Plan Review Details - Permit 19111310
Plan Review Stops For Permit 19111310
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-17 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-12-10 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-27 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-18 Cont ID  
Sent By ccole Date 2019-12-18 Time 17:46 Rev Time 0.00
Received By ccole Date 2019-12-18 Time 17:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-10 Cont ID  
Sent By ccole Date 2019-12-10 Time 10:03 Rev Time 0.00
Received By ccole Date 2019-12-10 Time 09:59 Sent To  
Notes
2019-12-10 10:06:481ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19111310
 12/10/2017
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MOTORIZED DAMPER SUBMITTAL NOT ACCEPTED. PLEASE
 REVIEW SECTION C403.2.4.3 FBC EC:
  
 C403.2.4.3 SHUTOFF DAMPERS.
  
 OUTDOOR AIR INTAKE AND EXHAUST OPENINGS AND STAIRWAY
 AND SHAFT VENTS SHALL BE PROVIDED WITH CLASS I
 MOTORIZED DAMPERS. THE DAMPERS SHALL HAVE AN AIR
 LEAKAGE RATE NOT GREATER THAN 4 CFM/FT2(20.3 L/S ? M2)
 OF DAMPER SURFACE AREA AT 1.0 INCH WATER GAUGE (249 PA)
 AND SHALL BE LABELED BY AN APPROVED AGENCY WHEN TESTED
 IN ACCORDANCE WITH AMCA 500D FOR SUCH PURPOSE.
  
 OUTDOOR AIR INTAKE AND EXHAUST DAMPERS SHALL BE
 INSTALLED WITH AUTOMATIC CONTROLS CONFIGURED TO CLOSE
 WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE OR
 DURING UNOCCUPIED PERIOD WARM-UP AND SETBACK OPERATION,
 UNLESS THE SYSTEMS SERVED REQUIRE OUTDOOR OR EXHAUST
 AIR IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL OR THE DAMPERS ARE OPENED TO PROVIDE
 INTENTIONAL ECONOMIZER COOLING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2019-12-10 Cont ID  
Sent By ccole Date 2019-12-10 Time 10:06 Rev Time 0.00
Received By ccole Date 2019-12-10 Time 10:06 Sent To I
Notes
***NONE***