Plan Review Details - Permit 19120049
Plan Review Stops For Permit 19120049
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-01-27 Cont ID  
Sent By dbattles Date 2020-01-27 Time 10:35 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 10:35 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-02 Cont ID  
Sent By dbattles Date 2020-01-02 Time 16:38 Rev Time 0.00
Received By dbattles Date 2020-01-02 Time 13:17 Sent To  
Notes
2020-01-02 16:38:39PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-27 Cont ID  
Sent By dbattles Date 2020-01-27 Time 10:35 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-02 Cont ID  
Sent By dbattles Date 2020-01-02 Time 16:38 Rev Time 0.00
Received By dbattles Date 2020-01-02 Time 13:17 Sent To  
Notes
2020-01-02 16:39:56BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120049
 REVIEWED: JANUARY 2, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 601 TABLE FBC[B]SHEET A1.0 STATES CONSTRUCTION TYPE
 AS TYPE III. IS THIS TYPE IIIA OR IIIB?
 -PLEASE STATE CONSTRUCTION TYPE AND APPLY FIRE
 RESISTANCE REQUIREMENTS FOR ELEMENTS AS LISTED IN TABLE
 601.
  
 2) 303.3 FBC[B]PLEASE REVIEW YOUR OCCUPANCY ON SHEET
 A1.0. THE AREA SERVING DRINKS WOULD BE CONSIDERED A-2.
 THE DOG RUN AREA MAY STAY UNDER A-3 AS CLOSEST
 OCCUPANCY.
 ALSO, SHOW SQ. FOOTAGE AND OCCUPANT LOAD FOR EACH
 OCCUPANCY AND AREA.
  
 3) 1010.1.10 FBC[B]ADD HARDWARE TO BE USED ON EGRESS
 DOORS TO THE DOOR SCHEDULE ON SHEET A1.2.
  
 4) 107.3.4.1 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR
 NEW WINDOWS AND MULL BAR IF BEING USED, OR INDICATE
 THAT THIS WILL BE A DEFERRED SUBMITTAL.
  
 5) 226.1 FBC[A] THE ACCESSIBILITY CODE REQUIRES 0.05 %
 OF ALL SEATING TO BE ACCESSIBLE. WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 0.05 PERCENT OF THE SEATING SPACES AND STANDING
 SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902.
 - SHOW ON PLANS 0.05% OF SEATING TO COMPLY WITH 226.1
 AND 902.
 - PROVIDE DETAILS TO SHOW HOW THE BAR MEETS 226.1
  
 6) 404.2.4 FBC[A] MANEUVERING CLEARANCES. MINIMUM
 MANEUVERING CLEARANCES AT DOORS.
 -SHOW CLEAR SPACE AT INTERIOR SIDE OF EXISTING BATHROOM
 THAT HAS BEEN RECONFIGURED. 48 INCHES NEEDED BETWEEN
 DOOR AND CLOSET WHERE WATER HEATER IS BEING LOCATED.
  
 7) 107.3.5 FBC[AMENDED]PLEASE PROVIDE DETAILS OF HOW
 INTERIOR PARTIONS ARE CONNECTED TO THE FLOOR AND THE
 CEILING.
 HOW DOES THE CEILING AND EXTERIOR WALL MEET
 PRESCRIPTIVE ENERGY CODE?
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-24 Cont ID  
Sent By jpearson Date 2020-01-24 Time 15:20 Rev Time 0.00
Received By jpearson Date 2020-01-24 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By jpearson Date 2019-12-24 Time 12:54 Rev Time 0.00
Received By jpearson Date 2019-12-24 Time 09:00 Sent To  
Notes
2019-12-24 12:54:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IS THERE AN EXISTING SERVICE AT THIS LOCATION THAT
 IS BEING REPLACED? PROVIDE RISER DIAGRAM OF EXISTING
 SERVICE AS WELL AS THE PROPOSED RISER. NEC 215.5; WPB
 FBC 107.2.1
 2. RISER DIAGRAM SHOWS A 120/240 VOLT DELTA SERVICE.
 PROVIDE NOTES FOR REQUIRED MRARKING AND IDENTIFICATION
 OF HIGH-LEG. NEC 110.15
 3. PANEL SCHEDULE SHOWS SINGLE PHASE LOADS ON THE HIGH
 LEG OF THE SYSTEM. PROVIDE CORRECTION. NEC 110.3,
 110.7, 110.8, 408.3(E)(1)
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 5. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 6. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 7. RISER DIAGRAM DOES NOT SHOW THE CORRECT AMOUNT OF
 WIRES FOR A THREE PHASE SUYSTEM. PROVIDE CORRECTION.
 WPB FBC 107.2.1; NEC 215.5, 250.24(C), 408.3
 8. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING
 CONDUCTOR TO PANEL B, WHICH IS A 125 AMP MAIN BREAKER
 PANEL. THIS WIRE IS UNDERSIZED. PROVIDE CORRECTION. NEC
 250.122
 9. RISER DIAGRAM SHOWS PANEL C AS A MAIN LUG PANEL.
 PROVIDE OVERCURRENT PROTECTION AND DISCONNECT FOR THIS
 PANEL. NEC 230.70, 240.4
 10. PANEL SCHEDULE FOR PANEL C SHOWS THE PANEL AS
 SINGLE PHASE, BUT STATES THAT IT IS A DELTA PANEL,
 WHICH IS ONLY A THREE PHASE DESIGNATION. PROVIDE
 CLARIFICATION AND/OR CORRECTION AS NEEDED. NEC 110.3;
 WPB FBC 107.2.1
 11. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 IN BAR AREA. NEC 210.8(B)
 12. FLOOR PLAN SHOWS AN ELECTRICAL PANEL IN THE
 BATHROOM AREAL. PROVIDE CORRECTION. NEC 240.24(E)
 13. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 14. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 15. EXIT AND EMERGENCY LIGHTS SHOULD BE ON THE SAME
 CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 16. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 17. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 18. PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62
  
 END OF COMMENTS.
  
 PLEASE NOTE: THIS PLAN IS SEVERELY LACKING IN REQUIRED
 INFORMATION. THEREFORE, A COMPLETE REVIEW IS NOT
 POSSIBLE AT THIS TIME. SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS. WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RESUBMITTAL
 FORM. ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED
 SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS
 SHOULD REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By pleduc Date 2020-01-17 Time   Rev Time 0.00
Received By pleduc Date 2020-01-17 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-12-04 Cont ID  
Sent By pleduc Date 2019-12-04 Time   Rev Time 0.00
Received By pleduc Date 2019-12-04 Time 15:36 Sent To  
Notes
2019-12-04 15:56:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.0 - THIUS APPEARS TO BE A CHANGE OF
 OCCUPANCY. WHAT IS THE EXISTING OCCUPANCY?
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR THE RECORD.
  
  
  
 1A) SHEET A 1.0 - THERE IS AN INDICATION OF AN A3
 OCCUPANCY WITH ON OCCUPANT LOAD OF 30 AND A SQ FT OF
 2940.
  
 REGARDLESS OF THE DOG RUN, HUMANS CAN AND WILL OCCUPY
 THIS SPACE WITH THEIR DOGS, IT IS STILL AN ASSEMBBLY
 OCCUPANCY PER NFPA 101.
  
 PLEASE REVIEW AND CORRECT THE OCCUPANCY LOAD WHILE
 PROVIDING SPECIFIC DIMENSIONS OF THE SEPARATE AREAS..
  
  
  
 1B) SHEET A 1.4 - THERE ARE NO INDICATION OF THE
 ADJACENT OCCUPANCIES NOR FIRE RESISTANCE RATING OF THE
 OCCUPANCY SEPARATION WALLS.
  
 PER NFPA 101, CH 6, OCCUPANCY CLASSIFICATION
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 1.0 - UNDER THE CODE INFORMATION THERE IS AN
 INDICATION OF NFPA 101, 2012.
  
 THE CURRENT EDITION OF NFPA 101 IS 2015.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE WITH ALL
 ASSOCIATED CODES OF THE 6TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE.
  
  
  
 3) SHEET A 1.4 - THERE IS AN INDICATION OF OCCUPANT
 LOAD OF 22 BAR 18 DOG PLAY AREA 8 DETERMINATION BY THE
 FIRE MARSHAL
  
 A. THIS TOTAL DOES NOT THE COVER PAGE AND PER # 1
 ABOVE.
  
 B. I AM THE FIRE MARSHAL AND I DO NOT RECALL THIS
 DETERMINATION.
  
 C. THERE ARE NO INDICATIONS OF SEATING AT THE BAR.
 THERE IS NO BAR LENGHT DIMENSION
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 4) SHEET A 1.2 - THERE IS NO EXIT DOOR HARDWARE
 INDICATED ON THE DOOR SCHEDULE.
  
 EXIT DOOR HARDWARE SHALL COMPLY PER NFPA 101, CH 12
 
 EGRESS.
  
 12.2.2 MEANS OF EGRESS COMPONENTS.
 12.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF
 EGRESS
 SHALL BE LIMITED TO THE TYPES DESCRIBED IN 12.2.2.2
 THROUGH 12.2.2.12.
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-01-30 Cont ID  
Sent By fmittner Date 2020-01-30 Time 15:42 Rev Time 0.00
Received By fmittner Date 2020-01-30 Time 15:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-12-05 Cont ID  
Sent By fmittner Date 2019-12-05 Time 11:40 Rev Time 0.00
Received By fmittner Date 2019-12-05 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-06 Cont ID  
Sent By jesmith Date 2020-02-06 Time 14:59 Rev Time 0.00
Received By jesmith Date 2020-02-06 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-05 Cont ID  
Sent By spalmer Date 2020-02-05 Time 15:33 Rev Time 0.00
Received By spalmer Date 2020-01-16 Time 15:55 Sent To  
Notes
2020-02-04 17:11:59ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/4/20 EL
2020-01-16 15:55:47B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-02 Cont ID  
Sent By dbattles Date 2020-01-02 Time 16:40 Rev Time 0.00
Received By dbattles Date 2019-12-02 Time 12:52 Sent To  
Notes
2019-12-13 15:38:13ROUTED FROM ZONING TO PERMIT LIBRARIAN 12/13/19 EL
2019-12-03 12:52:28B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-12 Cont ID  
Sent By dbattles Date 2020-02-12 Time 11:54 Rev Time 0.00
Received By dbattles Date 2020-02-12 Time 11:54 Sent To  
Notes
2020-02-12 11:54:41OK - PLANS STAMPED
 MU-2020-004870-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-02 Cont ID  
Sent By dbattles Date 2020-01-02 Time 16:40 Rev Time 0.00
Received By dbattles Date 2020-01-02 Time 13:17 Sent To  
Notes
2020-01-02 16:40:42109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-01-21 Cont ID  
Sent By ccole Date 2020-01-21 Time 09:51 Rev Time 0.00
Received By ccole Date 2020-01-21 Time 08:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By ccole Date 2019-12-24 Time 14:57 Rev Time 0.00
Received By ccole Date 2019-12-24 Time 13:51 Sent To  
Notes
2019-12-24 14:58:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT #9120049
 12/24/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION
 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE
 APPLIED IF THE MANUFACTURER'S PERFORMANCE DATA
 INDICATES THE AIR HANDLER IS NOT CAPABLE OF PRODUCING
 OVER 2000 CFMS OF SUPPLY AIR.
  
 2) M1.1: AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS
 REQUIRED FOR THE O/A INTAKE SUPPLYING AHU-1- SECTION
 C403.2.4.3 FBC EC.
  
 3) M1.1: SHOW THE SEQUENCE OF OPERATION FOR EF-2.
  
 4) M1.1: PLEASE PLACE A NOTE INDICATING A SEPARATE
 PERMIT IS REQUIRED FOR THE WALK-IN COOLER- SECTION
 107.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-02-06 Cont ID  
Sent By jesmith Date 2020-02-06 Time 14:59 Rev Time 0.00
Received By jesmith Date 2020-02-06 Time 08:07 Sent To  
Notes
2020-02-06 14:59:15PLUMBING COMMENTS: APPROVED W/PROVISO
  
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL TWO (2) COPIES UPDATED ENERGY &
 LOAD CALCULATIONS NOTING THE PROPER JURISDICTION AND
 THE WATER HEATER. DOCUMENT SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR
 OWN RISK.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL TWO (2) COPIES STAMPED AND
 SIGNED BY THE ENGINEER, A SLAB REPAIR DETAIL FOR REVIEW
 AND ONCE APPROVED HAVE TWO COPIES AT THE JOB SITE PRIOR
 TO FIRST INSPECTION. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS
 AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND
 THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
 3. PER FBC PL 1002.1, PROVIDE INDIVIDUAL TRAPPED
 FIXTURE DRAIN FOR EACH COMPARTMENT OF THE
 THREE-COMPARTMENT SINK. SEE REDLINED CORRECTION ON
 SANITARY ISOMETRIC.
 4. NOTE THAT NEW BATHROOM GROUP IS WET VENTED BY THE
 UPSTREAM EXISTING BATHROOM GROUP IN ACCORDANCE WITH FBC
 PL 912.1.
  
  
 19120049 525 CLEMATIS ST
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-02-04 Cont ID  
Sent By jesmith Date 2020-01-28 Time 10:43 Rev Time 0.00
Received By jesmith Date 2020-01-23 Time 15:38 Sent To  
Notes
2020-01-28 10:43:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. SECOND REQUEST; PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS AND INSTALLATION GUIDE FOR THE TANKLESS
 WATER HEATER IN ORDER TO VERIFY SIZING, PER WPB AMEND
 TO FBC 107.2.1. PLEASE NOTE THAT THE RTEX-08 NOTED IS
 ONLY CAPABLE OF PRODUCING 1.95 GPM WHICH IS
 INSUFFICIENT FOR THE HOT WATER REQUIREMENTS FOR THE
 PROJECT. ADDITIONALLY, DO NOT SPECIFY
 2. PER WPB AMEND TO FBC 107.2.1, PROVIDE CALCULATIONS
 IN ACCORDANCE WITH FBC PL SECTION 709 AND SECTION 915
 FOR SIZING OF THE COMBINATION WASTE AND VENT SYSTEM FOR
 THE BAR AND DOG RUN. INCLUDE SIZE OF STUDOR VENT(S).
 PER FBC PL 915.2.5, PROVIDE VENT FOR EACH DOG RUN FLOOR
 DRAIN.
 3. NEW BATHROOM APPEARS TO BE DOWNSTREAM FROM EXISTING
 BATHROOM GROUP. PER WPB FBC 107.2.1, CONFIRM THAT ONLY
 THE UPSTREAM BATHROOM GROUP FIXTURES ARE DISCHARGING
 THROUGH THE NEW BATHROOM GROUP COMPLYING WITH THE
 REQUIREMENTS OF FBC PL 912.1 OR VENT THE NEW WATER
 CLOSET AND FLOOR DRAIN WITH THE LAVATORY AS A WET VENT
 BEFORE CONNECTING TO THE BUILDING DRAIN.
 4. SECOND REQUEST; SHOW P-TRAPS AND FIXTURE DRAINS FOR
 3 COMPARTMENT POT SINK AND HAND SINK (SEE COMMENT 15
 FROM REVIEW #1); WATER CLOSET IS INTEGRALLY TRAPPED AND
 SHALL NOT BE PROVIDED WITH AN ADDITIONAL TRAP AS IS
 SHOWN ON THE ISOMETRIC.
 5. SHOW HOT WATER RECIRCULATION SYSTEM INCLUDING PUMP
 ON ISOMETRIC AND PLAN VIEW COMPLYING WITH FBC PL 607.2;
 SPECIFY INSULATION (SEE COMMENT 14 FROM REVIEW #1)).
 PER WPB AMEND TO FBC 107.2.1, PROVIDE MANUFACTURE
 SPECIFICATIONS FOR RECIRCULATION PUMP; PROVIDE SCHEDULE
 AND PUMP DETAIL.
 6. REGARDING ITEM 19; ICE MACHINE, PROVIDE A BACKFLOW
 PREVENTER FOR THE POTABLE WATER SUPPLY PER FBC PL 608.3
 FOR THE ICE MACHINE AND PROVIDE AN INDIRECT WASTE PIPE
 FROM THE UNIT TO A TRAPPED AND VENTED WASTE RECEPTOR
 THROUGH AN AIR GAP COMPLYING WITH FBC PL 802.1.3,
 802.2.1 AND 802.3.
 7. PROVIDE HOSE BIB IN VICINITY OF SOUTH END OF DOG RUN
 TO PROVIDE FOR WASHDOWN.
 8. PER WPB FBC 107.2.1, PROVIDE UPDATED ENERGY & LOAD
 CALCULATIONS NOTING THE PROPER JURISDICTION AND THE
 WATER HEATER.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120049 525 CLEMATIS ST
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By gjohnson Date 2019-12-27 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2019-12-27 Time 14:25 Sent To  
Notes
2019-12-27 16:50:061ST REVIEW: 19120049
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WALL FOR THE EXISTING BATHROOM WAS REMOVED
 MAKING THE BATHROOM AN ALTERATION AND SHALL COMPLY WITH
 FBC ACC 213
 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET
 ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH
 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING
 ROOM SHALL COMPLY WITH 603.
 213.3.2 WATER CLOSETS. WHERE WATER CLOSETS ARE
 PROVIDED, AT LEAST ONE SHALL COMPLY WITH 604.
 213.3.4 LAVATORIES. WHERE LAVATORIES ARE PROVIDED, AT
 LEAST ONE SHALL COMPLY WITH 606 AND SHALL NOT BE
 LOCATED IN A TOILET COMPARTMENT.
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,PER FBC PL 609.4
  
 3. SHT A1.2 THE DETAIL FOR THE ADA CLEARANCES AND
 MOUNTING HEIGHTS SHOW A SHOWER AND A URINAL THEY ARE
 NOT SHOWN ON THE PLAN PLEASE CLARIFY.PER WPB AMEND TO
 FBC 107.2.1
  
 4. PROVIDE FLOOR PLAN SHOWING CLEAR FLOOR SPACE FOR THE
 TOILETS AND LAVATORIES SHOW THE DIMENSIONS . PER FBC
 ACC 606.2,604.3.1
  
 5. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 6. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 7. THE PLAN IS CALLING THE OCCUPANCY AS AN A3 BUT IT
 APPEARS MORE LIKE A2 LIKE A BAR PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 8. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE FOR THE TANKLESS WATER HEATER IN
 ORDER TO VERIFY SIZING.PER WPB AMEND TO FBC 107.2.1
  
 9. ON THE SANITARY ISOMETRIC THE TOILET AND FLOOR DRAIN
 IN THE NEW BATHROOM SHALL BE VENTED BEFORE CONNECTING
 TO THE BUILDING DRAIN. THEY CAN BE VENTED BY THE
 LAVATORY TO FORM A WET VENT SYSTEM. PER FBC PL 912.1
  
 10. HOW WILL THE DOG AREA BE DRAINED TO MAINTAIN
 SANITARY CONDITIONS.PER WPB AMEND TO FBC 107.2.1
  
 11. ALL FLOOR DRAINS ARE REQUIRED TO HAVE A TRAP
 PRIMER. PER FBC PL 1002.4.1
  
 12. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 13. PROVIDE A WATER ISOMETRIC.PER WPB AMEND TO FBC
 107.2.1
  
 14. A RECIRCULATION SYSTEM IS GOING TO BE REQUIRED. PER
 FBC PL 607.2
  
 15. SHOW THE P-TRAPS ON THE SANITARY ISOMETRIC DRAWING
 FOR THE FLOOR DRAINS, SINKS PER WPB AMEND TO FBC
 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By elevesqu Date 2020-02-04 Time 17:11 Rev Time 0.00
Received By elevesqu Date 2020-02-04 Time 17:11 Sent To  
Notes
2020-02-04 17:11:40NO WORK ON PARKING LOT PERMITTED - REQUIRES SEPARATE
 PERMIT
  
 LIZ LEVESQUE,
 URBAN DESIGN PLANNER
  
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-13 Cont ID  
Sent By elevesqu Date 2019-12-13 Time 15:37 Rev Time 0.00
Received By elevesqu Date 2019-12-13 Time 15:34 Sent To  
Notes
2019-12-13 15:37:49PLEASE INCLUDE A SITE PLAN SHOWING PROPOSED BUILDING,
 EXISTING PARKING AREA, EXISTING BUILDINGS ON FRONT OF
 LOT, ETC.
  
 PLEASE INCLUDE ALL SF FOR ALL BUILDINGS ON THE PROPERTY
 AND INCLUDE THE PROPOSED FAR FOR THIS BUILDING
 FAR INCLUDES ALL PORTIONS OF THE BUILDING SHOWN ON
 PLANS
  
 ARE THERE ANY MODIFICATIONS TO AREAS ALONG FRONT FACADE
 (WEST ELEVATION)? PLEASE INDICATE ANY PROPOSED CHANGES
 OR USE OF AREA
  
 ANY MODIFICATIONS TO PARKING SPACES? PARKING LOT MAY
 REQUIRE SOME RESTRIPING IF NEEDED
  
 WHERE WILL THE TRASH COLLECTION BE LOCATED ON SITE?
 PLEASE INDICATE ON SITE PLAN
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426