| 2019-12-17 16:00:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3 PROVIDE THE |
| | FOLLOWING INFORMATION |
| | DRAWING INDEX NOTES PLUMBING DRAWINGS PLAN SHEETS P-1 |
| | AND P-2. PROVIDE THESE DRAWINGS FOR COMPREHENSIVE |
| | REVIEW. |
| | BASED UPON THE THE SCOPE OF WORK NOTES AND THE |
| | RECONFIGURATIONS NOTED BELOW, THE CLASSIFICATION OF |
| | WORK IS LEVEL 2, NOT LEVEL 1. |
| | ADDITIONAL COMMENTS AFTER REVIEW OF PLAN SHEETS A-1 AND |
| | D-1 |
| | 1. PLAN SHEET D-1 (DRAWING INDEX NOTES A-2 AS |
| | DEMOLITION PLAN; PLEASE CLARIFY): DEMOLITION PLAN. |
| | EXISTING WATER HEATERS; SHOW LOCATION OF EXISTING WATER |
| | HEATERS IN END APARTMENTS. PROVIDE EXISTING WATER |
| | HEATER SCHEDULE INDICATING STORAGE CAPACITY AND |
| | ELECTRICAL CHARACTERISTICS. |
| | 2. PLAN SHEET A-1; SHOW LOCATION OF ALL WATER HEATERS |
| | ON FINISH FLOOR PLAN. KITCHENS ARE RECONFIGURED. |
| | 3. PLAN SHEET A-1; SCOPE OF WORK. KITCHENS ARE |
| | RECONFIGURED. EXISTING WATER HEATERS SHALL BE REPLACED |
| | WITH NEW WATER HEATERS. PROVIDE DETAIL AND WATER HEATER |
| | SCHEDULE INDICATING MANUFACTURER, MODEL, STORAGE |
| | CAPACITY AND ELECTRICAL CHARACTERISTICS. COMPLY WITH |
| | FBC PL SECTION 504 AND FBC PL 607.3. |
| | 4. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A |
| | SANITARY RISER DIAGRAM AND PLAN VIEW LAYOUT TO SHOW |
| | CHANGES. COMPLY WITH FBC PL CHAPTER 7 AND CHAPTER 9 |
| | 5. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A |
| | WATER DISTRIBUTION RISER DIAGRAM AND PLAN VIEW LAYOUT |
| | TO SHOW CHANGES. COMPLY WITH FBC PL CHAPTER 6. |
| | 6. PROVIDE SHOWER DETAIL (ELEVATION VIEW). SHOW |
| | COMPLIANCE WITH FBC PL SECTION 417. |
| | 7. PROVIDE MATERIAL TYPE FOR SANITARY DRAINS AND VENTS. |
| | 8. PROVIDE MATERIAL TYPE FOR WATER DISTRIBUTION |
| | 9. PROVIDE UL RATED ASSEMBLIES FOR THROUGH THE FLOOR |
| | PIPING PENETRATIONS IN THE ELEVATED FLOOR. COMPLY WITH |
| | FBC CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19120033 710 10TH ST |
| | |