Plan Review Details - Permit 19111096
Plan Review Stops For Permit 19111096
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-01-06 Cont ID  
Sent By cpuell Date 2020-01-06 Time 16:00 Rev Time 0.00
Received By cpuell Date 2020-01-06 Time 16:00 Sent To  
Notes
2020-01-06 16:03:34ADDRESS CREATED 1/6/19 ADDRESSING INFO SENT TO
 APPROPRIATE AGENCIES CP

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-12-23 Cont ID  
Sent By cthroop Date 2019-12-23 Time 15:25 Rev Time 0.00
Received By cthroop Date 2019-12-23 Time 14:47 Sent To  
Notes
2019-12-23 15:26:02ADDRESSING
  
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2020-09-17 Cont ID  
Sent By cthroop Date 2020-09-17 Time 08:07 Rev Time 0.00
Received By cthroop Date 2020-09-17 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 07:39 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 07:03 Sent To  
Notes
2020-08-29 07:52:01PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 5TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 1- CORRECTED
  
 2- CORRECTED
  
 3- CORRECTED
  
 4- IMPACT FEE. (SEE IMPACT FEE REVIEW)
  
  
 5- DESIGNER SHALL SELECT MODEL OF EXTERIOR DOORS TO BE
 INSTALLED. SUBMITTED FL14982-R2 EXTERIOR FIBERGLASS
 DOOR.
 (FRONT DOOR FL14982-R2 IS A NON-IMPACT RATED DOOR.
 OPENING PROTECTION REQUIRED. PROVIDE SHUTTER SCHEDULE)
  
 DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
 (NOT ADDRESSED) (SELECT MODELS TO BE INSTALLED. IF
 NON-IMPACT RATED PROVIDE SHUTTER SCHEDULE)
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 A) CORRECTED
  
 B) CORRECTED
  
 C) CORRECTED
  
 D) CORRECTED
  
 E) CORRECTED
  
 NEW COMMENTS: 4TH REVIEW
  
 6- CORRECTED
  
 7- CORRECTED
  
 8- CORRECTED
  
 A) CORRECTED
  
 D) CORRECTED
  
 E) CORRECTED
  
 F) CORRECTED
  
 G) CORRECTED
  
 9- CORRECTED
  
 10- CORRECTED
  
 11- CORRECTED
  
 12- CORRECTED
  
 13- CORRECTED
  
 NEW COMMENTS: 5TH REVIEW
  
 14 - NOTE ON PLAN PAGE A-1.0 STATES FRONT DOOR (A)
 SHALL BE SOLID WOOD. PRODUCT APPROVAL SUBMITTED FOR
 REVIEW FL14982-R2 IS FOR A NON-IMPACT RATED FIBERGLASS
 DOOR. PLEASE CLARIFY.
  
 15 - HOUSEKEEPING - PLEASE REMOVE ANY DOCUMENTS FROM
 YOUR SUBMITTAL THAT ARE NOT RELEVANT TO THE PROJECT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 08:57 Rev Time 0.00
Received By cthroop Date 2020-07-02 Time 07:26 Sent To  
Notes
2020-07-06 09:35:17PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 4TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 ****IMPORTANT:
 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER
 PRIOR TO ISSUING THE PERMIT. - CORRECTED
  
 1- CORRECTED
  
 2- CORRECTED
  
 3- CORRECTED
  
 4- IMPACT FEE. (SEE IMPACT FEE REVIEW)
  
  
 5- DESIGNER SHALL SELECT MODEL OF EXTERIOR DOORS TO BE
 INSTALLED. (NOT ADDRESSED)
 (FRONT DOOR FL14982-R2 IS A NON-IMPACT RATED DOOR.
 OPENING PROTECTION REQUIRED. PROVIDE SHUTTER SCHEDULE)
  
 DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
 (NOT ADDRESSED) (SELECT MODELS TO BE INSTALLED. IF
 NON-IMPACT RATED PROVIDE SHUTTER SCHEDULE)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 A) CORRECTED
  
 B) CORRECTED
  
 C) CORRECTED
  
 D) NEED PRODUCT APPROVAL FOR ARCHED ENTRY DOOR AS SHOWN
 ON PLANS. (NOT ADDRESSED)
  
 E) CORRECTED
  
 NEW COMMENTS:
  
 6- CORRECTED
  
 7- CORRECTED
  
 8- CORRECTED
  
 A) CORRECTED
  
 D) CORRECTED
  
 E) CORRECTED
  
 F) CORRECTED
  
 G) CORRECTED
  
 9- CORRECTED
  
 10- CORRECTED
  
 11- CORRECTED
  
 12- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL. (NOT CORRECTED)
  
 13- CORRECTED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 13:52 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 12:02 Sent To  
Notes
2020-06-24 15:05:02PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 2ND REVIEW
  
  
 ****IMPORTANT:
 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER
 PRIOR TO ISSUING THE PERMIT.
  
 1- CORRECTED
  
 2- CORRECTED
  
 3- CORRECTED
  
 4- IMPACT FEE. (SEE IMPACT FEE REVIEW)
  
  
 5- DESIGNER SHALL SELECT MODEL OF EXTERIOR DOORS TO BE
 INSTALLED. (NOT ADDRESSED)
  
 DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
 (NOT ADDRESSED)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 A) METAL ROOFING. (NOT ADDRESSED)
  
 B) ROOFING TILES.(NOT ADDRESSED)
  
 C) GARAGE OVERHEAD DOOR DOOR. NEED TO PROVIDE PRODUCT
 APPROVAL FOR DOOR THAT MEETS THE DESIGN PRESSURE
 CALCULATED BY THE ARCHITECT OF RECORD ON SHEET A-2.0.
 (NOT ADDRESSED)
  
 D) NEED PRODUCT APPROVAL FOR ARCHED ENTRY DOOR AS SHOWN
 ON PLANS. (NOT ADDRESSED)
  
 E) NEED PRODUCT APPROVAL FOR FLAT ROOF AT THE PORTE
 COCHERE. (NOT ADDRESSED)
  
 NEW COMMENTS:
  
 6- SPECIFIED FOOTING SIZE WF5 -20 DOESN'T COMPLY WITH
 THE MINIMUM FOOTING DEPTH REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE FOOTING SIZE AS REQUIRED. NOTE:
 REVISE TYPICAL WALL SECTION ON SHEET A-3.0 ALSO. KEEP
 IN MIND THAT NEED TO PROVIDE THE 6" CLEARANCE FOR
 TERMITE INSPECTION. (NOT ADDRESSED)
  
 7- TYPE OF DOOR SHOWN ON THE DOOR TYPES ON SHEET A-1.0
 DOESN'T MATCH TYPE OF DOOR SHOWN ON THE EXTERIOR
 ELEVATION. EXTERIOR ELEVATION SHOWS AN ARCHED DOOR.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS. PRODUCT APPROVAL REQUIRED FOR ARCHED DOOR.
 (NOT ADDRESSED)
  
 8- ENERGY CALCULATIONS SUBMITTED: (NOT ADDRESSED)
  
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING COMPLETE ADDRESS, OWNER'S INFORMATION, THE
 BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 (604700). SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 C) THE AREA WEIGHTED AVERAGE SHGC SHOWN ON ITEM #7 ON
 PAGE 1 DOESN'T COMPLY WITH THE MAXIMUM FENESTRATION
 SHGC REQUIRED BY SEC. R405.5.3.4 OF FBC-ENERGY
 CONSERVATION. THE MAXIMUM AREA WEIGHTED AVERAGE
 FENESTRATION SHGC ALLOWED IS 0.50. ENERGY CALCULATIONS
 SUBMITTED SHOW 0.754. REVISE AS REQUIRED TO COMPLY.
  
 D) FLOOR TYPE SHOWN ON ITEM #8 ON PAGE 1 IS INCORRECT
 AND IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. (NOT
 ADDRESSED)
  
 E)REVISE ITEM #9(A) TO MATCH PLANS. INSULATION R-VALUE
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. (NOT
 ADDRESSED)
  
 F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5.
 TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2
 FBC-RESIDENTIAL. OR PERSON PREPARING THE ENERGY
 CALCULATIONS TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2. NOTE: ARCHITECT OF RECORD
 NEEDS TO REVIEW/APPROVE THEM PRIOR TO SUBMITTAL. (NOT
 ADDRESSED)
  
 G) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. (NOT
 ADDRESSED)
  
 9- ARCHITECTURAL PLANS SHOW CEILING FANS AND THE ENERGY
 CALCULATIONS ARE TAKING THE CREDIT FOR THEM. NEED TO
 SPECIFY THE CEILING FAN SIZE ON EACH ROOM SHOWING
 COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION.
 (NOT ADDRESSED)
  
 10- CORRECTED
  
 11- PROPOSED FLOOR PLAN ON SHEET A-1.0 SHOWS 3'-0"
 MASONRY OPENING FOR THE ENTRY DOOR. THIS MASONRY
 OPENING DIMENSION IS INCORRECT FOR THE REQUIRED 3'-0"
 DOOR. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 (NOT CORRECTED)
  
 12- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL. (NOT CORRECTED)
  
 13- NEW PORTE COCHERE: (NOT ADDRESSED)
 A) ROOF FRAMING PLAN ON SHEET S-2.0: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE FASTENING OF THE
 2X10 ROOF JOISTS. PROVIDE COMPLETE DETAILS/SPECS FOR
 THE WOOD LEDGER, FASTENERS, ETC. SEC. R301.2.1
 FBC-RESIDENTIAL.
 NOTE: THERE IS NOT METAL ROOFING ON A FLAT ROOF. REVISE
 ROOF SPECS.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ROOF DRAINAGE INCLUDING EMERGENCY
 SCUPPERS. SEC. R903.4 FBC-RESIDENTIAL. (NOT ADDRESSED)
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-30 Cont ID  
Sent By jgomez Date 2020-03-30 Time 13:22 Rev Time 0.00
Received By jgomez Date 2020-03-30 Time 09:04 Sent To  
Notes
2020-03-30 13:23:33NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ****IMPORTANT:
 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER
 PRIOR TO ISSUING THE PERMIT.
  
  
  
 1- OK.
 2- OK
  
 ORIGINAL COMMENT:
 3- PROVIDE SITE DRAINAGE PLAN. IT APPEARS THE SUBMITTED
 PLAN DRAINS TOWARD THE REAR OF THE PROPERTY.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
  
 RESPONSE:
 REPEAT COMMENT. NO DRAINAGE PLAN WAS SUBMITTED.
  
 ORIGINAL COMMENT:
 4- IMPACT FEE.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 RESPONSE:
 NO DONE YET. THIS CAN BE DONE LATER ONCE THE PLANS ARE
 APPROVED.
  
 ORIGINAL COMMENT:
 5- DESIGNER SHALL SELECT MODEL OF EXTERIOR DOORS TO BE
 INSTALLED.
 DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 RESPONSE:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) METAL ROOFING. FLORIDA PRODUCT APPROVAL FL21082-R2
 WAS SUBMITTED WITH INFORMATION FOR CONCRETE TILE AND IS
 MISSING THE INFORMATION FOR THE METAL ROOF. PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS FOR THE METAL ROOF.
  
 B) ROOFING TILES. FLORIDA PRODUCT APPROVAL FL7849-R11
 SUBMITTED IS INCOMPLETE. PROVIDE COMPLETE INSTALLATION
 INSTRUCTIONS AND CLEARLY MARK FASTENING METHOD. NOTE:
 SEE PLANS FOR LOCATION OF PROPOSED INSTALLATION.
 ADDITIONAL PRODUCT APPROVALS MAY BE REQUIRED BASED ON
 THE PROPOSED INSTALLATION METHOD. SEE ARCHITECT'S
 EXTERIOR ELEVATIONS.
  
 C) GARAGE OVERHEAD DOOR DOOR. NEED TO PROVIDE PRODUCT
 APPROVAL FOR DOOR THAT MEETS THE DESIGN PRESSURE
 CALCULATED BY THE ARCHITECT OF RECORD ON SHEET A-2.0.
  
 D) NEED PRODUCT APPROVAL FOR ARCHED ENTRY DOOR AS SHOWN
 ON PLANS.
  
 E)FLAT ROOF FOR THE PORTE COCHERE. AND, CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
 NEW COMMENTS:
 6- SPECIFIED FOOTING SIZE WF5 -20 DOESN'T COMPLY WITH
 THE MINIMUM FOOTING DEPTH REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE FOOTING SIZE AS REQUIRED. NOTE:
 REVISE TYPICAL WALL SECTION ON SHEET A-3.0 ALSO. KEEP
 IN MIND THAT NEED TO PROVIDE THE 6" CLEARANCE FOR
 TERMITE INSPECTION.
  
 7- TYPE OF DOOR SHOWN ON THE DOOR TYPES ON SHEET A-1.0
 DOESN'T MATCH TYPE OF DOOR SHOWN ON THE EXTERIOR
 ELEVATION. EXTERIOR ELEVATION SHOWS AN ARCHED DOOR.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS. PRODUCT APPROVAL REQUIRED FOR ARCHED DOOR.
  
 8- ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING COMPLETE ADDRESS, OWNER'S INFORMATION, THE
 BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 (604700). SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C) THE AREA WEIGHTED AVERAGE SHGC SHOWN ON ITEM #7 ON
 PAGE 1 DOESN'T COMPLY WITH THE MAXIMUM FENESTRATION
 SHGC REQUIRED BY SEC. R405.5.3.4 OF FBC-ENERGY
 CONSERVATION. THE MAXIMUM AREA WEIGHTED AVERAGE
 FENESTRATION SHGC ALLOWED IS 0.50. ENERGY CALCULATIONS
 SUBMITTED SHOW 0.754. REVISE AS REQUIRED TO COMPLY.
  
 D) FLOOR TYPE SHOWN ON ITEM #8 ON PAGE 1 IS INCORRECT
 AND IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)REVISE ITEM #9(A) TO MATCH PLANS. INSULATION R-VALUE
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5.
 TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2
 FBC-RESIDENTIAL. OR PERSON PREPARING THE ENERGY
 CALCULATIONS TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2. NOTE: ARCHITECT OF RECORD
 NEEDS TO REVIEW/APPROVE THEM PRIOR TO SUBMITTAL.
  
 G) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 9- ARCHITECTURAL PLANS SHOW CEILING FANS AND THE ENERGY
 CALCULATIONS ARE TAKING THE CREDIT FOR THEM. NEED TO
 SPECIFY THE CEILING FAN SIZE ON EACH ROOM SHOWING
 COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION.
  
 10- ALL THE DESIGN PARAMETERS INFORMATION SHOWN ON THE
 COVER SHEET AND SHEET A-1.0 ARE VERY DIFFERENT. WHICH
 ONE IS THE CORRECT ONE FOR THIS PROJECT?. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PROPOSED FLOOR PLAN ON SHEET A-1.0 SHOWS 3'-0"
 MASONRY OPENING FOR THE ENTRY DOOR. THIS MASONRY
 OPENING DIMENSION IS INCORRECT FOR THE REQUIRED 3'-0"
 DOOR. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL.
  
