Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 13:32 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-04-19 Cont ID  
Sent By jwitmer Date 2020-04-19 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2020-04-19 Time 07:33 Sent To  
Notes
2020-04-19 08:13:353RD REVIEW, THIS DOCUMENT MUST BE SUBMITTED BEFORE
 PERMIT ISSUANCE. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-03-31 Cont ID  
Sent By jwitmer Date 2020-03-31 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 15:50 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 12:57 Rev Time 0.00
Received By jwitmer Date 2020-02-04 Time 09:04 Sent To  
Notes
2020-02-04 12:57:06BUILT IN 1988. ASBESTOS COMMERCIAL. PLEASE PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON
 LETTERHEAD, STATING THAT THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE FOLLOWED
 AND THAT NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 13:32 Sent To  
Notes
2020-04-27 13:51:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120240 (INTERIOR REMODEL OF GUEST
 ROOMS)
 ADD: 600 NORTHPOINT PKWY.
 CONT: RELIANCE CONSTRUCTION
 TEL:
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. APRIL 27TH/2020
  
 ACTION: BUILDING PROVISO
  
 BUILDING PROVISO: SUBMIT ACTUAL TEST FOR COMPLIANCE
 WITH IIC, STC & FLAME SPREAD REQUIREMENTS FOR FLOOR
 INSULATION UNDER TILE AND OR WOOD LAMINATES.
  
 1) SEE ACTUAL 3RD REVIEW FOR SITE SAFETY REQUIREMENTS
 THAT THE CONTRACTOR IS TO SUBMIT TOTHE BUILDING
 DEPARTMENT BEFORE THE ISSUANCE OF WORK.
  
 2) SUBMIT DOCUMENTATION BEFORE THE START OF
 CONSTRUCTION. CONTRACTOR TO GET THE ARCHITECTS SHOP
 DRAWING STAMP OF APPROVAL FOR THE FLOOR UNDERLAYMENT
 INSULATION BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FLOOR INSULATION (FBC-B 2017) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: PLEASE
 PROVIDE TEST REPORTS (NOT SALES BROCHURES) SHOWING
 COMPLIANCE WITH ALL 3 REQUIREMENTS:
 FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.SHEET
 FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN
 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED
 IN ACCORDANCE WITH ASTM E 90.
 TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-19 Cont ID  
Sent By jwitmer Date 2020-04-19 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2020-04-19 Time 07:33 Sent To  
Notes
2020-04-19 08:07:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120240 (INTERIOR REMODEL OF GUEST
 ROOMS)
 ADD: 600 NORTHPOINT PKWY.
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN. APRIL 19TH/2020
  
 ACTION: BUILDING PROVISO
  
 BUILDING PROVISO: THE GENERAL CONTRACTOR SHALL
 COORDINATE PHASING PLAN AND SHALL PROVIDE THE NECESSARY
 DOCUMENTATION RELATED TO PHASING BEFORE CONSTRUCTION
 BEGINS. COPIES OF THE PHASING PLAN ARE TO BE SUBMITTED
 TO THE BUILDING & FIRE DEPARTMENTS. ALL EGRESS AND LIFE
 SAFETY FEATURES SHALL BE MAINTAINED DURING
 CONSTRUCTION. SUBMIT ACTUAL TEST FOR COMPLIANCE WITH
 IIC, STC & FLAME SPREAD REQUIREMENTS FOR FLOOR
 INSULATION UNDER TILE AND OR WOOD LAMINATES.
  
 1) SEE ACTUAL 3RD REVIEW FOR SITE SAFETY REQUIREMENTS
 THAT THE CONTRACTOR IS TO SUBMIT TOTHE BUILDING
 DEPARTMENT BEFORE THE ISSUANCE OF WORK.
  
 2) SUBMIT DOCUMENTATION BEFORE THE START OF
 CONSTRUCTION. CONTRACTOR TO GET THE ARCHITECTS SHOP
 DRAWING STAMP OF APPROVAL FOR THE FLOOR UNDERLAYMENT
 INSULATION BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FLOOR INSULATION (FBC-B 2017) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: PLEASE
 PROVIDE TEST REPORTS (NOT SALES BROCHURES) SHOWING
 COMPLIANCE WITH ALL 3 REQUIREMENTS:
 FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.SHEET
 FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN
 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED
 IN ACCORDANCE WITH ASTM E 90.
 TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-31 Cont ID  
Sent By jwitmer Date 2020-03-31 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 15:42 Sent To  
Notes
2020-03-31 15:43:30 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120240 (INTERIOR REMODEL OF GUEST
 ROOMS)
 ADD: 600 NORTHPOINT PKWY.
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 31/2020
 ACTION: BUILDING PROVISO
 BUILDING PROVISO: THE GENERAL CONTRACTOR SHALL
 COORDINATE PHASING PLAN AND SHALL PROVIDE THE NECESSARY
 DOCUMENTATION RELATED TO PHASING BEFORE CONSTRUCTION
 BEGINS. COPIES OF THE PHASING PLAN ARE TO BE SUBMITTED
 TO THE BUILDING & FIRE DEPARTMENTS. ALL EGRESS AND LIFE
 SAFETY FEATURES SHALL BE MAINTAINED DURING
 CONSTRUCTION.
  
  
  
  
  
 FLOOR INSULATION (FBC-B 2017) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING: PLEASE PROVIDE TEST REPORTS (NOT
 SALES BROCHURES) SHOWING COMPLIANCE WITH ALL 3
 REQUIREMENTS:
 FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.SHEET
 FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN
 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED
 IN ACCORDANCE WITH ASTM E 90.
 TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 12:56 Rev Time 0.00
Received By jwitmer Date 2020-02-04 Time 09:04 Sent To  
Notes
2020-02-04 12:56:052017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120240
 ADD: 600 NORTHPOINT PARKWAY INTERIOR REMODEL OF GUEST
 ROOMS
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 04/2020
 ACTION: DENIED
  
 1) THE COVER SHEET UNDER THE HEADING OF CODE
 INFORMATION DOES NOT INCLUDE THE 2017 FBC-EXISTING
 BUILDING CODE AS PART OF THE CODE DOCUMENTS THE PLANS
 WERE CREATED WITH. PLEASE REVIEW THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 101.2 SCOPE. THE PROVISIONS OF
 THE FLORIDA BUILDING CODE, EXISTING BUILDING SHALL
 APPLY TO THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY,
 ADDITIONS TO AND RELOCATION OF EXISTING BUILDINGS.
 PLEASE UPDATE THE PLANS.
  
 2) THE COVER SHEET WITH NOT LISTING THE EXISTING
 BUILDING CODE AS ONE OF THE DOCUMENTS THE PLANS WERE
 CREATED, THE OTHER ISSUE IS SHOWING COMPLIANCE WITH THE
 EXISTING BUILDING CODE SECTION 301.1. THE REPAIRS,
 ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS TO AND
 RELOCATION OF EXISTING BUILDINGS SHALL COMPLY WITH ONE
 OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT.
 301.1.1. PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2. WORK AREA METHOD. IF THE WORK AREA METHOD IS
 PICKED AT WHAT LEVEL ALTERATION WAS UNDER TAKEN?
 301.1.3. PERFORMANCE METHOD.
  
 3) PLEASE NOTE THIS PERMIT (19120240) IS STRICTLY FOR
 ALTERATIONS OF THE GUESTROOMS. PERMIT (19120241) IS FOR
 PUBLIC SPACES AND GUEST ROOM CORRIDORS. THE PLANS ARE
 SILENT ON THE SAFE GUARDING TENANTS DURING
 CONSTRUCTION, THERE IS NO PHASING SHOWN FOR WORK AREAS.
 WHEN THE CORRIDORS ARE BEING RENOVATED THERE CAN BE NO
 TENANTS IN THE ADJOINING ROOMS. SHOW COMPLIANCE WITH
 THE FOLLOWING CODE SECTIONS:
  
 3A) 2017 FBC-EXISTING BUILDING SECTION 1501.2 STORAGE &
 PLACEMENT.
 CONSTRUCTION MATERIALS AND EQUIPMENT SHALL BE STORED
 AND PLACED SO AS NOT TO ENDANGER THE PUBLIC, THE
 WORKERS OR ADJOINING PROPERTY FOR THE DURATION OF THE
 CONSTRUCTION PROJECT.
  
 3B) 2017 FBC-EXISTING BUILDING SECTION 1501. 3
 ALTERATIONS & REPAIRS. REQUIRED EXITS, FIRE PROTECTION
 DEVICES, AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT
 ALL TIMES DURING ALTERATIONS TO ANY BUILDING.
  
 3C) 2017 FBC-EXISTING BUILDING SECTION 1501.4. MANNER
 OF REMOVAL. WASTE MATERIALS SHALL BE REMOVED IN A
 MANNER WHICH PREVENTS INJURY OR DAMAGE TO PERSONS,
 ADJOINING PROPERTIES AND THE PUBLIC RIGHT OF WAY.
  
 3D) 2017 FBC-EXISTING BUILDING SECTION 1505.2
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS TO
 ANY BUILDING.
  
 4) SHEETS R701C, R701D, R703, R703D, R703E & R704B
 (ACCESSIBLE BATHROOMS) ALL MAKE REFERENCE TO NOTE 100,
 FLOOR TILE. REPLACE AT ACCESSIBLE TUB ROOMS AS REQUIRED
 BY TOILET RELOCATION ONLY. ARE THE TOILETS BEING MOVED
 TO MAKE ROOM FOR THE REQUIRED CLEAR FLOOR SPACE IN THE
 2017 FBC-ACCESSIBILITY CODE SECTION 604.3.1. THE
 PLUMBING SHEET MAKE NO MENTION OF THE WATER CLOSET
 BEING MOVED.
  
 5) SHEETS R701C, R701D, R703, R703D, R703E & R704B
 (ACCESSIBLE BATHROOMS) ALL MAKE REFERENCE TO NOTE 100,
 FLOOR TILE, TO BE REPLACED AS REQUIRED BY TOILET
 RELOCATION. IF THE WHOLE BATHROOM FLOOR IS BEING
 REPLACED THEN COMPLIANCE WITH FLOORING UNDERLAYMENT
 MUST BE MET.
  
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS:
  
 5A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR SLEEPING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.SHEET
  
 5B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS AND SLEEPING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 5C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By jpearson Date 2020-04-09 Time 07:53 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 07:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By jpearson Date 2020-01-30 Time 16:05 Rev Time 0.00
Received By jpearson Date 2020-01-30 Time 16:05 Sent To  
Notes
2020-01-30 16:05:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE DETAILS OF HOW MANY ROOMS HAVE ELECTRICAL
 WORK BEING COMPLETED. THERE SEEMS TO BE A LAYOUT FOR A
 KING ROOM, AND ONE OTHER ROOM, BUT NO INFORMATION ON
 WHICH ROOM NUMBERS ARE BEING REMODELED. WPB FBC 107.2.1
 2. PROVIDE TAMPER PROOF RECEPTACLES PER CODE IN AREAS
 REMODELED. NEC 406.12(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By pleduc Date 2020-03-27 Time   Rev Time 0.00
Received By pleduc Date 2020-03-27 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By pleduc Date 2020-01-09 Time   Rev Time 0.00
Received By pleduc Date 2020-01-09 Time 16:41 Sent To  
Notes
2020-01-09 16:42:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS REGARDING HOTEL OCCUPANCY
 WHILE CONSTRUCTION IS ONGOING.
  
 PER NFPA 1, CH 4 GENERAL REQUIRMENTS
  
 4.5.6 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS.
 4.5.6.1 BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY
 WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES AND
 BUILDING
 PROTECTION MEASURES ACCEPTABLE TO THE AHJ ARE IN PLACE.
  
