Plan Review Details - Permit 19111179
Plan Review Stops For Permit 19111179
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-03 Cont ID  
Sent By cthroop Date 2020-02-03 Time 10:51 Rev Time 0.00
Received By cthroop Date 2020-02-03 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By cthroop Date 2019-12-27 Time 13:55 Rev Time 0.00
Received By cthroop Date 2019-12-24 Time 13:25 Sent To  
Notes
2019-12-27 13:55:56PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 VALUE HAS BEEN CHANGED FROM $30,000 TO $57,710 PER THE
 ICC BUILDING VALUATION TABLES UPDATED AUGUST 2019.
  
 1. CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS.
 VALUATION ? BASED ON THE INTERNATIONAL CODE COUNCIL
 (ICC) BUILDING VALUATION DATA YOUR STATED VALUE APPEARS
 LOW.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. DESIGNER OF RECORD SHALL SIGN AND SEAL PLANS.
  
 ARCHITECT
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-24 Cont ID  
Sent By jpearson Date 2020-01-24 Time 15:31 Rev Time 0.00
Received By jpearson Date 2020-01-24 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By jpearson Date 2019-12-18 Time 10:11 Rev Time 0.00
Received By jpearson Date 2019-12-18 Time 06:50 Sent To  
Notes
2019-12-18 07:59:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED/SEALED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS 471,
 481; WPB FBC 107.1, 107.2.1, 107.3.5.1.2
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. AN ESTIMATED LOAD IS NOT
 ACCEPTABLE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. IF NONE
 ARE EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS.
 FBC RE R314.3, R315.1; WPB FBC 107.2.1
 5. THE GFCI PROTECTED RECEPTACLE OUTLET 3 FEET OF EACH
 BASIN SHALL BE LOCATED ON A WALL OR PARTITION THAT IS
 ADJACENT TO THE BASIN OR BASIN COUNTERTOP, LOCATED ON
 THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE
 BASIN CABINET. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D); FBC RE E3901.6
 6. LIGHTING IN CLOSET APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION OR NOTE FOR COMPLIANCE. NEC 410.16; FBC RE
 E4003.12
 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION OR NOTE
 FOR COMPLIANCE. NEC 410.10(D); FBC RE E4003.11
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-03 Cont ID  
Sent By cthroop Date 2020-02-03 Time 10:51 Rev Time 0.00
Received By cthroop Date 2020-01-07 Time 13:28 Sent To I
Notes
2020-01-08 13:28:35R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-27 Cont ID  
Sent By cthroop Date 2019-12-27 Time 14:14 Rev Time 0.00
Received By cthroop Date 2019-11-22 Time 13:41 Sent To  
Notes
2019-11-25 13:41:08R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-28 Cont ID  
Sent By cthroop Date 2020-02-28 Time 14:12 Rev Time 0.00
Received By cthroop Date 2020-02-28 Time 14:12 Sent To  
Notes
2020-02-28 14:13:25MU-2020-007214-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By cthroop Date 2019-12-27 Time 13:57 Rev Time 0.00
Received By cthroop Date 2019-12-24 Time 13:25 Sent To  
Notes
2019-12-27 13:58:17IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-03 Cont ID  
Sent By cthroop Date 2020-02-03 Time 10:52 Rev Time 0.00
Received By cthroop Date 2020-02-03 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By cthroop Date 2019-12-27 Time 14:10 Rev Time 0.00
Received By cthroop Date 2019-12-24 Time 13:25 Sent To  
Notes
2019-12-27 14:14:14PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 M 1.0 - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
 ARCHITECT
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By tklarge Date 2020-01-14 Time 08:15 Rev Time 0.00
Received By tklarge Date 2020-01-13 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-02 Cont ID  
Sent By lcrespo Date 2019-12-02 Time 17:46 Rev Time 0.00
Received By lcrespo Date 2019-12-02 Time 17:46 Sent To  
Notes
2019-12-02 17:46:2212/02/2019 2ND PLUMBING/ REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON P1 SHOWER AND TUB ARE LABELED AS FD PLEASE CHANGE
 TO CORRECT LABELS (TUB, SHOWER) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2. SHOWER NEEDS TO BE RAN OFF THE WET VENT NOT OFF THE
 TUB DRAIN LINE PER THE 2017 FBC SEC. R3108.1 HORIZONTAL
 WET VENT PERMITTED.
 3. THE PLANS ARE NOT SIGNED BY THE ARCHITECT OF RECORD,
 SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED (OR
 SEAL, OR TITLE BLOCK, OR ALL THREE) ARE NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 4. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION 2017 FBC SEC. 2708.4, R 2713.3
 BATHTUB AND WHIRLPOOL BATHTUB VALVES. (ADD TO PLUMBING
 NOTES)
 5. SHOWER CONTROL VALVES SHALL BE PRESSURE-BALANCED,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN 120
 F. (ADD TO PLUMBING NOTES)
 6. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING
 ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH
 ONE OF THE FOLLOWING MATERIALS. THE LINING MATERIAL
 SHALL EXTEND NOT LESS THAN 2 INCHES BEYOND OR AROUND
 THE ROUGH JAMBS AND NOT LESS THAN 2 INCHES ABOVE
 FINISHED THRESHOLDS. SHEET-APPLIED LOAD-BEARING, BONDED
 WATERPROOF MEMBRANES SHALL BE APPLIED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTRUCTIONS PER 2017 FBC SEC.
 R 2709.2.
 7. SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
 8. PLEASE SHOW A DETAIL OF THE SHOWER LINER
 INSTALLATION AND IF YOU ARE USING AN ALTERNATE METHOD
 IS MUST BE APPROVED AT THIS STAGE SO PROVIDE
 DOCUMENTATION FOR ALTERNATE PRODUCTS.
 9. HOT WATER RAN UNDER SLAB IN AN UN-CONDITION SPACE
 SHALL BE INSULATED PER THE 2017 FBC EC RE 403.5.3.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-02-03 Cont ID  
Sent By cthroop Date 2020-02-03 Time 10:52 Rev Time 0.00
Received By cthroop Date 2020-02-03 Time 09:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-12-27 Cont ID  
Sent By cthroop Date 2019-12-27 Time 13:58 Rev Time 0.00
Received By cthroop Date 2019-12-24 Time 13:25 Sent To  
Notes
2019-12-27 13:59:38PLAN REVIEW - ROOFING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. DESIGNER OF RECORD SHALL SIGN AND SEAL PLANS.
  
 ARCHITECT
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-10 Cont ID  
Sent By llouie Date 2020-01-10 Time   Rev Time 0.00
Received By llouie Date 2020-01-10 Time   Sent To  
Notes
2020-01-10 09:39:27VALUE OF SCOPE OF WORK INCREASED TO $57,710 PER
 BUILDING REVIEW COMMENT. INCREASE IN VALUE DOES NOT
 TRIGGER THE 50% THRESHOLD FOR LANDSCAPE IMPROVEMENT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By llouie Date 2019-12-09 Time   Rev Time  
Received By llouie Date 2019-12-09 Time   Sent To  
Notes
2019-12-09 16:56:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLANS MUST BE SIGNED AND SEALED BY THE ARCHITECT.
  
  
 NOTES:
  
 * SCOPE OF WORK DOES NOT EXCEED 50% THRESHOLD FOR
 LANDSCAPE UPGRADE.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  