| 2019-12-16 14:02:14 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19111231 |
| | ADD: 1751 PALM BEACH LACES BLVD. UNIT: E115 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ???????????????? |
| | E-MAIL: [email protected] CONTACT: LISA SUNDERLAND |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. DEC. 16TH/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET A0001 LIST THE APPLICABLE CODES, |
| | PLEASE UPDATE ALL OF THE FLORIDA CODES ARE UNDER THE |
| | 6TH EDITION, (2017): |
| | 2017 FLORIDA MECHANICAL CODE, 6TH EDITION |
| | 2017 FLORIDA FUEL GAS CODE, 6TH EDITION |
| | 2017 FLORIDA EXISTING BUILDING CODE, 6TH EDITION |
| | 2017 FLORIDA ENERGY CODE, 6TH EDITION |
| | 2017 FLORIDA PLUMBING CODE, 6TH EDITION |
| | |
| | 2) SHEET A0001 THE COVERSHEET SHOWS THE TENANT SPACE |
| | NUMBER E115 AND THE CLOSEST GANG RESTROOMS ARE FOUND IN |
| | THE FOOD COURT. IF THE DISTANCE FROM THE FRONT DOORS OF |
| | UNIT E115 TO THE GANGED RESTROOMS THROUGH THE BACK OF |
| | HOUSE CORRIDOR BEHIND THE FOOD COURT IS 365 FEET. IF |
| | YOU GO AROUND THE FRONT OF THE FOOD COURT THE DISTANCE |
| | IS OVER 745 FEET TO THE RESTROOMS. THIS TENANT SPACE |
| | AND OTHERS IN THIS BUILDING AND OTHER BUILDINGS ARE |
| | REQUIRED TO HAVE THEIR RESTROOMS OPEN TO THE PUBLIC AND |
| | EMPLOYEES SINCE THE MAXIMUM DISTANCE IN OPEN AND CLOSED |
| | MALLS TO RESTROOMS FOR EMPLOYEES AND THE PUBLIC IS 300 |
| | FEET. WHEN THE MALL WAS CREATED THIS WAS ONE |
| | REQUIREMENT THAT THE TENANT SPACES OVER 300 FEET AWAY |
| | FROM THE GANGED RESTROOMS HAD TO MEET. SEE THE 2017 |
| | FBC-B 2902.3.3 LOCATION OF TOILET FACILITIES IN MALLS. |
| | |
| | THE DEMO-SHEET A0090-DEMO FLOOR PLAN SHOWS A COMPLIANT |
| | RESTROOM IN COMPLIANCE WITH THE 2017 FBC-B SECTION |
| | 2902.3.1 ACCESS. THE ROUTE TO THE PUBLIC TOILET |
| | FACILITIES REQUIRED BY SECTION 2902.3 SHALL NOT PASS |
| | THROUGH STORAGE ROOMS OR CLOSETS. THE NEW PROPOSED |
| | FLOOR PLAN LAYOUT FOUND ON SHEET A0106 DOESN?T MEET THE |
| | REQUIREMENTS OF FBC-B 2902.3.1. |
| | |
| | 3) ON THE COVERSHEET PLEASE PROVIDE THE CLOSET PUBLIC |
| | COMMON AREA WATER FOUNTAIN AND DISTANCE FROM THIS |
| | TENANT SPACE. PLEASE SHOW COMPLIANCE WITH SECTION |
| | 2902.5 DRINKING FOUNTAIN LOCATION. PUBLIC DRINKING |
| | FOUNTAINS ARE TO BE LOCATED WITHIN A DISTANCE OF TRAVEL |
| | OF 500 FEET OF THE MOST REMOTE LOCATION IN THE TENANT |
| | SPACE. WHEN THE TENANT SPACE IS IN A COVERED OR OPEN |
| | MALL, SUCH DISTANCE SHALL NOT EXCEED 300 FEET. DRINKING |
| | FOUNTAINS SHALL BE LOCATED ON AN ACCESSIBLE ROUTE. |
| | PLEASE SHOW COMPLIANCE. |
| | |
| | 4) SHEET 017-A2300 STOREFRONT ELEVATIONS SHOWS (IN DARK |
| | LINED INK LINES) NEW ENTRY DOORS AND STOREFRONT GLAZING |
| | SYSTEM TO MATCH. THE NEW STOREFRONT SYSTEM WOULD APPEAR |
| | TO BE (2) NEW 3-0X 7-0 GLAZED DOORS, SIDE LITE, AND |
| | TRANSOMS ABOVE BOTH THE GLAZED DOORS. WHEREAS ON SHEET |
| | 020-A2500 THE PLANS STATE THE 2 TRANSOMS ABOVE THE (2) |
| | GLAZED DOORS ARE TO REMAIN. 107.2.1.2 DISCREPANCY IN |
| | THE PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5) WITH THE NEW STOREFRONT SYSTEM THERE IS NO WIND |
| | DESIGN CRITERIA PROVIDED FOR THIS REVIEW. PLEASE SHOW |
| | COMPLIANCE WITH 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 5.2. RISK CATEGORY. |
| | |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 6) SHOW COMPLIANCE WITH THE 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | |
| | 7) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 8A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | 8B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9) SHEET 053-M100 SHOWS ON BOTH ERTU UNITS 1 & 2 SMOKE |
| | DETECTORS IN THE SUPPLY AND RETURN DUCTS. PLEASE SHOW |
| | COMPLIANCE WIT THE 2017 FBC-B 907.3.1 AND THE |
| | FBC-MECHANICAL SECTIONS: |
| | 606.2 WHERE THE SMOKE DETECTORS ARE REQUIRED AND |
| | 606.2.1. SMOKE DETECTORS ARE REQUIRED ON THE SUPPLY |
| | SIDE AS PER NFPA 90A. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |