Sent To |
I |
|
| Notes |
| 2019-12-01 15:38:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. THIS RESPONSIBLE PERSON | | | SHOULD BE EITHER A DESIGN PROFESSIONAL LICENSED TO | | | DESIGN ELECTRICAL PLANS, OR THE ELECTRICAL CONTRACTOR | | | QUALIFIER. PROVIDE CORRECTION. WPB FBC 107.1; FS | | | 471/481 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-12-31 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-14 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-31 |
Time |
12:34 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-11-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-11-26 |
Time |
11:54 |
Sent To |
E |
|
| Notes |
| 2019-11-26 11:56:40 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE | | | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS | | | APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT. | | | | | | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR | | | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS | | | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF | | | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT | | | ALL OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS | | | AFFIXED TO THE DOOR LEAF. | | | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. | | | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE | | | HAND IN THE DIRECTION OF EGRESS. | | | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER | | | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE | | | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. | | | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE | | | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE | | | DIRECTION OF EGRESS. | | | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN | | | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS | | | CONTROL SYSTEM UNITS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-14 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-30 |
Time |
10:07 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-11-22 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2019-11-25 13:17:18 | ROUTED TO FIRE INBOX |
|
|
|