Plan Review Details - Permit 19120222
Plan Review Stops For Permit 19120222
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jgomez Date 2020-01-07 Time 09:28 Rev Time 0.00
Received By jgomez Date 2020-01-06 Time 11:34 Sent To  
Notes
2020-01-07 09:33:27RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- THIS BUILDING IS BUILT IN A AE FLOOD ZONE WITH THE
 BASE FLOOD BFE: 12.1 FEET BASED ON NAVD 1988. THE
 PROPOSED SCOPE OF WORK IS CONSIDERED SUBSTANTIAL
 IMPROVEMENT.
 CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2)
 FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC.
 18-284 CITY ORDINANCE NO. 4729-17). CLEARLY SPECIFY ON
 PLANS THE FINISHED ELEVATION USING THE NAVD 1988
 REFERENCE. NOTE: THE FINISHED FLOOR ELEVATION NEEDS TO
 BE AT 14.1 FEET NAVD 1988 OR HIGHER.
 IF THE FINISH FLOOR ELEVATION IS BELOW 14.1 FEET NAVD
 1988, THEN ENTIRE HOUSE NEEDS TO BE RAISED. NOTE:
 COORDINATE WITH ITEM #2 BELOW.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED
 FLOOR ELEVATION OF 12.1 FEET NAVD 88. ELEVATION
 CERTIFICATES ARE REQUIRED BASED ON CONSTRUCTION
 DRAWINGS, BUILDING UNDER CONSTRUCTION AND FINISHED
 CONSTRUCTION. PLEASE PROVIDE THE REQUIRED CONSTRUCTION
 DRAWINGS ELEVATION CERTIFICATE TO VERIFY COMPLIANCE
 WITH THE REQUIRED 2 FEET FREEBOARD.
 SEC. 18-284 CITY ORDINANCE NO. 4729-17.
  
 3- THIS IS AN ALTERATION LEVEL 3. PLANS SUBMITTED SHOW
 THAT ALL EXTERIOR WALLS ARE GOING TO BE DEMOLISHED AND
 REBUILT. THIS MEANS THAT ALL WINDOW AND DOORS FRAME
 OPENINGS ARE NEW. NONE OF THE WINDOW SIZES SPECIFIED ON
 THE WINDOW SCHEDULE FOR BEDROOMS #1 AND #2 ON SHEET S-7
 COMPLY WITH THE EGRESS REQUIREMENTS. SINGLE HUNG
 WINDOWS WITH A HEIGHT OF 4'-6"
 DON'T PROVIDE THE 24" MIN. CLEAR HEIGHT OPENING. REVISE
 AS REQUIRED.
 SEC. 505 AND SEC. 801.3 FBC-EXISTING BUILDING.
  
 4- REVISE ENERGY CALCULATIONS. COORDINATE WITH
 ARCHITECTURAL PLANS TO AVOID CONFLICTS/DELAYS:
 A) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, CORRECT
 PERMITTING OFFICE (WEST PALM BEACH NOT PALM BEACH
 COUNTY), AND JURISDICTION NUMBER (THIS JURISDICTION IS
 604700). SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) R-VALUE SPECIFIED ON ITEM #9 ON PAGE 1 OF 5 FOR
 EXTERIOR WALLS DON'T MATCH PLANS. SEE PLANS AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) COOLING AND HEATING INFORMATION SHOWN ON ITEMS #12
 AND #13 ON PAGE 1 OF 5 DOESN'T MATCH INFORMATION SHOWN
 ON PLANS AND LOAD CALCULATIONS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEE SEER AND CAPACITY OF EQUIPMENT.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 F) CLARIFY/REVISE THE "SPACES" INFORMATION ON PAGE 2 OF
 5 WHY THERE ARE NO OCCUPANTS IN THIS HOUSE?. SEC.
 107.2.1 CITY AMENDMENTS AND SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 G) WINDOWS INFORMATION SHOWN ON PAGE 4 OF 5 IS
 INCORRECT. REVISE THE BUILDING ORIENTATION, AND
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEE PLANS
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 A)SELF ADHERING ROOF UNDERLAYMENT AS SPECIFIED ON
 PLANS.
  
 B) GABLE END VENT AS SHOWN ON PLANS.
  
 C) VINYL SOFFIT AS SPECIFIED ON PLANS.
  
 D) EXTERIOR DOOR PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL (2 COPIES), INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO THE DRAWINGS
 SUBMITTED. THE FLORIDA PRODUCT APPROVAL IS REQUIRED
 BECAUSE IT SHOWS IF PRODUCT IS APPROVED AND CURRENT
 CODE IN EFFECT.
  
 E) METAL ROOF PRODUCT APPROVAL:
 PLEASE CLEARLY MARK WHICH FASTENING OPTION FROM TABLE
 "A" OF PRODUCT APPROVAL SUBMITTED IS GOING TO BE
 INSTALLED. THIS IS REQUIRED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF ALL ROOF ZONES. SEC. R301.2.1
 FBC-RESIDENTIAL.
 ALSO, DRAWINGS SUBMITTED ARE NOT THE OFFICIAL DRAWINGS
 THAT WERE APPROVED BY THE FLORIDA BUILDING COMMISSION.
 THEY DON'T HAVE THE COPY OF THE ENGINEER OF RECORD SEAL
 AND SIGNATURE. PLEASE PROVIDE COPY OF THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND ALL DRAWINGS THAT
 CORRESPOND THIS PRODUCT APPROVAL.
 FAC 61G20-3.001
  
 6-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
 NOTE: PLEASE PROVIDE REVIEW STAMP ON THE FRONT PAGE OR
 ON THE FRONT OF ANY PAGE NOT ON THE BACK OF THE PAGE.
 THIS WILL FACILITATE THE SCANNING OF THE PRODUCT
 APPROVAL FOR FILING PURPOSES.
  
 7- SHEET S-1:
 A) REVISE THE FLOOD ZONE SPECIFIED ON THE SITE TABULAR
 DATA. ACCORDING TO THE NEW MAPS IN EFFECT OCTOBER 5,
 2017 THIS PROPERTY IS IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION OF 12.1 FEET NAVD 88. REVISE AS
 REQUIRED.
  
 B) SINGLE FAMILY RESIDENCE IS CLASSIFIED AS R3 NOT R2.
 REVISE TYPICAL NOTE #4 AS REQUIRED. SEC. 310.5
 FBC-BUILDING.
  
 8- REVISE STUCCO THICKNESS SPECIFIED ON ALL DETAILS AND
 SECTIONS.
 NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS NOT
 3/4". SEC. 801.3 FBC-EXISTING BUILDING AND TABLE
 R702.1(1)FBC-RESIDENTIAL.
  
 9- NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE
 BARRIERS. SEC. 801.3 FBC-EXISTING BUILDING AND SEC.
 R703.7.3 FBC-RESIDENTIAL ON THE WOOD FRAMED WALL.
  
 10- WIND LOAD DIAGRAM ON SHEET S-4: THE MINIMUM CORNER
 DISTANCE IS 4'-0" NOT 3'-0".
 SEC. 801.3 FBC-EXISTING BUILDING AND SEE NOTE "A" ON
 FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL SCOPE OF WORK SHOWN ON PLANS.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION TO INCLUDE ALL MATERIALS, LABOR OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES OR PROVIDE COPY
 SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 12- SITE PLAN ON SHEET S-1 AND PALM BEACH COUNTY
 PROPERTY APPRAISER SHOW AN EXISTING SHED. THE PROPERTY
 APPRAISER SHOWS THAT THIS SHED WAS BUILT ON 2019. THIS
 IS A BIG STRUCTURE AND ACCORDING TO CITY RECORDS THERE
 ARE NO PERMITS FOR THE CONSTRUCTION OF THIS BUILDING. A
 BUILDING PERMIT IS REQUIRED FOR THE CONSTRUCTION OF ANY
 STRUCTURE. SEC. 105.1 CITY AMENDMENTS. NEED TO PROVIDE
 COMPLETE DRAWINGS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THIS SHED.
 NOTE: THIS COMMENT WILL NOT AFFECT THE PROCESS OF THE
 PERMIT FOR THE MAIN HOUSE BUT IT WILL NEED TO BE
 ADDRESSED. INFORMATION CAN BE SUBMITTED ALONG WITH THIS
 PERMIT OR IT CAN BE SUBMITTED UNDER A SEPARATE PERMIT.
 PLEASE ADVISE HOW DEALING WITH THIS COMMENT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-20 Cont ID  
Sent By jpearson Date 2019-12-20 Time 15:00 Rev Time 0.00
Received By jpearson Date 2019-12-20 Time 14:59 Sent To  
Notes
2019-12-20 14:48:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 1/0 WIRE ON A 200 AMP BREAKER.
 THIS WIRE IS NOT RATED FOR 200 AMPS, PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1, E3705.1
 2. PANEL SCHEDULE SHOWS # 4 WIRE ON A 100 AMP BREAKER
 FOR TANKLESS WATER HEATER. THIS WIRE IS NOT RATED FOR
 100 AMPS, PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-07 Cont ID  
Sent By jgomez Date 2020-01-07 Time 10:01 Rev Time 0.00
Received By jgomez Date 2019-12-05 Time 15:41 Sent To I
Notes
2019-12-06 15:41:39R16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jgomez Date 2020-01-07 Time 09:43 Rev Time 0.00
Received By jgomez Date 2020-01-07 Time 09:43 Sent To  
Notes
2020-01-07 09:53:27RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- REVISE EQUIPMENT LOAD CALCULATIONS. LOAD
 CALCULATIONS ARE DONE BASED ON THE FRONT DOOR FACING
 NORTH. THIS IS INCORRECT. FRONT DOOR IS FACING SOUTH.
 LOAD CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL
 ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. 801.3
 FBC-EXISTING BUILDING AND SEC. R403.7.1 FBC-ENERGY
 CONSERVATION.
  
