Plan Review Details - Permit 19111287
Plan Review Stops For Permit 19111287
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By jgomez Date 2020-02-04 Time 11:04 Rev Time 0.00
Received By jgomez Date 2020-02-04 Time 10:49 Sent To  
Notes
2020-01-31 11:04:37 
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2020-01-03 Time 13:41 Sent To  
Notes
2020-01-03 13:46:44ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By jwitmer Date 2020-03-24 Time 14:00 Rev Time 0.00
Received By shill Date 2020-03-22 Time 08:16 Sent To  
Notes
2020-03-22 08:16:15REVIEWED REMOTELY BY JIM WITMER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-05 Cont ID  
Sent By jgomez Date 2020-02-05 Time 13:17 Rev Time 0.00
Received By jgomez Date 2020-02-05 Time 07:53 Sent To  
Notes
2020-02-05 13:17:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111287
 ADD: 515 N FLAGLER DR. / 5TH FLOOR RENOVATION/ SUITES
 500, 510, 520, 530, 540 & 550.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-251-2459
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WEDNESDAY FEB. 05, 2020
 ACTION: DENIED
  
 1) OK
 2) OK
  
  
 ORIGINAL COMMENT:
 3A)IN THE CORRIDOR IT APPEARS THERE IS ONLY A SINGLE
 WATER FOUNTAIN. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATS THAT DRINKING
 FOUNTAIN SHALL COMPLY WITH SECTIONS 602.1 THROUGH 602.7
 AND THERE WILL BE (1) HI-LOW ADA DRINKING FOUNTAIN.
 PLANS SUBMITTED DON'T SHOW ANY INFORMATION ABOUT (1)
 HI-LOW ADA DRINKING FOUNTAIN. PLEASE SHOW WHERE IS THIS
 INFORMATION PROVIDED? THERE ARE NO SPECS FOR PLUMBING
 FIXTURE P6.
  
  
 ORIGINAL COMMENT:
 3B) THE PROJECT VALUE OF THE PROJECT IS INDICATED TO BE
 $1,375,800.00 IN VALUE. THE ACCESSIBILITY CODE STATES
 THAT UP TO 20% OF THE PROJECT CAN BE ASSESSED FOR
 ACCESSIBLE UPGRADES, THIS WOULD INCLUDE THE WATER
 FOUNTAINS. PLEASE REVIEW THE ORDER IN WHICH THE FUNDS
 ARE TO BE SPENT.
  
 DISPROPORTIONATE COST. PLEASE PROVIDE A LETTER EITHER
 FROM THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTERHEAD WHERE UP TO 20 % OF THE CONTRACT VALUE IS
 GOING TO BE SPENT IN ACCESSIBLE UPGRADES TO THE
 PROJECT. IF ALL EXISTING CONDITIONS ARE COMPLETED
 (COMPLIED) BEFORE DISPROPORTIONATION COST IS MET A
 LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT "PROVIDING THE
 ACCESSIBLE TOILET STALL WOULD BE STRUCTURALLY
 IMPRACTICABLE (FBCA 203.15) OR TECHNICALLY INFEASIBLE".
 BASED ON PLANS AND WITH MEETING WITH ROBERT BROWN
 (BUILDING OFFICIAL) IT LOOKS LIKE IT IS NOT
 STRUCTURALLY IMPRACTICABLE TO MAKE THE RESTROOMS
 ACCESSIBLE. NEED TO MAKE RESTROOM FULLY ACCESSIBLE.
 NOTE: 20% OF $1,375.800 IS $275,160. THIS IS THE MONEY
 REQUIRED TO BE USED TO MAKE RESTROOMS ACCESSIBLE.
  
 4) OK.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 15:47 Rev Time 0.00
Received By jwitmer Date 2020-01-03 Time 13:41 Sent To  
Notes
2020-01-03 15:47:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111287
 ADD: 515 N FLAGLER DR. / 5TH FLOOR RENOVATION/ SUITES
 500, 510, 520, 530, 540 & 550.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-251-2459
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 02/2020
 ACTION: DENIED
  
 1) SHEET A0.02 THE LIFE SAFETY PLAN FOR OFFICE # 540
 THE TRAVEL DISTANCE (EXIT ACCESS TRAVEL DISTANCE TABLE
 1017.2 OF THE 2017 FBC-B) IS GIVEN BUT NOT THE COMMON
 PATH OF TRAVEL (TABLE 1006.2.1 OF THE 2017
 FBC-B). THE CODE ANALYSIS FOR THIS UNIT LIST 95 FEET,
 WHEN MEASURED ALONG THE EXIT TRAVEL DISTANCE IT WOULD
 APPEAR CLOSER TO EXACTLY 100 FT. WITH CALIBRATING THE
 PLAN.
  
 2) SHEET A0.02 SHOWS ALL OF THE TENANT SEPARATION WALLS
 AND CORRIDOR WALLS AS ONE HOUR FIRE RATED WALLS.
 SHEET A1.11 FLOOR PLAN SHOWS THE ENTRY DOORS FOR THE
 VARIOUS SUITES WITH DOOR IDENTIFICATION TAGS. THE
 DESIGNER OF RECORD CAN DESIGN TO A MORE STRINGENT
 REQUIREMENT THAN THE MINIMUM CODE. IN DOING SO YOU
 WOULD ALSO BE REQUIRED TO HAVE ALL OF THE ENTRY DOORS
 INTO EACH TENANT SPACE RATED SEE THE 2017 FBC-B TABLE
 716.5. IN THE DOOR SCHEDULE FOUND ON SHEET A0.15 NONE
 OF THE ENTRY DOORS SHOW A RATING.
  
 3A) IN THE CORRIDOR IT APPEARS THERE IS ONLY A SINGLE
 WATER FOUNTAIN. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3B) THE PROJECT VALUE OF THE PROJECT IS INDICATED TO BE
 $1,375,800.00 IN VALUE. THE ACCESSIBILITY CODE STATES
 THAT UP TO 20% OF THE PROJECT CAN BE ASSESSED FOR
 ACCESSIBLE UPGRADES, THIS WOULD INCLUDE THE WATER
 FOUNTAINS. PLEASE REVIEW THE ORDER IN WHICH THE FUNDS
 ARE TO BE SPENT.
  
 DISPROPORTIONATE COST. PLEASE PROVIDE A LETTER EITHER
 FROM THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTERHEAD WHERE UP TO 20 % OF THE CONTRACT VALUE IS
 GOING TO BE SPENT IN ACCESSIBLE UPGRADES TO THE
 PROJECT. IF ALL EXISTING CONDITIONS ARE COMPLETED
 (COMPLIED) BEFORE DISPROPORTIONATION COST IS MET A
 LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4) SHEET M5.1 IS MISSING FIRE RATED WALLS BETWEEN
 TENANT SPACES. THE ARCHITECT OF RECORD HAS REQUIRED A
 MORE STRINGENT RATING ON THE TENANT SEPARATION WALLS
 AND CORRIDOR WALLS, A 1 HOUR FIRE RATING SEE THE
 ARCHITECTURAL LIFE SAFETY PLAN. FIRE DAMPERS ARE
 MISSING IN ALL OF THESE WALLS. SEE SECTION 717.5 WHERE
 REQUIRED OF THE 2017 FBC-B.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By jpearson Date 2020-03-19 Time 09:42 Rev Time 0.00
Received By jpearson Date 2020-03-19 Time 09:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-25 Cont ID  
Sent By jpearson Date 2019-12-25 Time 09:51 Rev Time 0.00
Received By jpearson Date 2019-12-25 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-12-25 Cont ID  
Sent By jpearson Date 2019-12-25 Time 11:22 Rev Time 0.00
Received By jpearson Date 2019-12-25 Time 11:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-30 Cont ID  
Sent By pleduc Date 2020-01-30 Time   Rev Time 0.00
Received By pleduc Date 2020-01-30 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-06 Cont ID  
Sent By pleduc Date 2019-12-06 Time   Rev Time 0.00
Received By pleduc Date 2019-12-06 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 14:00 Rev Time 0.00
Received By shill Date 2020-03-13 Time 10:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 12:28 Rev Time 0.00
Received By gjohnson Date 2020-01-29 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-04 Time 14:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2020-01-03 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By jbaker Date 2020-03-24 Time 13:50 Rev Time 0.00
Received By shill Date 2020-03-24 Time 12:19 Sent To  
Notes
2020-03-24 13:51:08REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By ccole Date 2020-02-05 Time 10:54 Rev Time 0.00
Received By ccole Date 2020-02-05 Time 07:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-19 Cont ID  
Sent By ccole Date 2019-12-19 Time 09:40 Rev Time 0.00
Received By ccole Date 2019-12-19 Time 07:35 Sent To  
Notes
2019-12-19 10:06:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19111287
 12/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0.02 & M5.2: IT APPEARS THAT FIRE DAMPERS
 ARE MISSING WHERE THE O/A DUCT AND OTHER AIR
 DISTRIBUTION DUCTS ARE PENETRATING FIRE-RATED DEMISING
 WALLS SEPARATING THE OFFICE SUITES.- SECTION 607.5.2
 FBC M.
  
 2) M5.2: PLEASE PLACE A NOTE TO INDICATE WHERE THE O/A
 DUCT FOR THE FLOOR IS CONNECTING TO THE MAIN TRUNK-
 SECTION 107.2.1 WPB.
  
 3) M5.3: PROVIDE A THROUGH PENETRATION FIRESTOPPING
 DETAIL FOR THE CONDENSER WATER PIPING PENETRATING THE
 FIRE-RATED SEPARTION WALLS- SECTION 714.3.1 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 10:00 Rev Time 0.00
Received By shill Date 2020-03-24 Time 10:00 Sent To  
Notes
2020-03-24 10:00:18REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 11:43 Rev Time 0.00
Received By gjohnson Date 2020-02-07 Time 11:43 Sent To  
Notes
2020-02-07 12:28:222ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT HAVE NOT BEEN
 COMPLIED WITH. I SUGGEST A MEETING WITH THE OWNER,
 ARCHITECT AND THE PLAN REVIEWERS AND BUILDING OFFICIAL
 TO CLEAR THIS UP.
  
 1. PLEASE SHOW 60" CLEAR FLOOR SPACE IN ALL THE CAFE.
 PER FBC ACC 804.2.2
  
 2. ON ALL REMODELS 20% OF THE TOTAL COST OF THE JOB
 SHALL BE SPENT ON BRING UP THE LEVEL OF ACCESSIBILITY
 PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE WITH
 FBC ACC 202.4.1, 202.4.2
 IN ORDER TO PROVIDE A ACCESSIBLE TOILET STALL YOU CAN
 REMOVE ONE TOILET AND STILL BE CODE COMPLIANT FOR THE
 PLUMBING FIXTURE COUNT
  
  
 4. SHOW COMPLIANCE WITH FBC ACC 602.4 , 602.7,602.2 THE
 CLEAR FLOOR SPACE SHALL BE FOR A FRONT APPROACH. WITH 2
 SPOUTS. SHT A0.04 DETAIL #6 SHALL SHOW COMPLIANCE WITH
 602.7 THE HIGH SPOUT ALONG WITH THE LOW SPOUT AND THE
 CLEAR FLOOR SPACE FOR THE FRONT APPROACH THE PARALLEL
 APPROACH IS NOT CODE COMPLIANT.
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By gjohnson Date 2019-12-24 Time 13:52 Rev Time 0.00
Received By gjohnson Date 2019-12-24 Time 13:52 Sent To  
Notes
2019-12-24 13:52:251ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW 60" CLEAR FLOOR SPACE IN ALL THE CAFE.
 PER FBC ACC 804.2.2
  
 2. ON ALL REMODELS 20% OF THE TOTAL COST OF THE JOB
 SHALL BE SPENT ON BRING UP THE LEVEL OF ACCESSIBILITY
 PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE WITH
 FBC ACC 202.4.1, 202.4.2
  
 3. PROVIDE THE EXISTING LAYOUT OF THE BATHROOMS. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHOW COMPLIANCE WITH FBC ACC 602.4 , 602.7,602.2 THE
 CLEAR FLOOR SPACE SHALL BE FOR A FRONT APPROACH. WITH 2
 SPOUTS.
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 12:22 Rev Time 0.00
Received By shill Date 2020-03-24 Time 12:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 12:29 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2020-02-07 12:29:49PLUMB SHEETS OK GPJ
2020-02-05 13:27:0902/05/2020 ARCHITECTURAL SHEETS OK / JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By shill Date 2020-01-06 Time 11:59 Rev Time 0.00
Received By shill Date 2020-01-06 Time 11:59 Sent To  
Notes
2020-01-03 15:55:1401/02/2020 ALL ARCHITECTURAL SHEETS CHECKED FOR DIGITAL
 SIGNATURES. OK. / JW
2019-12-25 09:38:09ELECTRICAL SHEETS OK.