 4.4.3 MEANS OF EGRESS.
 4.4.3.1 UNOBSTRUCTED EGRESS.
 4.4.3.1.1 IN EVERY OCCUPIED BUILDING OR STRUCTURE,
 MEANS OF
 EGRESS FROM ALL PARTS OF THE BUILDING SHALL BE
 MAINTAINED FREE AND
 UNOBSTRUCTED.
  
 4.5.8.2 NO EXISTING LIFE SAFETY FEATURE SHALL BE
 REMOVED OR REDUCED
 WHERE SUCH FEATURE IS A REQUIREMENT FOR NEW
 CONSTRUCTION.
  
 PLEASE PROVIDE DETAILS, INCLUDING A LIFE SAFETY PLAN
 SHOWING HOW ALL REQUIRED EXITS WILL BE MAINTAINED, FIRE
 SPORINKLER AND FIRE ALARM WORK, EXIT MARKING, EMERGENCY
 LIGHTING, ETC.
  
  
 2) THERE ARE NO INDICATIONS OF FIRE SPRINKLER NOR FIRE
 ALARM WORK.
  
 ANY WORK ON THE FIRE SPRINKLER OR FIRE ALARM, INCLUDING
 DEMO OR RELOCATIOPN, SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUR ALL CONSTRUCTION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-04-27 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-21 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-21 Cont ID  
Sent By lmarchan Date 2020-04-21 Time 15:52 Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-26 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-02-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-30 Time 10:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 12:57 Rev Time 0.00
Received By jwitmer Date 2020-02-04 Time 09:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 11:08 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 11:06 Sent To  
Notes
2020-03-31 11:10:01PER DESIGNERS COMMENTS: NO MECHANICAL WORK BEING DONE
 UNDER THIS PERMIT.
  
 MECHANICAL REVIEW COMMENTS
  
 1) NO MECHANICAL PLANS OR SPECIFICATIONS WERE SUBMITTED
 FOR REVIEW. PLEASE PROVIDE A
 SCOPE OF WORK, DRAWINGS AND DETAILS FOR MECHANICAL
 ALTERATIONS AND IMPROVEMENTS- SECTION
 107.2.1 WPB.
  
 RESPONSE: NO MECHANICAL WORK SHALL BE PERFORMED UNDER
 THIS PERMIT.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-03 Cont ID  
Sent By ccole Date 2020-02-03 Time 16:49 Rev Time 0.00
Received By ccole Date 2020-02-03 Time 16:30 Sent To  
Notes
2020-02-03 16:53:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120240
 2/3/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS OR SPECIFICATIONS WERE SUBMITTED
 FOR REVIEW. PLEASE PROVIDE A SCOPE OF WORK, DRAWINGS
 AND DETAILS FOR MECHANICAL ALTERATIONS AND
 IMPROVEMENTS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-30 Cont ID  
Sent By gjohnson Date 2020-01-30 Time 15:59 Rev Time 0.00
Received By gjohnson Date 2020-01-29 Time 17:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 13:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 11:27 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 11:11 Sent To  
Notes
2020-03-31 11:24:39PROVISO: PAUL SPRING, SCOTT STILLKEY ARE TO OBTAIN
 DIGITAL SIGNATURE ISSUED BY CERTIFICATE AUTHORITY (SENT
 EMAIL 2/10/20)
  
 ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-10 Cont ID  
Sent By shill Date 2020-02-10 Time 07:53 Rev Time 0.00
Received By shill Date 2020-02-10 Time 07:53 Sent To  
Notes
2020-02-10 07:54:37PROVISO: PAUL SPRING, SCOTT STILLKEY ARE TO OBTAIN
 DIGITAL SIGNATURE ISSUED BY CERTIFICATE AUTHORITY (SENT
 EMAIL 2/10/20)
2020-01-30 15:50:09 
 ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481
  