| 2019-12-05 10:10:58 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| | 805-6724 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | 1. FBC B 107.2.1. PLEASE IDENTIFY ON PLANS ALL TENET |
| | SEPARATION WALLS AND CORRIDOR SEPARATION WALLS. THE |
| | INTEGRITY OF ALL FIRE RATED CEILINGS, FLOORS AND WALLS |
| | MUST BE MAINTAINED. |
| | 2. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING |
| | CONSTRUCTION METHOD OF PROPOSED NEW SHOWER WALLS/FLOORS |
| | AND SHOWING COMPLIANCE WITH 2509.2 AND 1210.2 FBC B. |
| | 3. FBC B 107.2.1. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | 4. PROVIDE THE FOLLOWING TEST REPORTS FOR PROFLEX |
| | RCU-250. MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE. |
| | 5. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | 6. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | 7. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |