Plan Review Details - Permit 19111230
| Plan Review Stops For Permit 19111230 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-01-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-25 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-16 |
Time |
07:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2020-01-11 10:52:49 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. VALUE HAS BEEN ADJUSTED FROM $85,000 TO $180,405 | | | BASED ON THE ICC BUILDING VALUATION TABLES. 1488 SQ FT | | | X $121.24/SQ FT = $180,405. | | | | | | CITY OF WPB CHPT. 1 VALUE 109.3 BUILDING PERMIT | | | VALUATIONS. | | | | | | 2. DESIGNER OF RECORD (DOR) STATES VALUE IS OVER | | | ESTIMATED FOR THIS NEIBORHOOD. ADJUSTMENTS TO VALUE ARE | | | OUT OF PLANS EXAMINERS PERVIEW. | | | | | | 3. DOR MAY SUBMIT ADJUSTMENT REQUEST ON COMPANY | | | LETTERHEAD TO MR. ROBERT BROWN, BUILDING OFFICIAL, CITY | | | OF WEST PALM BEACH, FL 33401. LETTER MUST BE ORIGINAL | | | SIGNED AND SEALED BY DOR. | | | | | | 4. SUBMIT PRODUCT APPROVALS FOR PROPOSED WINDOWS, DOORS | | | AND ROOFING SYSTEM COMPONENTS. INCLUDE PRODUCT APPROVAL | | | COVER LETTER AND INSTALLATION INSTRUCTIONS FOR SPECIFIC | | | MODEL/PRODUCTS SELECTED. | | | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | DEFERAL OF PRODUCT APPROVALS MAY BE SELECTED. SEE | | | BELOW. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | IF DEFERAL OPTION IS SELECTED, PROVIDE LIST OF PRODUCTS | | | TO BE DEFERRED ON PLANS. I.E. WINDOWS, DOORS, ROOFING | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-30 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2019-11-30 08:35:37 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. VALUE HAS BEEN ADJUSTED FRO 85000 TO 180405 BASED ON | | | THE ICC BUILDING VALUATION TABLES. | | | | | | 2. PROVIDE SURVEY AND DRAINAGE PLAN. | | | FBC R401.3 SITE DRAINAGE | | | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING | | | COMPLIANCE WITH FBC R401.3 DRAINAGE. | | | | | | PROVIDE SITE PLAN. | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED ON A BOUNDARY LINE SURVEY. | | | | | | 3. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH | | | OPENINGS AND DESIGN PRESSURES. | | | FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-R301.2. | | | | | | 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND | | | EXTERIOR DOORS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | 5. DESIGNER SHALL STATE INSULATION R VALUES ON PLAN. | | | CEILINGS R-30 AND WALLS R-3.0. | | | R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE). | | | IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1, | | | INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF | | | SECTIONS R402.2.1 THROUGH R402.2.13. | | | | | | 6. INSULATION ABOVE ATTIC SCUTTLE SHALL EQUAL | | | SURRONDING R VALUE. | | | R402.2.4 ACCESS HATCHES AND DOORS. | | | | | | 7. ATTIC SCUTTLE SHALL HAVE WEATHER STRIPPING. | | | R402.2.4 ACCESS HATCHES AND DOORS. | | | | | | 8. LANSCAPE PLAN PAGE L INDICATES A THREE FOOT OVERHANG | | | FOR ROOFING. NO STRUCTURAL DETAILS ARE PROVIDED. PLEASE | | | CLARIFY. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 9. SHOW LOCATION OF ATTIC ACCESS ON PLANS. ACCESS SHALL | | | COMPLY WITH M1305.1.3. SWITCHED LUMINARE AND SERVICE | | | OUTLET ARE REQUIRED FOR MECH. EQUIPT. IN ATTICS. | | | M1305.1.3.1 ELECTRICAL REQUIREMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, | | | INSERT CORRECTED PAGES INTO | | | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS | | | DETACHED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-03 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2019-12-03 10:39:02 | PLAN REVIEW - ELECTRICAL | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. AIC: | | | | | | PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM | | | UTILITY. | | | E3404.2INTERRUPTING RATING. | | | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS | | | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 | | | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT | | | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN | | | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT | | | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) | | | | | | 2. PANEL SCHEDULE STATES PANELS A&B. PLEASE CLARIFY. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. CIRCUTS 15 AND 17 FOR SMALL APPLIANCE SHALL BE A | | | MINIMUM OF 20 AMP PER E3703.2 & E3902.3. | | | E3703.2 KITCHEN AND DINING AREA RECEPTACLES. | | | A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL | | | BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE | | | OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, | | | DINING AREA OR SIMILAR AREA OF A DWELLING. | | | E3901.3 SMALL APPLIANCE RECEPTACLES. | | | IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR | | | SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE | | | 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY | | | SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR | | | RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND | | | E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR | | | REFRIGERATION APPLIANCES. [210.52(B)(1)]. | | | | | | 4. CIRCUT 23 FOR LAUNDRY SHALL BE A MINIMUM OF 20 AMPS | | | PER E3703.3. | | | E3703.3 LAUNDRY CIRCUIT. | | | A MINIMUM OF ONE 20-AMPERE-RATED BRANCH CIRCUIT SHALL | | | BE PROVIDED FOR RECEPTACLES LOCATED IN THE LAUNDRY AREA | | | AND SHALL SERVE ONLY RECEPTACLE OUTLETS LOCATED IN THE | | | LAUNDRY AREA. [210.11(C)(2)]. | | | | | | 5. CONDUCTOR SIZING FOR THE WATER HEATER (2/40AMP) AND | | | STOVE (2/60AMP) IS UNDERSIZED PER TABLE E3705.1. | | | | | | 6. ARC FAULT NOTE ON PAGE E-1 SHALL INCLUDE KITCHENS. | | | AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH | | | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND | | | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, | | | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, | | | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING, POWER | | | OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI | | | AND GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8, | | | 210.12; FBC RE E3902.16; FBC EX 607.1.1 OR 801.1, | | | 801.2, OR 901.2 AS APPLICABLE. | | | | | | 7. PROVIDE SERVICE OUTLET AT CONDENSING UNIT PER | | | E3901.12. | | | E3901.12 HVAC OUTLET. | | | | | | 8. EXTERIOR OUTLET REQUIRED AT FRONT OF STRUCTURE PER | | | E3901.7. | | | E3901.7 OUTDOOR OUTLETS. | | | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY | | | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 | | | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE | | | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH | | | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. | | | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM | | | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE | | | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE | | | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE | | | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE | | | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-01-26 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-01-13 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-06 |
Time |
07:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-04 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-25 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-01-27 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-01-13 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2020-01-27 08:08:57 | RECEIPT 2020-0117-293 - $9401.07 - PAID | | 2020-01-13 11:55:07 | 1/13/20 SENT EMAIL TO IMPACT FEE OFFICE. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-11 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2020-01-11 10:23:15 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-11-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-30 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2019-11-30 08:14:31 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-30 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2019-11-30 10:46:26 | PLAN REVIEW - MECHANICAL | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE SERVICE OUTLET AT CONDENSING UNIT PER | | | E3901.12 | | | E3901.12 HVAC OUTLET. | | | | | | 2. SHOW FLEX DUCT TO BATHROOM. SHOW SIZE AND CFM. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. RETURN AIR SHALL COMPLY WITH M1602.2. | | | PROVIDE CFM'S AT EACH SUPPLY. BALANCED RETURN AIR SHALL | | | COMPLY WITH 1602.3. 50 SQ. INCHES FOR EACH 100 CFM OF | | | SUPPLY. | | | | | | 4. SHOW LOCATION OF EXHAUST FANS ON PLANS. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 5. PROVIDE LOCATION OF DRYER EXHAUST ON PLANS. EXHAUST | | | TERMINATION SHALL COMPLY WITH M1502.3. | | | | | | 6. SHOW LOCATION OF ATTIC ACCESS ON PLANS. ACCESS SHALL | | | COMPLY WITH M1305.1.3. SWITCHED LUMINARE AND SERVICE | | | OUTLET ARE REQUIRED FOR MECH. EQUIPT. IN ATTICS. | | | M1305.1.3.1 ELECTRICAL REQUIREMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, | | | INSERT CORRECTED PAGES INTO | | | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS | | | DETACHED. | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-03 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2020-01-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-25 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-16 |
Time |
07:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2020-01-11 10:34:27 | PLAN REVIEW - ROOFING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | | | | 1. ROOFING PERMIT REQUIRED. (ACKNOWLEDGED) | | | PERMITS - 105.1 REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS OF NEW ROOFING SYSTEM | | | COMPONENETS. (NOT ADDRESSED) (YOU MAY SELECT TO DEFER | | | PRODUCT APPROVALS - SEE BELOW) | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-11-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-30 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2019-11-30 08:20:20 | PLAN REVIEW - ROOFING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | PERMITS - 105.1 REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS OF NEW ROOFING SUSTEM | | | COMPONENETS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, | | | INSERT CORRECTED PAGES INTO | | | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS | | | DETACHED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-01-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-25 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-16 |
Time |
07:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-11 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-11-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-30 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-27 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2019-11-30 08:17:07 | PLAN REVIEW - DIGITAL SIGNATURES AND SEALS | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | DIGITAL REVIEW | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS | | | 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE NEXT | | | REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-12-11 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-12-11 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-12-11 |
Time |
09:37 |
Sent To |
I |
|
| Notes |
| 2019-12-11 09:38:21 | 12/11/19 | | | | | | SEPERATE LANDSCAPE PERMIT MUST BE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-04 |
|
|
Cont ID |
|
| Sent By |
cdglass |
Date |
2019-12-04 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
cdglass |
Date |
2019-12-04 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2019-12-04 09:16:06 | ZBA APPROVAL REQUIRED FOR PASSING OF THIS PERMIT. | | | | | | CAROLINE GLASS | | | [email protected] |
|
|
|