 2- A/C PLAN DOESN'T SHOW ANY TRANSFER DUCT-OR TRANSFER
 GRILL ON THE BEDROOM SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR SEC. M1602.3 FBC-RESIDENTIAL.
 PROVIDE COMPLETE INFORMATION. SPECIFY THE TRANSFER DUCT
 OR TRANSFER GRILL SIZE.
  
 3- THIS BUILDING IS BUILT IN A AE FLOOD ZONE WITH THE
 BASE FLOOD ELEVATION OF 12.1 FEET BASED ON NAVD 1988.
 THE PROPOSED SCOPE OF WORK IS CONSIDERED SUBSTANTIAL
 IMPROVEMENT.
 CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2)
 FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC.
 18-284 CITY ORDINANCE NO. 4729-17). CLEARLY SPECIFY ON
 PLANS THE FINISHED ELEVATION OF THE A/C EQUIPMENT USING
 THE NAVD 1988 REFERENCE. NOTE: THE FINISHED FLOOR
 ELEVATION NEEDS TO BE AT 14.1 FEET NAVD 1988 OR HIGHER.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By jgomez Date 2020-01-06 Time 11:55 Rev Time 0.00
Received By jgomez Date 2020-01-06 Time 11:55 Sent To  
Notes
2020-01-06 11:56:46PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOR
 ELEVATION OF 12.1 FEET NAVD 88. ELEVATION CERTIFICATES
 ARE REQUIRED BASED ON CONSTRUCTION DRAWINGS, BUILDING
 UNDER CONSTRUCTION AND FINISHED CONSTRUCTION. PROVIDE
 THE REQUIRED CONSTRUCTION DRAWINGS ELEVATION
 CERTIFICATE. SEC. 18-284 CITY ORDINANCE NO. 4729-17.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-12-10 Cont ID  
Sent By lcrespo Date 2019-12-10 Time 06:37 Rev Time 0.00
Received By lcrespo Date 2019-12-10 Time 06:37 Sent To  
Notes
2019-12-10 06:37:5712/10/2019 1ST PLUMBING/REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 2. WASHING MACHINE VALVES SHALL BE ACCESSIBLE WITHOUT
 HAVING TO MOVE UNIT 2017 FBC SEC. R2903.3.
 3. VENT FOR WASHING MACHINE NOT SHOWN IN WALL PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 4. TANKLESS HEATER UNIT RHEEM RTEX-11 IS SHOWN OUTSIDE
 AND MANUFACTURES INSTALLATION INSTRUCTION STATES THAT
 THIS PRODUCT IS DESIGNED TO BE INSTALLED INDOORS ONLY
 ON (PAGE 4). IF THE UNIT WILL BE INSIDE MANUFACTURE
 RECOMMEND THAT YOU INSTALL A DRIP PAN (CONNECTED TO A
 SAFE DRAIN) BELOW THE WATER HEATER TO AVOID PROPERTY
 DAMAGE IN THE UNLIKELY EVENT OF A LEAK (ALSO ON PAGE
 4). HTTPS://CDN.GLOBALIMAGESERVER.COM/FETCHDOCUMENT.ASP
 X?ID=E0C72D82-1F76-4A55-A7D2-F20611901BD4. PLEASE
 PROVIDE A MANUFACTURES SPECIFICATION IF USING ALIENATE
 UNIT OR MOVE INSIDE WITH DRAIN PAN AS RECOMMENDED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-01-07 Cont ID  
Sent By jgomez Date 2020-01-07 Time 09:33 Rev Time 0.00
Received By jgomez Date 2020-01-07 Time 09:33 Sent To  
Notes
2020-01-07 09:36:411- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 A)SELF ADHERING ROOF UNDERLAYMENT AS SPECIFIED ON
 PLANS.
  
 B) METAL ROOF PRODUCT APPROVAL:
 PLEASE CLEARLY MARK WHICH FASTENING OPTION FROM TABLE
 "A" OF PRODUCT APPROVAL SUBMITTED IS GOING TO BE
 INSTALLED. THIS IS REQUIRED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF ALL ROOF ZONES. SEC. R301.2.1
 FBC-RESIDENTIAL.
 ALSO, DRAWINGS SUBMITTED ARE NOT THE OFFICIAL DRAWINGS
 THAT WERE APPROVED BY THE FLORIDA BUILDING COMMISSION.
 THEY DON'T HAVE THE COPY OF THE ENGINEER OF RECORD SEAL
 AND SIGNATURE. PLEASE PROVIDE COPY OF THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND ALL DRAWINGS THAT
 CORRESPOND THIS PRODUCT APPROVAL.
 FAC 61G20-3.001
  
 2-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
 NOTE: PLEASE PROVIDE REVIEW STAMP ON THE FRONT PAGE OR
 ON THE FRONT OF ANY PAGE NOT ON THE BACK OF THE PAGE.
 THIS WILL FACILITATE THE SCANNING OF THE PRODUCT
 APPROVAL FOR FILING PURPOSES.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-19 Cont ID  
Sent By rfalcone Date 2019-12-19 Time 09:44 Rev Time 0.00
Received By rfalcone Date 2019-12-19 Time 09:44 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved