Plan Review Details - Permit 19111204
Plan Review Stops For Permit 19111204
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-01-06 Cont ID  
Sent By shill Date 2020-01-06 Time 15:36 Rev Time 0.00
Received By shill Date 2020-01-06 Time 15:36 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 08:05 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 08:05 Sent To  
Notes
2020-01-06 08:05:44ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-05 Cont ID  
Sent By jwitmer Date 2020-06-05 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2020-06-05 Time 16:28 Sent To  
Notes
2020-06-05 16:57:362017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: JUNE 05TH/ 2020
 ACTION: BUILDING PROVISO:
 1) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L
 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW
 COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-03 Cont ID  
Sent By jwitmer Date 2020-05-03 Time 14:26 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 14:30 Sent To  
Notes
2020-05-03 14:26:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MARCH27TH- MAY 03RD/ 2020
 ACTION: DENIED
  
 1) SEMI-COMPLIED. THE DESIGNER OF RECORD HAS RESPONDED
 TO THIS ROUND OF COMMENTS, THANK YOU. THERE IS GOING TO
 BE A QUESTION LATER IN THIS REVIEW ABOUT THE ALTERNATE
 MATERIALS & METHODS REQUEST, HOW TO SUBMIT.
  
 2A) 3RD REQUEST SEMI-COMPLIED. THIS EXTERIOR DOOR
 TESTING REPORT MANUFACTURER PHILADELPHIA HARDWARE GROUP
 (PHG) IS FOR A STEEL EXTERIOR DOOR, 5 PAGES LONG. THIS
 DOCUMENT ALONE DOES NOT MEET THE REQUIREMENTS FORM THE
 STATE OF FLORIDA FOR A PRODUCT APPROVAL.
 THERE ARE NO DOCUMENTS SUBMITTED FOR THE INDEPENDENT
 3RD PARTY CERTIFICATION REQUIRED BY THE STATE FOR A
 STATE APPROVAL OR FOR A LOCAL WEST PALM BEACH LOCAL OR
 SITE PRODUCT APPROVAL.
  
 2A)2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR
 AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR
 REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED
 NEW DOOR. . FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010.
 PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE
 COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
  
 2B) 3RD REQUEST. SEMI-COMPLIED. THERE IS A MIAMI-DADE
 NOA 17-0919.04 SUBMITTED. SINCE THERE ARE 2 ISSUES WITH
 LOUVERED OPENINGS WE NEED TO HAVE LISTED ON THE NOA FOR
 WHICH OPENINGS THIS PRODUCT IS GOING TO BE SUBMITTED
 FOR? 2ND IT ALSO NEEDS TO BE UNDERSTOOD THAT THERE IS A
 LETTER TO BE SUBMITTED FOR THE GENERATOR EXHAUST. OUR
 INSPECTORS ARE NOT ALWAYS AWARE OF THE COMMENTS DURING
 PLAN REVIEW AND LOCATIONS EACH PRODUCT APPROVAL CAN OR
 CANNOT BE INSTALLED.
 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE ENGINEER
 OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED AS
 INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT WILL
 BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS PRESSURE
 GOING TO BE GREATER THAN THAT OF PRESSURES DESIGN
 PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2C-2D) COMPLIED.
  
 2E) COMPLIED.5/18/2020. E-MAIL SENT TO
 [email protected]
 REQUEST FOR ALTEERNATE MATERIALS & METHODS. BUILDING
 OFFICIAL BELIEVES WITH THE SUBMITTED DOCUMENTS &
 CALCULATIONS THAT IS SUFFICIENT TO MEET THE ENTENT OF
 THE CODE. ALTERNANTE MATERIALS & METHODS WOULD NOT NEED
 TO BE USED. WE WILL STILL NEED THE SUBMITTED DOCUMENTS
 TO SUBSTANUATE CODE COMPLIANCE.
  
 NEW COMMENT: 5/03/2020. THIS COMMENT DEALS WITH THE
 REQUEST FOR ALTERNATE MATERIALS & METHOD REQUEST FOR
 THE GENERATOR EXHAUST REQUIREMENTS INSTEAD OF A LOUVER
 REQUIRED UNDER COMPONENTS AND CLADDING REQUIREMENTS OF
 THE FBC-B 6TH EDITION. I SENT AN E-MAIL ( 4-27-2020)
 .TO MY SUPERVISOR SAMANTHA HILL & ASSISTANT BUILDING
 OFFICIAL DYLAN BATTLES ABOUT THIS REQUEST. MS. HILL HAS
 BEEN IN CONTACT WITH MS. FELICIA SAFFOLD ABOUT WHAT IS
 REQUIRED FOR AN ALTERNATE MATERIALS, METHODS DESIGN AND
 METHODS OF CONSTRUCTION AND EQUIPMENT 104.11 OF THE
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE
 6TH EDITION, CHAPTER 1, ADMINISTRATION. MS. SAFFOLD
 INDICATED BY E-MAIL THAT THEY WOULD BE APPLYING SHORTLY
 FOR ALTERNATE MATERIALS & METHODS. THIS REQUEST SHOULD
 BE ADDRESSED TO THE BUILDING OFFICIAL ROBERT BROWN.
  
 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS
 WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE
 CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) SEMI-COMPLIED. SEE COMMENT 2A.
  
 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L
 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW
 COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jwitmer Date 2020-03-12 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2020-03-12 Time   Sent To  
Notes
2020-03-12 07:44:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MARCH12TH/ 2020
 ACTION: DENIED
  
 NOTICE ONLY!!!!!!!! 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 1) 2ND REQUEST. THE RESPONSE INDICATES THE WIND DESIGN
 CRITERIA CAN BE FOUND ON SHEET S-001 REVISION # 1.
 PLEASE NOTE THERE WERE NO NEW SHEETS ADDED OR REVISION
 IN THE ARCHITECTURAL OR STRUCTURAL SHEETS. PLEASE ALSO
 NOTE THE REVIEW COMMENTS LOOK LIKE THEY WERE DEVELOPED
 BY THE CONTRACTOR (ALL-SITE CONSTRUCTION, INC.) AND NOT
 THE DESIGNER OF RECORD FOR THIS PROJECT.
 1ST REVIEW COMMENT. THE DEMOLITION, ARCHITECTURAL AND
 STRUCTURAL SHEETS ALL SHOW NEW COMPONENTS AND CLADDING
 TO THE EXTERIOR OF THE BUILDING, BUT THERE IS NO WIND
 DESIGN CRITERIA GIVEN. 2017 FBC-B 1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS.
  
 1.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 1.8 IT WOULD APPEAR THE NEW AND REPLACEMENT EXTERIOR
 DOORS ARE IN THE WALL ZONE 5, HIGHER PRESSURES.
  
 2A) 2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR
 AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR
 REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED
 NEW DOOR.
 PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE
 COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
  
 2B) 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE
 ENGINEER OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED
 AS INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT
 WILL BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS
 PRESSURE GOING TO BE GREATER THAN THAT OF PRESSURES
 DESIGN PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2C) 2ND REQUEST. WITHIN THE GENERATOR ROOM WHEN THE
 GENERATOR IS RUNNING WILL THE PRESSURES WITHIN THIS
 ROOM BE NEUTRAL TO WHERE YOU WILL BE ABLE TO OPEN THE
 EXTERIOR MAN DOOR AS WELL AS THE DOUBLE DOORS TO THE
 NEW SWITCH GEAR? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2D) 2ND REQUEST. THE SAME CONCERN OF WHAT TYPE OF
 PRESSURES WILL BE EXERTED ON THE NEW PROPOSED 2 HR.
 FIRE RATED WALLS. PLEASE PROVIDE THE DEFLECTION
 LIMITATIONS FOR THE NEW WALL SEE THE 2017 FBC-B TABLE
 1604.3.
  
 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS
 WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE
 CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW
 DOOR. WITHIN ALL OF THE PRODUCT APPROVALS PLEASE CIRCLE
 ALL RELATIVE SECTIONS THAT PERTAIN TO THE SITE SPECIFIC
 INSTALLATION INCLUDING PRESSURES, ANCHORS, SPACING OF
 ANCHORS, ETC. 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L
 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW
 COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 06:37 Sent To  
Notes
2020-01-06 08:04:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JAN. 6TH/ 2020
 ACTION: DENIED
  
 1) THE DEMOLITION, ARCHITECTURAL AND STRUCTURAL SHEETS
 ALL SHOW NEW COMPONENTS AND CLADDING TO THE EXTERIOR OF
 THE BUILDING, BUT THERE IS NO WIND DESIGN CRITERIA
 GIVEN. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS.
  
 1.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2A) PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE
 COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
 (C) PANEL WALLS: WALL LOUVERS FOR BOTH INTAKE AND
 EXHAUST, BOTH INTAKE AND EXHAUST FANS, WALL
 MOUNTED.
  
 2B) NOTE IF LOUVERS ARE TO BE INSTALLED AS INTAKE OR
 EXHAUST LOUVERS AND THE PRESSURES THAT WILL BE EXERTED
 ON THE LOUVER WHEN IN USE, IS THIS PRESSURE GOING TO BE
 GREATER THAN THAT OF PRESSURES DESIGN PRESSURES FOR
 HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2C) WITHIN THE GENERATOR ROOM WHEN THE GENERATOR IS
 RUNNING WILL THE PRESSURES WITHIN THIS ROOM BE NEUTRAL
 TO WHERE YOU WILL BE ABLE TO OPEN THE EXTERIOR MAN DOOR
 AS WELL AS THE DOUBLE DOORS TO THE NEW SWITCH GEAR?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) THE SAME CONCERN OF WHAT TYPE OF PRESSURES WILL BE
 EXERTED ON THE NEW PROPOSED 2 HR. FIRE RATED WALLS.
 PLEASE PROVIDE THE DEFLECTION LIMITATIONS FOR THE NEW
 WALL SEE THE 2017 FBC-B TABLE 1604.3.
  
 3) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE
 SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) WITHIN ALL OF THE PRODUCT APPROVALS PLEASE CIRCLE
 ALL RELATIVE SECTIONS THAT PERTAIN TO THE SITE SPECIFIC
 INSTALLATION INCLUDING PRESSURES, ANCHORS, SPACING OF
 ANCHORS, ETC. 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 5) SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L 4X4 SS
 FRAME AROUND THE INTAKE FANS PLEASE SHOW COMPLIANCE
 WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 08:11 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 08:11 Sent To  
Notes
2020-03-23 08:12:15REVIEWED BY JAKE LEAHY.
2020-03-22 09:13:08JL
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-25 Cont ID  
Sent By jpearson Date 2019-12-25 Time 13:03 Rev Time 0.00
Received By jpearson Date 2019-12-25 Time 13:03 Sent To  
Notes
2019-12-25 13:03:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IT APPEARS THAT THE NEW SWITCHGEAR WILL NOT HAVE THE
 REQUIRED CLEARANCE ON THE SOUTH SIDE DUE TO THE
 EXISTING REMOTE I/O CABINET. PROVIDE CLARIFICATION
 AND/OR CORRECTION AS NEEDED. NEC 110.34
 2. FIRE ALARM, ACCESS CONTROL, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-09 Cont ID  
Sent By pleduc Date 2019-12-09 Time   Rev Time 0.00
Received By pleduc Date 2019-12-09 Time 12:23 Sent To  
Notes
2019-12-09 12:25:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED
 FIRE SPRINKLER CONTRACTORS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-09 Cont ID  
Sent By lmarchan Date 2020-06-09 Time 15:37 Rev Time 0.00
Received By lmarchan Date 2020-06-04 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-04 Cont ID  
Sent By lmarchan Date 2020-05-04 Time 10:04 Rev Time 0.00
Received By lmarchan Date 2020-04-23 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-23 Cont ID  
Sent By shill Date 2020-03-23 Time 12:04 Rev Time 0.00
Received By shill Date 2020-03-03 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-09 Cont ID  
Sent By lmarchan Date 2020-01-09 Time 14:35 Rev Time 0.00
Received By lmarchan Date 2019-12-06 Time 15:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-06-09 Cont ID  
Sent By medwards Date 2020-06-09 Time 15:07 Rev Time 0.00
Received By medwards Date 2020-06-09 Time 13:37 Sent To  
Notes
2020-06-09 15:09:42I HAVE APPROVED THIS PROJECT AS IT MEETS FBC M 501.3.2
 WITH THE 1/2" OPENINGS IN THE SCREEN COVERING THE
 OPENING FOR THE GENERATOR RADIATOR EXHAUST.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-04-28 Cont ID  
Sent By ccole Date 2020-04-28 Time 15:03 Rev Time 0.00
Received By ccole Date 2020-04-28 Time 08:54 Sent To  
Notes
2020-04-28 15:05:213RD REVIEW FBC-2017
 PERMIT #19111204
 4/28/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL COMMENT RESPONSE DOCUMENT DATED
 4/14/2020 DOES NOT BEAR THE NAME OF THE ENGINEER,
 ARCHITECT, CONTRACTOR, QUALIFIER OR OTHER PERSON TO
 IDENTIFY WHO PREPARED THE DOCUMENT AND PROVIDED THE
 RESPONSES. A) ITEM #3 IN THE RESPONSE DOCUMENT
 INDICATES THE CONTRACTOR SHALL INSURE THERE IS A DRAIN
 ON THE FLOOR OF THE GENERATOR ROOM TO REMOVE ANY WATER
 ON THE FLOOR TO THE OUTSIDE. PLEASE CLARIFY IF THERE IS
 AN EXISTING FLOOR DRAIN IN THE ROOM IN PROXIMITY OF THE
 RADIATOR SHROUD OR IF A NEW DRAIN WILL BE INSTALLED.
  
 2) ALTERNATE APPROVAL LETTER FOR MECHANICAL: A) PROVIDE
 EVIDENCE THAT THE ALTERNATIVE MESH SCREEN WHICH
 INCLUDES A CHAIN LINK FENCE IS EQUIVALENT TO A
 MANUFACTURED LOUVER IN CORROSION RESISTANCE, AND IN
 PREVENTING WATER INTRUSION- SEE SECTION 501.3.2 FBC M:
 "EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR
 GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL
 BE SIZED NOT LESS THAN 1/4 INCH (6.4 MM) AND NOT LARGER
 THAN 1/2 INCH (12.7 MM). OPENINGS SHALL BE PROTECTED
 AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT
 EXHAUST OPENINGS IN STRUCTURES LOCATED IN
 HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA
 STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR
 WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL
 OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING." B) THE LETTER THAT IS
 INDICATED TO BE FROM CATERPILLAR IS NOT FROM
 CATERPILLAR COMPANY BUT IS AN EMAIL FROM A MR. ROBERT
 BUTT WHO IS EMPLOYED BY PANTROPIC POWER, THEREFORE NOT
 ACCEPTABLE EVIDENCE OF COMPLIANCE PER MANUFACTURER'S
 GUIDELINES AND SPECIFICATIONS. C) SHEETS M-201, A-002,
 A-005: THE EXHAUST LOUVER IS NOT CALLED OUT ON THE
 MECHANICAL PLAN AND IS IDENTIFIED AS TYPICAL CHAIN LINK
 FENCE DETAIL ON THE ARCHITECTURAL PLANS. PLEASE
 PROPERLY IDENTIFY THE EXHAUST SCREEN PROPERLY TO
 CORRELATE WITH THE THE ALTERNATE APPROVAL REQUEST.
 AT THIS TIME THERE IS NOT ENOUGH EVIDENCE TO PROVE THAT
 THE PROPOSED EXHASUT SCREEN DESIGN IS EQUIVALENT OF
 THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY-
 SEE SECTION 104.11 FBC B.
  
 3) SHEETS A-002, A-003, M-201: THE NORTH ELEVATION VIEW
 AND THE FAN INSTALLATION DETAILL DO NOT INDICATE THE
 LV-3 AND LV-4 LOUVERS TO BE INSTALLED OVER INTAKE FANS
 SAF-1 AND SAF-2 AS IS INDICATED ON SHEET M201. PLEASE
 REVIEW COMMENT #2 FROM THE 1ST REVIEW COPIED BELOW.
 M-201 & M-401: THE DETAIL SHOWING THE ATTACHMENT OF THE
 LOUVERS DIRECTLY TO SAF 1 & 2 MAY NOT BE CONSISTENT
 WITH THE APPROVED INSTALLATION DETAILS SHOWN IN THE
 MIAMI-DADE NOA FOR THE LOUVER. PLEASE SUBMIT TWO COPIES
 OF THE NOA WITH APPLICABLE INSTALLATION DETAILS CIRCLED
 OR HIGHLIGHTED.
 THE LOUVER NOA HAS BEEN SUBMITTED HOWEVER NO ATTACHMENT
 DETAILS HAVE BEEN MARKED. PLEASE NOTE THAT THE LOUVER
 SPECIFIES ATTACHMENT INTO STRUCTURAL SUBSTRATES AND
 ALSO SPECIFIES TYPES AND SIZES OF FASTENERS, SPACING OF
 FASTENERS, EDGE DISTANCE CLEARANCES, AND DEPTHS OF
 EMBEDMENT. ALL OF THESE DETAILS MUST BE CALLED OUT BY
 THE EOR.
  
 4) THE ENGINE EXHAUST PIPING TERMINATIONS ON THE
 DRAWINGS APPEAR TO BE OPEN TO WATER INTRUSION. ARE
 THESE ACTUAL FIELD CONDITIONS OR JUST A RENDERING? ARE
 THE EXHAUST PIPES BEING REPLACED? HOW ARE THEY
 SUPPORTED? PLEASE PROVIDE SPECIFIC DETAILS TO ADDRESS
 THESE ISSUES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-23 Cont ID  
Sent By shill Date 2020-03-23 Time 12:03 Rev Time 0.00
Received By shill Date 2020-03-23 Time 10:24 Sent To  
Notes
2020-03-23 10:25:16REVIEWED BY JAMES BAKER, PE
  
 FAILED SEE COMMENTS BELOW:
 1) 2017 FMC 501.3.2 EXHAUST OPENING PROTECTION. THE
 CHAIN LINK FENCE PROPOSED MUST HAVE OPENINGS NO LARGER
 THAN 1/2INCH AND NO SMALLER THAN 1/4INCH. PLEASE
 INDICATE ON DRAWINGS.
  
  
 2) 2017 FBC 107.2.1 CONFIRM AND PROVIDE LETTER FROM
 GENERATOR MANUFACTURER THAT BARRIER WALL WILL NOT
 IMPEDE THE EXHAUST AIRFLOW TO THE POINT OF CAUSING
 EXCESSIVE HEAT BUILD UP IN GENERATOR AND EXCESSIVE LOSS
 OF EFFICIENCY.
  
  
 3) 2017 FBC 107.2.1 FURTHER EVALUATE ANY POTENTIAL FOR
 RAIN PENETRATION THROUGH THE 1/2 CHAIN LINK FENCE INTO
 THE DUCTWORK ATTACHING THE GENERATOR EXHAUST TO THE
 OPENING. SUGGEST CONSULTING THE GENERATOR ENGINEERING
 DEPARTMENT.
  
 561-805-6724

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By ccole Date 2019-12-27 Time 10:52 Rev Time 0.00
Received By ccole Date 2019-12-27 Time 10:52 Sent To  
Notes
2019-12-27 11:21:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19111204
 12/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS D-102 & M-201: INDICATE HOW THE GENERATOR
 RADIATOR DISCHARGE OPENING WILL BE PROTECTED- SECTION
 501.3.2 FBC M.
  
 2) M-201 & M-401: THE DETAIL SHOWING THE ATTACHMENT OF
 THE LOUVERS DIRECTLY TO SAF 1 & 2 MAY NOT BE CONSISTENT
 WITH THE APPROVED INSTALLATION DETAILS SHOWN IN THE
 MIAMI-DADE NOA FOR THE LOUVER. PLEASE SUBMIT TWO COPIES
 OF THE NOA WITH APPLICABLE INSTALLATION DETAILS CIRCLED
 OR HIGHLIGHTED.
  
 3) M-301: SUBMIT THE MIAMI- DADE NOA FOR THE EXHAUST
 FANS EF-1 & EF-2- RULE 9-N3 FAC. PLEASE CIRCLE OR
 HIGHLIGHT ALL APPLICABLE INSTALLATION DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-06-08 Cont ID  
Sent By shill Date 2020-06-08 Time 16:30 Rev Time 0.00
Received By shill Date 2020-06-08 Time 16:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-03 Cont ID  
Sent By shill Date 2020-05-03 Time 11:43 Rev Time 0.00
Received By shill Date 2020-05-03 Time 11:43 Sent To  
Notes
2020-04-28 15:33:34MECH PLANS AND DOCUMENTS PREPARED BY THE EOR OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-22 Cont ID  
Sent By shill Date 2020-03-22 Time 09:46 Rev Time 0.00
Received By shill Date 2020-03-22 Time 09:46 Sent To  
Notes
2020-03-27 11:42:273/27/20 RECEIVED ORIGINAL APPLICATION. LEM
2020-03-22 09:48:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES ARE OK.
  
 2. THIS APPLICATION HAS A PRINT HOLD FOR THE ORIGINAL
 APPLICATION. PLEASE MAIL TO:
  
 PERMIT LIBRARIAN
 BUILDING DIVISION, 1ST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
  
 YOUR PERMIT WILL BE SENT TO YOU VIA EMAIL.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By shill Date 2020-01-06 Time 15:39 Rev Time 0.00
Received By shill Date 2020-01-06 Time 15:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-04-28 Cont ID  
Sent By eschneid Date 2020-04-28 Time 10:27 Rev Time 0.25
Received By eschneid Date 2020-04-28 Time 10:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By eschneid Date 2020-03-18 Time 16:25 Rev Time 0.25
Received By eschneid Date 2020-03-18 Time 16:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By eschneid Date 2020-01-09 Time 13:41 Rev Time 0.50
Received By eschneid Date 2020-01-09 Time 12:09 Sent To  
Notes
2020-01-09 14:01:51FAILED
  
 1) PROVIDE A SURVEY WHICH CLEARLY INDICATES WHICH
 BUILDING IS SUBJECT TO THIS PERMIT, SO STAFF CAN VERIFY
 THE WORK, INCLUDING THE NEW WALL AND FENCING. THE SITE
 PLANS PROVIDED ARE AT SUCH A SMALL SCALE THAT ZONING
 STAFF IS UNABLE TO VERIFY THE BUILDING LOCATION, SO THE
 SURVEY NEEDS TO BE AT A LARGER SCALE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  