| 2019-12-12 15:29:29 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE |
| | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS |
| | APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT. |
| | |
| | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| | ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS. |
| | |
| | |
| | |
| | 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS. |
| | 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS. |
| | 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING |
| | SYSTEMS SHALL BE PERMITTED TO BE INSTALLED ON DOOR |
| | ASSEMBLIES SERVING LOW AND ORDINARY HAZARD CONTENTS IN |
| | BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| | ACCORDANCE WITH SECTION |
| | 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.7, AND WHERE |
| | PERMITTED IN CHAPTERS 11 THROUGH 43, PROVIDED THAT ALL |
| | OF THE FOLLOWING CRITERIA ARE MET: |
| | (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| | EGRESS UPON ACTUATION OF ONE OF THE FOLLOWING: |
| | (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7 |
| | (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED, |
| | SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.6 |
| | (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED, |
| | SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.6 |
| | (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| | EGRESS UPON LOSS OF POWER CONTROLLING THE LOCK OR |
| | LOCKING MECHANISM. |
| | (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN |
| | THE DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30 |
| | SECONDS WHERE APPROVED BY THE AUTHORITY HAVING |
| | JURISDICTION, UPON APPLICATION OF A FORCE TO THE |
| | RELEASE DEVICE REQUIRED IN 7.2.1.5.10 UNDER ALL OF THE |
| | FOLLOWING CONDITIONS: |
| | (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF |
| | (67 N). |
| | (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY |
| | APPLIED FOR MORE THAN 3 SECONDS. |
| | (C) THE INITIATION OF THE RELEASE PROCESS SHALL |
| | ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR |
| | OPENING. |
| | (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION |
| | OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY |
| | MANUAL MEANS ONLY. |
| | (4)* A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT |
| | LESS THAN 1 IN. (25 MM) HIGH AND NOT LESS THAN 1?8 IN. |
| | (3.2 MM) IN STROKE WIDTH ON A CONTRASTING BACKGROUND |
| | THAT READS AS FOLLOWS SHALL BE LOCATED ON THE DOOR LEAF |
| | ADJACENT TO THE RELEASE DEVICE IN THE DIRECTION OF |
| | EGRESS: |
| | PUSH UNTIL ALARM SOUNDS |
| | DOOR CAN BE OPENED IN 15 SECONDS |
| | (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH |
| | DELAYED-EGRESS LOCKS SHALL BE PROVIDED WITH EMERGENCY |
| | LIGHTING IN ACCORDANCE WITH SECTION 7.9. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |