Plan Review Details - Permit 19111204
| Plan Review Stops For Permit 19111204 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-01-06 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-01-06 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-01-06 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-01-06 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2020-01-06 08:05:44 | ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED | | | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, | | | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF | | | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF | | | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT | | | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL | | | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE | | | FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-06-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-06-05 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-06-05 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2020-06-05 16:57:36 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19111204 | | | ADD: 6329 N. JOG RD. | | | CONT: ALL-SITE CONSTRUCTION INC. | | | TEL: 561-848-1110 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 4TH REVIEW | | | DATE: JUNE 05TH/ 2020 | | | ACTION: BUILDING PROVISO: | | | 1) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L | | | 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW | | | COMPLIANCE WITH: | | | WELDED OR BOLTED CONNECTIONS | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE | | | AMERICAN WELDING SOCIETY. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS | | | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING | | | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-05-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-05-03 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-04-27 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2020-05-03 14:26:03 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19111204 | | | ADD: 6329 N. JOG RD. | | | CONT: ALL-SITE CONSTRUCTION INC. | | | TEL: 561-848-1110 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: MARCH27TH- MAY 03RD/ 2020 | | | ACTION: DENIED | | | | | | 1) SEMI-COMPLIED. THE DESIGNER OF RECORD HAS RESPONDED | | | TO THIS ROUND OF COMMENTS, THANK YOU. THERE IS GOING TO | | | BE A QUESTION LATER IN THIS REVIEW ABOUT THE ALTERNATE | | | MATERIALS & METHODS REQUEST, HOW TO SUBMIT. | | | | | | 2A) 3RD REQUEST SEMI-COMPLIED. THIS EXTERIOR DOOR | | | TESTING REPORT MANUFACTURER PHILADELPHIA HARDWARE GROUP | | | (PHG) IS FOR A STEEL EXTERIOR DOOR, 5 PAGES LONG. THIS | | | DOCUMENT ALONE DOES NOT MEET THE REQUIREMENTS FORM THE | | | STATE OF FLORIDA FOR A PRODUCT APPROVAL. | | | THERE ARE NO DOCUMENTS SUBMITTED FOR THE INDEPENDENT | | | 3RD PARTY CERTIFICATION REQUIRED BY THE STATE FOR A | | | STATE APPROVAL OR FOR A LOCAL WEST PALM BEACH LOCAL OR | | | SITE PRODUCT APPROVAL. | | | | | | 2A)2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR | | | AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR | | | REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED | | | NEW DOOR. . FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, | | | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ | | | 2010. | | | PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE | | | COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2 | | | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & | | | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, | | | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ | | | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS , | | | | | | 2B) 3RD REQUEST. SEMI-COMPLIED. THERE IS A MIAMI-DADE | | | NOA 17-0919.04 SUBMITTED. SINCE THERE ARE 2 ISSUES WITH | | | LOUVERED OPENINGS WE NEED TO HAVE LISTED ON THE NOA FOR | | | WHICH OPENINGS THIS PRODUCT IS GOING TO BE SUBMITTED | | | FOR? 2ND IT ALSO NEEDS TO BE UNDERSTOOD THAT THERE IS A | | | LETTER TO BE SUBMITTED FOR THE GENERATOR EXHAUST. OUR | | | INSPECTORS ARE NOT ALWAYS AWARE OF THE COMMENTS DURING | | | PLAN REVIEW AND LOCATIONS EACH PRODUCT APPROVAL CAN OR | | | CANNOT BE INSTALLED. | | | 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE ENGINEER | | | OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED AS | | | INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT WILL | | | BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS PRESSURE | | | GOING TO BE GREATER THAN THAT OF PRESSURES DESIGN | | | PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 2C-2D) COMPLIED. | | | | | | 2E) COMPLIED.5/18/2020. E-MAIL SENT TO | | | [email protected] | | | REQUEST FOR ALTEERNATE MATERIALS & METHODS. BUILDING | | | OFFICIAL BELIEVES WITH THE SUBMITTED DOCUMENTS & | | | CALCULATIONS THAT IS SUFFICIENT TO MEET THE ENTENT OF | | | THE CODE. ALTERNANTE MATERIALS & METHODS WOULD NOT NEED | | | TO BE USED. WE WILL STILL NEED THE SUBMITTED DOCUMENTS | | | TO SUBSTANUATE CODE COMPLIANCE. | | | | | | NEW COMMENT: 5/03/2020. THIS COMMENT DEALS WITH THE | | | REQUEST FOR ALTERNATE MATERIALS & METHOD REQUEST FOR | | | THE GENERATOR EXHAUST REQUIREMENTS INSTEAD OF A LOUVER | | | REQUIRED UNDER COMPONENTS AND CLADDING REQUIREMENTS OF | | | THE FBC-B 6TH EDITION. I SENT AN E-MAIL ( 4-27-2020) | | | .TO MY SUPERVISOR SAMANTHA HILL & ASSISTANT BUILDING | | | OFFICIAL DYLAN BATTLES ABOUT THIS REQUEST. MS. HILL HAS | | | BEEN IN CONTACT WITH MS. FELICIA SAFFOLD ABOUT WHAT IS | | | REQUIRED FOR AN ALTERNATE MATERIALS, METHODS DESIGN AND | | | METHODS OF CONSTRUCTION AND EQUIPMENT 104.11 OF THE | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE | | | 6TH EDITION, CHAPTER 1, ADMINISTRATION. MS. SAFFOLD | | | INDICATED BY E-MAIL THAT THEY WOULD BE APPLYING SHORTLY | | | FOR ALTERNATE MATERIALS & METHODS. THIS REQUEST SHOULD | | | BE ADDRESSED TO THE BUILDING OFFICIAL ROBERT BROWN. | | | | | | 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS | | | WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE | | | CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 4) SEMI-COMPLIED. SEE COMMENT 2A. | | | | | | 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L | | | 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW | | | COMPLIANCE WITH: | | | WELDED OR BOLTED CONNECTIONS | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE | | | AMERICAN WELDING SOCIETY. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS | | | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING | | | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. | | | | | | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-03-12 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-03-12 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-12 07:44:04 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19111204 | | | ADD: 6329 N. JOG RD. | | | CONT: ALL-SITE CONSTRUCTION INC. | | | TEL: 561-848-1110 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: THURS. MARCH12TH/ 2020 | | | ACTION: DENIED | | | | | | NOTICE ONLY!!!!!!!! 4X FEE / NOTICE!!!!! FLORIDA | | | STATUTE 553.80(2)(B) | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | | | | | 1) 2ND REQUEST. THE RESPONSE INDICATES THE WIND DESIGN | | | CRITERIA CAN BE FOUND ON SHEET S-001 REVISION # 1. | | | PLEASE NOTE THERE WERE NO NEW SHEETS ADDED OR REVISION | | | IN THE ARCHITECTURAL OR STRUCTURAL SHEETS. PLEASE ALSO | | | NOTE THE REVIEW COMMENTS LOOK LIKE THEY WERE DEVELOPED | | | BY THE CONTRACTOR (ALL-SITE CONSTRUCTION, INC.) AND NOT | | | THE DESIGNER OF RECORD FOR THIS PROJECT. | | | 1ST REVIEW COMMENT. THE DEMOLITION, ARCHITECTURAL AND | | | STRUCTURAL SHEETS ALL SHOW NEW COMPONENTS AND CLADDING | | | TO THE EXTERIOR OF THE BUILDING, BUT THERE IS NO WIND | | | DESIGN CRITERIA GIVEN. 2017 FBC-B 1603.1.4 WIND DESIGN | | | DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | | STRUCTURE: | | | | | | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS | | | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. | | | | | | 1.2. RISK CATEGORY. | | | | | | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. | | | HEIGHT AND EXPOSURE. | | | | | | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | | | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENTS AND CLADDING MATERIALS. | | | | | | 1.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & | | | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE | | | BUILDING. | | | | | | 1.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. | | | | | | 1.8 IT WOULD APPEAR THE NEW AND REPLACEMENT EXTERIOR | | | DOORS ARE IN THE WALL ZONE 5, HIGHER PRESSURES. | | | | | | 2A) 2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR | | | AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR | | | REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED | | | NEW DOOR. | | | PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE | | | COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2 | | | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & | | | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, | | | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ | | | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS , | | | | | | 2B) 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE | | | ENGINEER OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED | | | AS INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT | | | WILL BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS | | | PRESSURE GOING TO BE GREATER THAN THAT OF PRESSURES | | | DESIGN PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2. | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 2C) 2ND REQUEST. WITHIN THE GENERATOR ROOM WHEN THE | | | GENERATOR IS RUNNING WILL THE PRESSURES WITHIN THIS | | | ROOM BE NEUTRAL TO WHERE YOU WILL BE ABLE TO OPEN THE | | | EXTERIOR MAN DOOR AS WELL AS THE DOUBLE DOORS TO THE | | | NEW SWITCH GEAR? 107.2.1.2 ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 2D) 2ND REQUEST. THE SAME CONCERN OF WHAT TYPE OF | | | PRESSURES WILL BE EXERTED ON THE NEW PROPOSED 2 HR. | | | FIRE RATED WALLS. PLEASE PROVIDE THE DEFLECTION | | | LIMITATIONS FOR THE NEW WALL SEE THE 2017 FBC-B TABLE | | | 1604.3. | | | | | | 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS | | | WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE | | | CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 4) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW | | | DOOR. WITHIN ALL OF THE PRODUCT APPROVALS PLEASE CIRCLE | | | ALL RELATIVE SECTIONS THAT PERTAIN TO THE SITE SPECIFIC | | | INSTALLATION INCLUDING PRESSURES, ANCHORS, SPACING OF | | | ANCHORS, ETC. 2017 FBC-M- 301.15 WIND RESISTANCE. | | | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE | | | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO | | | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L | | | 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW | | | COMPLIANCE WITH: | | | WELDED OR BOLTED CONNECTIONS | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE | | | AMERICAN WELDING SOCIETY. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS | | | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING | | | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. | | | | | | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-01-06 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-01-06 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2020-01-06 08:04:33 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19111204 | | | ADD: 6329 N. JOG RD. | | | CONT: ALL-SITE CONSTRUCTION INC. | | | TEL: 561-848-1110 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MONDAY JAN. 6TH/ 2020 | | | ACTION: DENIED | | | | | | 1) THE DEMOLITION, ARCHITECTURAL AND STRUCTURAL SHEETS | | | ALL SHOW NEW COMPONENTS AND CLADDING TO THE EXTERIOR OF | | | THE BUILDING, BUT THERE IS NO WIND DESIGN CRITERIA | | | GIVEN. 2017 FBC-B 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | | STRUCTURE: | | | | | | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS | | | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. | | | | | | 1.2. RISK CATEGORY. | | | | | | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. | | | HEIGHT AND EXPOSURE. | | | | | | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | | | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENTS AND CLADDING MATERIALS. | | | | | | 1.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & | | | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE | | | BUILDING. | | | | | | 1.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. | | | | | | 2A) PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE | | | COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2 | | | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & | | | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, | | | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ | | | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS , | | | (C) PANEL WALLS: WALL LOUVERS FOR BOTH INTAKE AND | | | EXHAUST, BOTH INTAKE AND EXHAUST FANS, WALL | | | MOUNTED. | | | | | | 2B) NOTE IF LOUVERS ARE TO BE INSTALLED AS INTAKE OR | | | EXHAUST LOUVERS AND THE PRESSURES THAT WILL BE EXERTED | | | ON THE LOUVER WHEN IN USE, IS THIS PRESSURE GOING TO BE | | | GREATER THAN THAT OF PRESSURES DESIGN PRESSURES FOR | | | HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 2C) WITHIN THE GENERATOR ROOM WHEN THE GENERATOR IS | | | RUNNING WILL THE PRESSURES WITHIN THIS ROOM BE NEUTRAL | | | TO WHERE YOU WILL BE ABLE TO OPEN THE EXTERIOR MAN DOOR | | | AS WELL AS THE DOUBLE DOORS TO THE NEW SWITCH GEAR? | | | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 2D) THE SAME CONCERN OF WHAT TYPE OF PRESSURES WILL BE | | | EXERTED ON THE NEW PROPOSED 2 HR. FIRE RATED WALLS. | | | PLEASE PROVIDE THE DEFLECTION LIMITATIONS FOR THE NEW | | | WALL SEE THE 2017 FBC-B TABLE 1604.3. | | | | | | 3) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE | | | SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 4) WITHIN ALL OF THE PRODUCT APPROVALS PLEASE CIRCLE | | | ALL RELATIVE SECTIONS THAT PERTAIN TO THE SITE SPECIFIC | | | INSTALLATION INCLUDING PRESSURES, ANCHORS, SPACING OF | | | ANCHORS, ETC. 2017 FBC-M- 301.15 WIND RESISTANCE. | | | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE | | | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO | | | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 5) SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L 4X4 SS | | | FRAME AROUND THE INTAKE FANS PLEASE SHOW COMPLIANCE | | | WITH: | | | WELDED OR BOLTED CONNECTIONS | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE | | | AMERICAN WELDING SOCIETY. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS | | | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING | | | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. | | | | | | 6) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-23 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-23 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2020-03-23 08:12:15 | REVIEWED BY JAKE LEAHY. | | 2020-03-22 09:13:08 | JL | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-12-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-12-25 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-12-25 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2019-12-25 13:03:41 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. IT APPEARS THAT THE NEW SWITCHGEAR WILL NOT HAVE THE | | | REQUIRED CLEARANCE ON THE SOUTH SIDE DUE TO THE | | | EXISTING REMOTE I/O CABINET. PROVIDE CLARIFICATION | | | AND/OR CORRECTION AS NEEDED. NEC 110.34 | | | 2. FIRE ALARM, ACCESS CONTROL, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-09 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2019-12-09 12:25:01 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL | | | BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED | | | FIRE SPRINKLER CONTRACTORS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-06-09 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-06-09 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-06-04 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-05-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-05-04 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-23 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-23 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-03 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-01-09 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-01-09 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-06 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2020-06-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-06-09 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-06-09 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2020-06-09 15:09:42 | I HAVE APPROVED THIS PROJECT AS IT MEETS FBC M 501.3.2 | | | WITH THE 1/2" OPENINGS IN THE SCREEN COVERING THE | | | OPENING FOR THE GENERATOR RADIATOR EXHAUST. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2020-04-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-04-28 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-04-28 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2020-04-28 15:05:21 | 3RD REVIEW FBC-2017 | | | PERMIT #19111204 | | | 4/28/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL COMMENT RESPONSE DOCUMENT DATED | | | 4/14/2020 DOES NOT BEAR THE NAME OF THE ENGINEER, | | | ARCHITECT, CONTRACTOR, QUALIFIER OR OTHER PERSON TO | | | IDENTIFY WHO PREPARED THE DOCUMENT AND PROVIDED THE | | | RESPONSES. A) ITEM #3 IN THE RESPONSE DOCUMENT | | | INDICATES THE CONTRACTOR SHALL INSURE THERE IS A DRAIN | | | ON THE FLOOR OF THE GENERATOR ROOM TO REMOVE ANY WATER | | | ON THE FLOOR TO THE OUTSIDE. PLEASE CLARIFY IF THERE IS | | | AN EXISTING FLOOR DRAIN IN THE ROOM IN PROXIMITY OF THE | | | RADIATOR SHROUD OR IF A NEW DRAIN WILL BE INSTALLED. | | | | | | 2) ALTERNATE APPROVAL LETTER FOR MECHANICAL: A) PROVIDE | | | EVIDENCE THAT THE ALTERNATIVE MESH SCREEN WHICH | | | INCLUDES A CHAIN LINK FENCE IS EQUIVALENT TO A | | | MANUFACTURED LOUVER IN CORROSION RESISTANCE, AND IN | | | PREVENTING WATER INTRUSION- SEE SECTION 501.3.2 FBC M: | | | "EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE | | | PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR | | | GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL | | | BE SIZED NOT LESS THAN 1/4 INCH (6.4 MM) AND NOT LARGER | | | THAN 1/2 INCH (12.7 MM). OPENINGS SHALL BE PROTECTED | | | AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT | | | EXHAUST OPENINGS IN STRUCTURES LOCATED IN | | | HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA | | | BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA | | | STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR | | | WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL | | | OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING." B) THE LETTER THAT IS | | | INDICATED TO BE FROM CATERPILLAR IS NOT FROM | | | CATERPILLAR COMPANY BUT IS AN EMAIL FROM A MR. ROBERT | | | BUTT WHO IS EMPLOYED BY PANTROPIC POWER, THEREFORE NOT | | | ACCEPTABLE EVIDENCE OF COMPLIANCE PER MANUFACTURER'S | | | GUIDELINES AND SPECIFICATIONS. C) SHEETS M-201, A-002, | | | A-005: THE EXHAUST LOUVER IS NOT CALLED OUT ON THE | | | MECHANICAL PLAN AND IS IDENTIFIED AS TYPICAL CHAIN LINK | | | FENCE DETAIL ON THE ARCHITECTURAL PLANS. PLEASE | | | PROPERLY IDENTIFY THE EXHAUST SCREEN PROPERLY TO | | | CORRELATE WITH THE THE ALTERNATE APPROVAL REQUEST. | | | AT THIS TIME THERE IS NOT ENOUGH EVIDENCE TO PROVE THAT | | | THE PROPOSED EXHASUT SCREEN DESIGN IS EQUIVALENT OF | | | THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH, | | | EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY- | | | SEE SECTION 104.11 FBC B. | | | | | | 3) SHEETS A-002, A-003, M-201: THE NORTH ELEVATION VIEW | | | AND THE FAN INSTALLATION DETAILL DO NOT INDICATE THE | | | LV-3 AND LV-4 LOUVERS TO BE INSTALLED OVER INTAKE FANS | | | SAF-1 AND SAF-2 AS IS INDICATED ON SHEET M201. PLEASE | | | REVIEW COMMENT #2 FROM THE 1ST REVIEW COPIED BELOW. | | | M-201 & M-401: THE DETAIL SHOWING THE ATTACHMENT OF THE | | | LOUVERS DIRECTLY TO SAF 1 & 2 MAY NOT BE CONSISTENT | | | WITH THE APPROVED INSTALLATION DETAILS SHOWN IN THE | | | MIAMI-DADE NOA FOR THE LOUVER. PLEASE SUBMIT TWO COPIES | | | OF THE NOA WITH APPLICABLE INSTALLATION DETAILS CIRCLED | | | OR HIGHLIGHTED. | | | THE LOUVER NOA HAS BEEN SUBMITTED HOWEVER NO ATTACHMENT | | | DETAILS HAVE BEEN MARKED. PLEASE NOTE THAT THE LOUVER | | | SPECIFIES ATTACHMENT INTO STRUCTURAL SUBSTRATES AND | | | ALSO SPECIFIES TYPES AND SIZES OF FASTENERS, SPACING OF | | | FASTENERS, EDGE DISTANCE CLEARANCES, AND DEPTHS OF | | | EMBEDMENT. ALL OF THESE DETAILS MUST BE CALLED OUT BY | | | THE EOR. | | | | | | 4) THE ENGINE EXHAUST PIPING TERMINATIONS ON THE | | | DRAWINGS APPEAR TO BE OPEN TO WATER INTRUSION. ARE | | | THESE ACTUAL FIELD CONDITIONS OR JUST A RENDERING? ARE | | | THE EXHAUST PIPES BEING REPLACED? HOW ARE THEY | | | SUPPORTED? PLEASE PROVIDE SPECIFIC DETAILS TO ADDRESS | | | THESE ISSUES- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-23 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-23 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2020-03-23 10:25:16 | REVIEWED BY JAMES BAKER, PE | | | | | | FAILED SEE COMMENTS BELOW: | | | 1) 2017 FMC 501.3.2 EXHAUST OPENING PROTECTION. THE | | | CHAIN LINK FENCE PROPOSED MUST HAVE OPENINGS NO LARGER | | | THAN 1/2INCH AND NO SMALLER THAN 1/4INCH. PLEASE | | | INDICATE ON DRAWINGS. | | | | | | | | | 2) 2017 FBC 107.2.1 CONFIRM AND PROVIDE LETTER FROM | | | GENERATOR MANUFACTURER THAT BARRIER WALL WILL NOT | | | IMPEDE THE EXHAUST AIRFLOW TO THE POINT OF CAUSING | | | EXCESSIVE HEAT BUILD UP IN GENERATOR AND EXCESSIVE LOSS | | | OF EFFICIENCY. | | | | | | | | | 3) 2017 FBC 107.2.1 FURTHER EVALUATE ANY POTENTIAL FOR | | | RAIN PENETRATION THROUGH THE 1/2 CHAIN LINK FENCE INTO | | | THE DUCTWORK ATTACHING THE GENERATOR EXHAUST TO THE | | | OPENING. SUGGEST CONSULTING THE GENERATOR ENGINEERING | | | DEPARTMENT. | | | | | | 561-805-6724 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-27 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-27 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2019-12-27 11:21:01 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19111204 | | | 12/27/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS D-102 & M-201: INDICATE HOW THE GENERATOR | | | RADIATOR DISCHARGE OPENING WILL BE PROTECTED- SECTION | | | 501.3.2 FBC M. | | | | | | 2) M-201 & M-401: THE DETAIL SHOWING THE ATTACHMENT OF | | | THE LOUVERS DIRECTLY TO SAF 1 & 2 MAY NOT BE CONSISTENT | | | WITH THE APPROVED INSTALLATION DETAILS SHOWN IN THE | | | MIAMI-DADE NOA FOR THE LOUVER. PLEASE SUBMIT TWO COPIES | | | OF THE NOA WITH APPLICABLE INSTALLATION DETAILS CIRCLED | | | OR HIGHLIGHTED. | | | | | | 3) M-301: SUBMIT THE MIAMI- DADE NOA FOR THE EXHAUST | | | FANS EF-1 & EF-2- RULE 9-N3 FAC. PLEASE CIRCLE OR | | | HIGHLIGHT ALL APPLICABLE INSTALLATION DETAILS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2020-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-06-08 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-06-08 |
Time |
16:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-05-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-05-03 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-05-03 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2020-04-28 15:33:34 | MECH PLANS AND DOCUMENTS PREPARED BY THE EOR OK. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-22 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-22 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2020-03-27 11:42:27 | 3/27/20 RECEIVED ORIGINAL APPLICATION. LEM | | 2020-03-22 09:48:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. DIGITAL SIGNATURES ARE OK. | | | | | | 2. THIS APPLICATION HAS A PRINT HOLD FOR THE ORIGINAL | | | APPLICATION. PLEASE MAIL TO: | | | | | | PERMIT LIBRARIAN | | | BUILDING DIVISION, 1ST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | | | | YOUR PERMIT WILL BE SENT TO YOU VIA EMAIL. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-01-06 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-01-06 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2020-04-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-04-28 |
Time |
10:27 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2020-04-28 |
Time |
10:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-03-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-03-18 |
Time |
16:25 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2020-03-18 |
Time |
16:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-01-09 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-01-09 |
Time |
13:41 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2020-01-09 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2020-01-09 14:01:51 | FAILED | | | | | | 1) PROVIDE A SURVEY WHICH CLEARLY INDICATES WHICH | | | BUILDING IS SUBJECT TO THIS PERMIT, SO STAFF CAN VERIFY | | | THE WORK, INCLUDING THE NEW WALL AND FENCING. THE SITE | | | PLANS PROVIDED ARE AT SUCH A SMALL SCALE THAT ZONING | | | STAFF IS UNABLE TO VERIFY THE BUILDING LOCATION, SO THE | | | SURVEY NEEDS TO BE AT A LARGER SCALE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | |
|
|
|