTRUCTION.
 2017 FBC-EXIST. BUILD. CODE SECTIONS:
 1501.2 STORAGE & PLACEMENT.
 1501.3 ALTERATIONS, REPAIRS AND ADDITIONS.
 1501.4MANNER OF REMOVAL.
 1501.5 FIRE SAFETY DURING CONSTRUCTION.
 1501.6. PROTECTION OF PEDESTRIANS.
 1501.6.1. WALKWAYS.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-06 Cont ID  
Sent By jwitmer Date 2020-04-06 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2020-04-01 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 14:15 Rev Time  
Received By jwitmer Date 2020-02-04 Time   Sent To  
Notes
2020-02-04 14:16:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120241
 ADD: 600 NORTHPOINT PARKWAY REMODEL OF THE CORRIDORS
 AND PUBLIC SPACES.
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 04/2020
 ACTION: DENIED
  
 1) THE COVER SHEET UNDER THE HEADING OF CODE
 INFORMATION DOES NOT INCLUDE THE 2017 FBC-EXISTING
 BUILDING CODE AS PART OF THE CODE DOCUMENTS THE PLANS
 WERE CREATED WITH. PLEASE REVIEW THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 101.2 SCOPE. THE PROVISIONS OF
 THE FLORIDA BUILDING CODE, EXISTING BUILDING SHALL
 APPLY TO THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY,
 ADDITIONS TO AND RELOCATION OF EXISTING BUILDINGS.
 PLEASE UPDATE THE PLANS.
  
 2) THE COVER SHEET WITH NOT LISTING THE EXISTING
 BUILDING CODE AS ONE OF THE DOCUMENTS THE PLANS WERE
 CREATED, THE OTHER ISSUE IS SHOWING COMPLIANCE WITH THE
 EXISTING BUILDING CODE SECTION 301.1. THE REPAIRS,
 ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS TO AND
 RELOCATION OF EXISTING BUILDINGS SHALL COMPLY WITH ONE
 OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT.
 301.1.1. PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2. WORK AREA METHOD. IF THE WORK AREA METHOD IS
 PICKED AT WHAT LEVEL ALTERATION WAS UNDER TAKEN?
 31.1.3. PERFORMANCE METHOD.
 3) PLEASE NOTE THIS PERMIT (19120241) IS STRICTLY FOR
 PUBLIC SPACES AND GUEST ROOM CORRIDORS. THE PLANS ARE
 SILENT ON THE SAFE GUARDING TENANTS DURING
 CONSTRUCTION, THERE IS NO PHASING SHOWN FOR WORK AREAS.
 WHEN THE CORRIDORS ARE BEING RENOVATED THERE CAN BE NO
 TENANTS IN THE ADJOINING ROOMS. SHOW COMPLIANCE WITH
 THE FOLLOWING CODE SECTIONS:
  
 3A) 2017 FBC-EXISTING BUILDING SECTION 1501.2 STORAGE &
 PLACEMENT.
 CONSTRUCTION MATERIALS AND EQUIPMENT SHALL BE STORED
 AND PLACED SO AS NOT TO ENDANGER THE PUBLIC, THE
 WORKERS OR ADJOINING PROPERTY FOR THE DURATION OF THE
 CONSTRUCTION PROJECT.
  
 3B) 2017 FBC-EXISTING BUILDING SECTION 1501. 3
 ALTERATIONS & REPAIRS. REQUIRED EXITS, FIRE PROTECTION
 DEVICES, AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT
 ALL TIMES DURING ALTERATIONS TO ANY BUILDING.
  
 3C) 2017 FBC-EXISTING BUILDING SECTION 1501.4. MANNER
 OF REMOVAL. WASTE MATERIALS SHALL BE REMOVED IN A
 MANNER WHICH PREVENTS INJURY OR DAMAGE TO PERSONS,
 ADJOINING PROPERTIES AND THE PUBLIC RIGHT OF WAY.
  
 3D) 2017 FBC-EXISTING BUILDING SECTION 1505.2
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS TO
 ANY BUILDING.
  
 4) SHEET C105 OWNER SUPPLIED FINISHES SHOWS CARPET,
 CARPET PADDING, AND VINYL WALL COVERINGS THE COST OF
 THESE MATERIALS NEEDS TO BE ADDED TO THE VALUE OF THE
 PROJECT. 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 5A) SHEET C603 & C604 BOTH SHOW THE USE OF CARPET & PAD
 OR CARPET IN THE CORRIDORS (EXIT ACCESS) AND VERTICAL
 EXIT STAIRS. PLEASE PROVIDE DOCUMENTATION THAT THE
 FLOOR COVERING MATERIAL IN ALL OCCUPANCIES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE DOC FF-1 PILL TEST, (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 5B) PLEASE PROVIDE THE MINIMUM CRITICAL RADIANT FLUX
 FOR THE FLOOR COVERINGS. 2017 FBC-B 804.4.2. IN ALL
 OCCUPANCIES, INTERIOR FLOOR FINISHES AND FLOOR COVERING
 MATERIALS IN ENCLOSURES FOR STAIRWAYS, EXIT
 PASSAGEWAYS, CORRIDORS AND ROOMS AND SPACES OR SPACES
 NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING
 FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL
 WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM
 RADIANT FLUX SHALL BE NOT LESS THAN CLASS II IN GROUP
 A, B, H, I-4, M R-1,R-2 AND S.
  
 6) C-106 THE LOBBY FURNITURE PLAN DOES NOT PROVIDE
 ELEVATIONS OF THE FOOD COUNTERS, NOR ANY OF THE VARIOUS
 TABLES AND CHAIRS IN THE DINING ROOM COMPLIANCE FOR THE
 ACCESSIBILITY CANNOT BE REVIEWED.
  
 6A ) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 6C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 6D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS
  
 6D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-04-23 Cont ID  
Sent By jpearson Date 2020-04-23 Time 11:09 Rev Time 0.00
Received By jpearson Date 2020-04-23 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-04-21 Cont ID  
Sent By jpearson Date 2020-04-21 Time 07:41 Rev Time 0.00
Received By jpearson Date 2020-04-21 Time 07:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-08 Cont ID  
Sent By jpearson Date 2020-04-08 Time 16:54 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 07:25 Sent To  
Notes
2020-04-08 16:54:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED(S), SEE COMMENTS
 BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-02 Cont ID  
Sent By jleahy Date 2020-02-02 Time 07:36 Rev Time 0.00
Received By jleahy Date 2020-02-01 Time 17:19 Sent To  
Notes
2020-02-02 07:49:31JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
  
  
 1) VALUE FOR PERMIT TO LOW PLEASE SUBMIT A SIGNED
 CONTRACT FOR ALL WORK TO BE PERFORMED ON THIS PROJECT
  
 2) LOW VOLTAGE, FIRE ALARM, SECURITY, AND DATA REQUIRE
 PERMITS FROM A CONTRACTOR. NOTES PAGE E301
  
 3) PAGE E100, E101 SHOW ALL RECEPTACLES THE BE MOVED OR
 RELOCATED
 SHOW ALL LOW VOLTAGE OUTLETS BEING MOVED OR RELOCATED.
 PER NOTES 1 THROUGH 9
  
 4) PAGE E102 NEED TO SUBMIT CUT SHEETS ON FIXTURES.
 NEED TO SHOW ALL JBOXES PER NOTE 1 AND ALL RECEPTACLES
 PER NOTE 5
  
 5) PAGE E200 SHOW ALL SWITCH LOCATION ON PLANS BEING
 MOVED OR RELOCATED
 PLEASE SUBMIT CUTSHEETS ON FIXTURES
  
 6) PAGE E201 NO LIGHTS SHOWN IN DETAIL OF EXCERSIZE
 ROOM.
 SHOW ALL DIMMERS THAT ARE BEING RELOCATED CHANGED OR
 MOVED PER NOTE D
 SUBMIT CUTSHEETS FOR DIMMERS AND FIXTURES
 PLEASE SUBMIT CUTSHEETS ON HOLD ON BREAKERS.
  
 7) PAGE E202 CUT SHEETS ON HOLD ON BREAKERS
  
 8) PAGE E301 TELEPHONE, SECURITY, DATA, ALL REQUIRE A
 SEPARATE PERMIT PULLED BY A LICENSED CONTRACTOR IN THE
 STATE OF FLORIDA.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-04-16 Cont ID  
Sent By pleduc Date 2020-04-16 Time   Rev Time 0.00
Received By pleduc Date 2020-04-16 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By pleduc Date 2020-03-27 Time   Rev Time 0.00
Received By pleduc Date 2020-03-27 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By pleduc Date 2020-01-09 Time   Rev Time 0.00
Received By pleduc Date 2020-01-06 Time 14:46 Sent To  
Notes
2020-01-09 16:41:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS REGARDING HOTEL OCCUPANCY
 WHILE CONSTRUCTION IS ONGOING.
  
 PER NFPA 1, CH 4 GENERAL REQUIRMENTS
  
 4.5.6 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS.
 4.5.6.1 BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY
 WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES AND
 BUILDING
 PROTECTION MEASURES ACCEPTABLE TO THE AHJ ARE IN PLACE.
  
 4.4.3 MEANS OF EGRESS.
 4.4.3.1 UNOBSTRUCTED EGRESS.
 4.4.3.1.1 IN EVERY OCCUPIED BUILDING OR STRUCTURE,
 MEANS OF
 EGRESS FROM ALL PARTS OF THE BUILDING SHALL BE
 MAINTAINED FREE AND
 UNOBSTRUCTED.
  
 4.5.8.2 NO EXISTING LIFE SAFETY FEATURE SHALL BE
 REMOVED OR REDUCED
 WHERE SUCH FEATURE IS A REQUIREMENT FOR NEW
 CONSTRUCTION.
  
 PLEASE PROVIDE DETAILS, INCLUDING A LIFE SAFETY PLAN
 SHOWING HOW ALL REQUIRED EXITS WILL BE MAINTAINED, FIRE
 SPORINKLER AND FIRE ALARM WORK, EXIT MARKING, EMERGENCY
 LIGHTING, ETC.
  
  
 2) THERE ARE NO INDICATIONS OF FIRE SPRINKLER NOR FIRE
 ALARM WORK.
  
 ANY WORK ON THE FIRE SPRINKLER OR FIRE ALARM, INCLUDING
 DEMO OR RELOCATIOPN, SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUR ALL CONSTRUCTION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-28 Cont ID  
Sent By lmarchan Date 2020-04-28 Time 09:52 Rev Time 0.00
Received By lmarchan Date 2020-04-21 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-04-21 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 16:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-26 Time 15:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-02-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-30 Time 10:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 14:17 Rev Time  
Received By jwitmer Date 2020-02-04 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 11:35 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 11:31 Sent To  
Notes
2020-03-31 11:35:49PER DESIGNER RESPONSE COMMENT FROM CYCLE 1 REVIEW: NO
 MECHANICAL WORK SHALL BE DONE UNDER THIS PERMIT.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By ccole Date 2020-02-04 Time 11:49 Rev Time 0.00
Received By ccole Date 2020-02-04 Time 11:49 Sent To  
Notes
2020-02-04 11:50:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120241
 2/4/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS OR SPECIFICATIONS WERE SUBMITTED
 FOR REVIEW. PLEASE PROVIDE A SCOPE OF WORK, DRAWINGS
 AND DETAILS FOR MECHANICAL ALTERATIONS AND
 IMPROVEMENTS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-30 Cont ID  
Sent By tklarge Date 2020-03-30 Time 14:54 Rev Time 0.00
Received By tklarge Date 2020-03-30 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-28 Cont ID  
Sent By tklarge Date 2020-01-28 Time 06:44 Rev Time 0.00
Received By tklarge Date 2020-01-21 Time 13:57 Sent To  
Notes
2020-01-28 06:44:151) SHT.R731 - THE PLANS SHOW GRAB BARS INSTALLED IN A
 VERTICAL POSITION. GRAB BARS ARE TO BE INSTALLED IN A
 HORIZONTAL POSITION PER THE FBC-ACCESS. SEC. 609.4.
 2) REMOVEABLE TUB SEATS SHALL COMPLY WITH FBC-ACCESS.
 SEC. 610.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time   Sent To  
Notes
2020-04-27 14:20:08ARCHITECTURAL SHEETS ARE GOOD. JIM W.
2020-04-23 11:10:18ELECTRICAL SHEETS GOOD. PLUMBING SHEET IS
 SELF-CERTIFIED BY ENGINEER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-21 Cont ID  
Sent By jpearson Date 2020-04-21 Time 07:48 Rev Time 0.00
Received By jpearson Date 2020-04-21 Time 07:48 Sent To  
Notes
2020-04-21 07:48:23PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
  
  
2020-04-16 06:44:50ELEC - JASON RINDERLE, PE WILL SEND A DIGITALLY SIGNED
 PDF AFTER ELECTRICAL PASSES REVIEW
 ([email protected])
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 11:54 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 11:37 Sent To  
Notes
2020-03-31 11:53:45PAUL R SPRONG MUST DIGITALLY SEAL AND SIGN THE
 ELECTRICAL DRAWINGS.
 SCOTT SEVERT STILKEY MUST DIGITALLY SEAL AND SIGN THE
 PLUMBING DRAWINGS. FBC WPB 107.3.4

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-21 Cont ID  
Sent By shill Date 2020-02-10 Time 07:59 Rev Time 0.00
Received By jpearson Date 2020-02-10 Time 07:59 Sent To  
Notes
2020-02-10 08:00:32PROVISO, DIGITAL SIGNATURE ISSUED BY CERTIFICATE
 AUTHORITY REQUIRED FOR FUTURE SUBMITTALS (19120240)
  