Plan Review Details - Permit 19120174
Plan Review Stops For Permit 19120174
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-12-12 Cont ID  
Sent By rcmdouga Date 2019-12-12 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2019-12-12 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2019-12-12 Cont ID  
Sent By jleahy Date 2019-12-12 Time 14:07 Rev Time 0.00
Received By jleahy Date 2019-12-12 Time 14:03 Sent To  
Notes
2019-12-12 14:06:56NO ELECTRIC SHOWN JL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-09 Cont ID  
Sent By pleduc Date 2019-12-09 Time   Rev Time 0.00
Received By pleduc Date 2019-12-09 Time 16:46 Sent To  
Notes
2019-12-09 16:48:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF CARD READER AT THE EXIT
 DOOR.
  
 THE CARD READER SHALL BE INSTALLED UNDER SEPARATE PEMTI
 AND SHOP DRAWINGS AND COMPLY WITH NFP 101, CH 7 MEANS
 OF EGRESS.
  
  
  
 2) THERE IS A INDICATION OF FIRE SPRINKLER WORK.
  
 ANY WORK ON THE SPRINKLER SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-12 Cont ID  
Sent By rmcdouga Date 2019-12-12 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2019-12-05 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-12-12 Cont ID  
Sent By rmcdouga Date 2019-12-12 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2019-12-12 Time 18:30 Sent To  
Notes
2019-12-12 18:31:06NO CHANGES TO PLUMBING ARE SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-12 Cont ID  
Sent By jesmith Date 2019-12-12 Time 17:22 Rev Time 0.00
Received By shill Date 2019-12-12 Time 17:22 Sent To  
Notes
2019-12-12 17:22:541ST PLUMBING REVIEW**DENIED**19120174
  
 1) REVISION IS SUPPOSED TO BE FOR THE REMOVAL OF THE
 LIFT IN THE REAR OF STORE BUT ALL SHEETS SUBMITTED ARE
 SHOWING INTERIOR LAY OUT WITH MULTIPLE SECTIONS CLOUDED
 IN LEADING ME TO BELIEVE MORE IS CHANGING THEN WHAT YOU
 PROVIDED. NO SHEETS PROVIDE SHOW THE REMOVAL OF A LIFT.
  
 PROVIDE A COMPLETE NARRATIVE OF CHANGES FOR EACH SHEET
 AND REMOVE ALL SHEETS THAT DO NOT REFLECT THIS
 REVISION. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-12-12 Cont ID  
Sent By rmcdouga Date 2019-12-12 Time 18:33 Rev Time 0.00
Received By rmcdouga Date 2019-12-12 Time 18:33 Sent To  
Notes
***NONE***