Plan Review Details - Permit 19111348
Plan Review Stops For Permit 19111348
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2020-03-09 Cont ID  
Sent By cpuell Date 2020-03-09 Time 16:30 Rev Time 0.00
Received By cpuell Date 2020-03-09 Time 16:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-30 Cont ID  
Sent By jgomez Date 2019-12-30 Time 10:27 Rev Time 0.00
Received By jgomez Date 2019-12-27 Time 14:55 Sent To  
Notes
2019-12-27 16:32:07RESIDENTIAL (R3) SEPARATE BUILDING ADDITION, BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL.
  
 4- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED
 FLOOR ELEVATION OF 6 FEET NAVD 88. ELEVATION
 CERTIFICATES ARE REQUIRED BASED ON CONSTRUCTION
 DRAWINGS, BUILDING UNDER CONSTRUCTION AND FINISHED
 CONSTRUCTION. PROVIDE THE REQUIRED CONSTRUCTION
 DRAWINGS ELEVATION CERTIFICATE. SEC. 18-284 CITY
 ORDINANCE NO. 4729-17.
  
 5- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD
 ZONE WITH THE BASE FLOOD BFE: 6 FEET BASED ON NAVD
 1988.
 CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2)
 FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC.
 18-284 CITY ORDINANCE NO. 4729-17). CLEARLY SPECIFY ON
 PLANS THE GARAGE PROPOSED FINISHED ELEVATION. IF THE
 GARAGE FINISH FLOOR ELEVATION IS BELOW THE TWO FEET
 FREE BOARD, THEN PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW TO MEET THE OPENING AND WET
 FLOODPROOFING REQUIREMENTS FOR ENCLOSURES AS REQUIRED
 BY SEC. R322.2.2 FBC-RESIDENTIAL. THE OTHER OPTION IS
 TO RAISE THE FINISH FLOOR ELEVATION OF THE GARAGE AT
 THE LOWEST LEVEL TO 2 FEET ABOVE THE BASE FLOOD
 ELEVATION.
  
 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE PROPOSED DORMER. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. DETAIL PROVIDED ON SHEET A-2 IS
 INCOMPLETE. PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 REINFORCEMENT OF THE ROOF OPENING AND CONNECTION OF THE
 DORMER TO THE MAIN ROOF (TOP AND BOTTOM). SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE INFORMATION FOR THE CONSTRUCTION OF
 THE EXTERIOR STAIRWAY. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS, POSTS (STAIRWAY AND BALCONY), FOOTINGS
 (STAIRWAY AND BALCONY), TREADS AND RISERS, BALUSTERS,
 RAILINGS AND GUARDRAILS (STAIRWAY AND BALCONY), ETC.
 SHOWING COMPLIANCE WITH SEC. R301.2.1 AND SEC. R311.7
 FBC-RESIDENTIAL.
  
 7- ROOF FRAMING PLAN: PROPOSED ROOF FRAMING MEMBERS ARE
 NOT ENGINEERED ROOF TRUSSES. PROVIDE COMPLETE DETAILS
 ANS SPECIFICATIONS FOR THE PROPOSED CONVENTIONAL ROOF
 FRAMING. CLEARLY SPECIFY CONNECTORS TO THE RIDGE BEAM.
 ALSO, SPECIFY COLLAR TIES OR RIDGE STRAPS AS REQUIRED
 BY SEC. R3802.3.1 FBC-RESIDENTIAL. AND, CLARIFY SIZE OF
 RIDGE VENT SPECIFIED ON THE ROOF FRAMING PLAN. SEE SEC.
 R3802.3.1 FBC-RESIDENTIAL FOR MINIMUM SIZE REQUIRED.
 ALSO, PROVIDE DETAIL/SPECIFICATIONS AT THE GABLE END.
 SPECIFY FRAMING MEMBERS AND CONNECTORS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8- CLEARLY SPECIFY SIZE OF HURRICANE STRAPS AT SECOND
 FLOOR JOISTS. SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: REVISE TITLE OF THE SECOND FLOOR FRAMING PLAN ON
 SHEET A-1. IT IS SECOND FLOOR FRAMING PLAN NOT FIRST
 FLOOR.
  
 8- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL.
  
 9- SPECIFY THE 6" CLEARANCE FOR TERMITE INSPECTION AS
 REQUIRED BY SEC. R318.7 INSPECTION FOR TERMITES.
  
 10- FOOTING SIZE SPECIFIED ON THE FOUNDATION PLAN AND
 FOOTING SIZE SPECIFIED ON THE WALL SECTION DON'T MATCH.
 REVISE AS REQUIRED TO MATCH AND COORDINATE SIZE WITH
 ITEM 9 ABOVE TO AVOID CONFLICT/DELAYS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 11- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL
  
 12- SPECIFY SECOND FLOOR ATTIC ACCESS SIZE AND LOCATION
 SHOWING COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 13- PROPOSED BUILDING SHOWN ON THE SITE PLAN ON SHEET
 C-1 IS MISSING THE STAIRWAY. PROVIDE COMPLETE
 INFORMATION. NEED TO VERIFY COMPLIANCE WITH THE FIRE
 RESISTANT PROTECTION SEC. R302.1 FBC-RESIDENTIAL
  
 14- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $98,333. THE
 PERMIT FEE BALANCE IS $2269.30.
  
 15- A UNITY OF TITLE IS REQUIRED. SUBMIT APPLICATION TO
 THE ENGINEERING DEPARTMENT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 IF THIS HAS ALREADY BEEN DONE, PLEASE PROVIDE A COPY OF
 THE RECORDED DOCUMENT.
  
  
 16- PROVIDE ROOF SHEATHING NAIL TYPE, SIZE AND SPACING
 AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: NEED TO SPECIFY RING SHANK NAILS AND GABLE ROOFS
 ENDS ARE IN ZONE #3 (5'-0" MIN.).
  
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) IN-SWING EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) OVERHEAD GARAGE DOORS AS SHOWN ON PLANS.
  
 C) SINGLE HUNG WINDOWS.
  
 D) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 E)METAL ROOFING AS SPECIFIED ON PLANS.
  
 F) ROOF UNDERLAYMENT AS SPECIFIED ON PLANS.
  
 G) HARDIE BOARD AS SPECIFIED ON PLANS.
  
 18- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-20 Cont ID  
Sent By jpearson Date 2019-12-20 Time 14:41 Rev Time 0.00
Received By jpearson Date 2019-12-20 Time 14:28 Sent To  
Notes
2019-12-20 14:41:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 3. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 4. ONLY ONE SERVICE PER ADDRESS IS PERMITTED, UNLESS
 ONE OF THE EXCEPTIONS IS MET. PROVIDE CORRECTION AND/OR
 CLARIFICATION. WPB FBC 107.2.1; NEC 230.2; FBC RE
 E3601.2
 5. PROVIDE RISER DIAGRAM OF EXISTING SERVICE THIS WILL
 BE FED FROM. NEC 215.5; WPB FBC 107.2.1
 6. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 7. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 9. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-30 Cont ID  
Sent By jgomez Date 2019-12-30 Time 10:45 Rev Time 0.00
Received By jgomez Date 2019-11-27 Time 14:31 Sent To I
Notes
2019-12-02 14:31:30R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By jgomez Date 2019-12-27 Time 15:08 Rev Time 0.00
Received By jgomez Date 2019-12-27 Time 15:08 Sent To  
Notes
2019-12-27 15:09:06IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-30 Cont ID  
Sent By jgomez Date 2019-12-30 Time 10:43 Rev Time 0.00
Received By jgomez Date 2019-12-30 Time 10:43 Sent To  
Notes
2019-12-30 10:45:24RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE COMPLETE MECHANICAL PLANS AND EQUIPMENT
 SIZING CALCULATIONS OR PROVIDE COMPLETE INFORMATION
 UNDER A SEPARATE APPLICATION. SEC. 107.5.3(11) CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By jgomez Date 2019-12-27 Time 15:10 Rev Time 0.00
Received By jgomez Date 2019-12-27 Time 15:09 Sent To  
Notes
2019-12-27 15:11:061- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED
 FLOOR ELEVATION OF 6 FEET NAVD 88. ELEVATION
 CERTIFICATES ARE REQUIRED BASED ON CONSTRUCTION
 DRAWINGS, BUILDING UNDER CONSTRUCTION AND FINISHED
 CONSTRUCTION. PROVIDE THE REQUIRED ELEVATION
 CERTIFICATES. SEC. 18-284 CITY ORDINANCE NO. 4729-17.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-04 Cont ID  
Sent By lcrespo Date 2019-12-04 Time 16:25 Rev Time  
Received By lcrespo Date   Time   Sent To  
Notes
2019-12-04 16:26:2211/05/2019 1ST PLUMBING/ REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLUMBING SANITARY RISER AN WATER DIAGRAM REQUIRED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11)
 RESIDENTIAL PLUMBING
 2. WHERE IS THE SOURCE OF HOT WATER, HOT WATER RAN
 UNDER SLAB OR IN AN UN CONDITION SPACE SHALL BE
 INSULATED PER THE 2017 FBC EC RE 403.5.3.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-12-30 Cont ID  
Sent By jgomez Date 2019-12-30 Time 10:41 Rev Time 0.00
Received By jgomez Date 2019-12-30 Time 10:41 Sent To  
Notes
2019-12-30 10:42:361- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) METAL ROOFING AS SPECIFIED ON PLANS.
  
 B) ROOF UNDERLAYMENT AS SPECIFIED ON PLANS.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By awooten Date 2019-12-09 Time   Rev Time 0.00
Received By awooten Date 2019-12-06 Time 14:54 Sent To  
Notes
2019-12-09 10:50:54********************************ZONING REVIEW
 FAILED********************
  
 PLEASE SUBMIT A COPY OF THE RECORDED UNITY OF TITLE FOR
 THE TWO LOTS.
  
 PLEASE PROVIDE THE SETBACK FOR THE OUTSIDE STAIRWAYS.
  
 OUTSIDE STAIRWAYS. OUTSIDE STAIRWAYS OVER THREE FEET IN
 HEIGHT ABOVE GRADE SHALL MEET ALL SETBACK REQUIREMENTS
 OF THE MAIN STRUCTURE (5 FEET).
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 AWOOTEN