Plan Review Details - Permit 19111213
Plan Review Stops For Permit 19111213
Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-12-05 Cont ID  
Sent By rrossano Date 2019-12-05 Time   Rev Time  
Received By rrossano Date 2019-12-05 Time   Sent To I
Notes
2019-12-05 12:00:27PLEASE APPLY FOR FORMAL ENGINEERING SUBMITTAL.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX:
 (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ, SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1085
 FAX: (561) 494-1116 MOBILE: (561) 644-7301 EMAIL:
 [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-27 Cont ID  
Sent By pleduc Date 2019-11-27 Time   Rev Time 0.00
Received By pleduc Date 2019-11-27 Time 12:54 Sent To P
Notes
2019-11-27 12:58:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) INSTALL, TEST AND INSPECT PER NFPA 24, STANDARD FOR
 THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES, 2013 EDITION.
  
  
 2) INSTALL SHALL BE COMPLETED BY A LICENSED FLORIDA
 UNDERGROUND FIRE PROTECTION CONTRACTOR.
  
  
 3) PROVIDE ALL PRODUCT AND MATERIALS MANUFACTURES SPEC
 AND INSTALLATION SHEETS FOR REVIEW AND VERIFICATION BY
 FIRE INSPECTOR ON INSPECTION.
  
  
 4) DO NOT COVER OVER PRIOR TO INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-05 Cont ID  
Sent By cpuell Date 2019-12-05 Time 13:02 Rev Time 0.00
Received By cpuell Date 2019-11-25 Time 13:06 Sent To  
Notes
2019-11-26 13:07:03ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-04 Cont ID  
Sent By cmontell Date 2019-12-04 Time 05:26 Rev Time 0.00
Received By cmontell Date 2019-12-04 Time 05:26 Sent To ENG
Notes
2019-12-04 05:27:02SEE PLUMBING NOTES

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-27 Cont ID  
Sent By lcrespo Date 2019-11-27 Time 18:19 Rev Time 0.00
Received By lcrespo Date 2019-11-27 Time 18:19 Sent To  
Notes
2019-11-27 18:20:0211/27/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLANS ARE DIGITALLY SIGNED AND SEAL. ONLY WHEN THE
 PLANS ARE SUBMITTED DIGITALLY IS THIS ALLOWED.
 61G15-23.005. PLANS SUBMITTED IN PAPER FORM ARE
 REQUIRED TO BE SEALED AND WET SIGNED BY THE DESIGN
 PROFESSIONAL. 61G15-23.001.
 2. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE
 WORK SECTION ON THE PERMIT APPLICATION.
 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT THE
 DEPARTMENT OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
 5. THE 2017 FLORIDA STATUTES 633.102, INSURANCE,
 CHAPTER 633, FIRE PREVENTION AND CONTROL, 3 (A)
 CONTRACTOR I, II AND V ARE THE ONLY ONE'S LICENSED
 CONTRACTOR WHOSE BUSINESS INCLUDES THE EXECUTION OF
 CONTRACTS REQUIRING THE ABILITY TO LAYOUT, FABRICATE,
 INSTALL, INSPECT, ALTER, REPAIR, AND SERVICE ALL TYPES
 OF FIRE PROTECTION SYSTEMS, EXCLUDING PRE-ENGINEERED
 SYSTEMS. PLEASE PROVE PROPER PAPERWORK SUPPORTING YOUR
 LICENSE FOR THIS TYPE OF WORK.
 6. SEPARATE BACKFLOW PERMIT, CERTIFICATION BY THE CITY
 OF WEST PALM BEACH UTILITIES DEPARTMENT AND A FINAL
 PLUMBING INSPECTION REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  