 13- NEW PORTE COCHERE:
 A) ROOF FRAMING PLAN ON SHEET S-2.0: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE FASTENING OF THE
 2X10 ROOF JOISTS. PROVIDE COMPLETE DETAILS/SPECS FOR
 THE WOOD LEDGER, FASTENERS, ETC. SEC. R301.2.1
 FBC-RESIDENTIAL.
 NOTE: THERE IS NOT METAL ROOFING ON A FLAT ROOF. REVISE
 ROOF SPECS.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ROOF DRAINAGE INCLUDING EMERGENCY
 SCUPPERS. SEC. R903.4 FBC-RESIDENTIAL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By cthroop Date 2019-12-24 Time 09:56 Rev Time 0.00
Received By cthroop Date 2019-12-23 Time 14:45 Sent To  
Notes
2019-12-24 10:09:02PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE ICC BUILDING EVALUATION TABLES, THE
 VALUE HAS BEE CHANGED FROM 104,725 TO 226,910.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 2. ADDRESS. - SEE ADDRESS REVIEW.
  
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
 3. PROVIDE SITE DRAINAGE PLAN. IT APPEARS THE SUBMITTED
 PLAN DRAINS TOWARD THE REAR OF THE PROPERTY.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
  
 4. IMPACT FEE.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 5. DESIGNER SHALL SELECT MODEL OF EXTERIOR DOORS TO BE
 INSTALLED.
 DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 10:02 Rev Time 0.00
Received By cthroop Date 2020-07-02 Time 07:27 Sent To  
Notes
2020-07-06 10:02:46NO COMMENTS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 15:43 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 12:02 Sent To  
Notes
2020-06-24 15:46:33PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 2ND ELECTRICAL REVIEW HAVE NOT BEEN
 ADDRESSED. BELOW IS A COPY FOR YOUR REFERENCE.
  
 ELECTRICAL REVIEW STATUS: DENIED - DENIED
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SHEET E-2.0, NOTE 14, THE NEC AND FBC SPECIFIED FOR
 DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)(2ND REVIEW: NOT
 CORRECTED.)
 2. SEVERAL NOTES THROUGHOUT INDICATE AFCI PROTECTION
 THAT IS NOT CODE COMPLIANT. REMOVE AND/OR EDIT NOTES TO
 REFLECT CURRENT CODE COMPLIANCE. ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (2ND REVIEW: NOT
 CORRECTED.)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (I SEE THAT A SEPARATE SHEET IS INCLUDED
 WITH THIS INFORMATION, BUT IT IS NOT SHOWN ON THE
 SIGNED/SEALED PLANS. PROVIDE CORRECTION.)
 4. CORRECTED.
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (2ND
 REVIEW: NOT CORRECTED.)
 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS BASED ON THE METHOD PRESCRIBED IN FBC
 RESIDENTIAL. NEC 220; FBC RE E3602.2 (2ND REVIEW: NOT
 CORRECTED, ALL LOADS NOT INCLUDED.)
 7. RISER DIAGRAM PROVIDED, BUT NEEDS CORRECTIONS. SEE
 NOTES BELOW.
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANEL IN MAIN
 HOUSE. NEC 225.31, 225.32 (2ND REVIEW: NOT CORRECTED.)
 9. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (2ND REVIEW: NOT
 CORRECTED.)
 10. CORRECTED.
 NEW COMMENTS:
 11. RISER DIAGRAM SHOWS A METER MAIN COMBO WITH FEED
 THROUGH LUGS, AND THEN A SEPARATE DISCONNECT NEXT TO
 THIS METER MAIN. WHAT IS THE PURPOSE OF THIS
 DISCONNECT? ADDITIONALLY, THE WIRE SIZE TO THIS
 DISCONNECT IS SHOWN AS 1/0, WHICH IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16);
 FBC RE E3603.1, E3705.1; WPB FBC 107.2.1
 12. WIRE SIZE TO PANEL A IS NOT SIZED CORRECTLY. BASED
 ON THE 200 AMP OVERCURRENT PROTECTION SHOWN, THESE
 CONDUCTORS SHOULD BE SIZED FOR 200 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1, E3705.1
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
 SINCERELY,
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-20 Cont ID  
Sent By jpearson Date 2020-03-20 Time 10:57 Rev Time 0.00
Received By jpearson Date 2020-03-20 Time 10:57 Sent To  
Notes
2020-03-20 09:40:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SHEET E-2.0, NOTE 14, THE NEC AND FBC SPECIFIED FOR
 DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)(2ND REVIEW: NOT
 CORRECTED.)
 2. SEVERAL NOTES THROUGHOUT INDICATE AFCI PROTECTION
 THAT IS NOT CODE COMPLIANT. REMOVE AND/OR EDIT NOTES TO
 REFLECT CURRENT CODE COMPLIANCE. ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (2ND REVIEW: NOT
 CORRECTED.)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (I SEE THAT A SEPARATE SHEET IS INCLUDED
 WITH THIS INFORMATION, BUT IT IS NOT SHOWN ON THE
 SIGNED/SEALED PLANS. PROVIDE CORRECTION.)
 4. CORRECTED.
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (2ND
 REVIEW: NOT CORRECTED.)
 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS BASED ON THE METHOD PRESCRIBED IN FBC
 RESIDENTIAL. NEC 220; FBC RE E3602.2 (2ND REVIEW: NOT
 CORRECTED, ALL LOADS NOT INCLUDED.)
 7. RISER DIAGRAM PROVIDED, BUT NEEDS CORRECTIONS. SEE
 NOTES BELOW.
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANEL IN MAIN
 HOUSE. NEC 225.31, 225.32 (2ND REVIEW: NOT CORRECTED.)
 9. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (2ND REVIEW: NOT
 CORRECTED.)
 10. CORRECTED.
  
 NEW COMMENTS:
  
 11. RISER DIAGRAM SHOWS A METER MAIN COMBO WITH FEED
 THROUGH LUGS, AND THEN A SEPARATE DISCONNECT NEXT TO
 THIS METER MAIN. WHAT IS THE PURPOSE OF THIS
 DISCONNECT? ADDITIONALLY, THE WIRE SIZE TO THIS
 DISCONNECT IS SHOWN AS 1/0, WHICH IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16);
 FBC RE E3603.1, E3705.1; WPB FBC 107.2.1
 12. WIRE SIZE TO PANEL A IS NOT SIZED CORRECTLY. BASED
 ON THE 200 AMP OVERCURRENT PROTECTION SHOWN, THESE
 CONDUCTORS SHOULD BE SIZED FOR 200 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1, E3705.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By jpearson Date 2019-12-17 Time 14:55 Rev Time 0.00
Received By jpearson Date 2019-12-17 Time 11:14 Sent To  
Notes
2019-12-17 14:54:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-2.0, NOTE 14, THE NEC AND FBC SPECIFIED FOR
 DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. SEVERAL NOTES THROUGHOUT INDICATE AFCI PROTECTION
 THAT IS NOT CODE COMPLIANT. REMOVE AND/OR EDIT NOTES TO
 REFLECT CURRENT CODE COMPLIANCE. ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9; FBC RE E3606.3
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS BASED ON THE METHOD PRESCRIBED IN FBC
 RESIDENTIAL. NEC 220; FBC RE E3602.2
 7. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. IT APPEARS THAT
 THE SERVICE IS ON A SEPARATE STRUCTURE FROM THE MAIN
 HOUSE. HOW WILL THE CIRCUITS IN THE GARAGE BE FEED?
 RISER DIAGRAM SHOULD ACCURATELY REFLECT WHAT EQUIPMENT
 WILL BE INSTALLED. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANEL IN MAIN
 HOUSE. NEC 225.31, 225.32
 9. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 10. RISER DIAGRAM SHOWS A #6 EQUIPMENT GROUNDING
 CONDUCTOR IN THE CONDUIT FROM THE METER CAN TO THE MAIN
 DISCONNECT. THE # 6 EQUIPMENT GROUNDING CONDUCTOR
 SHOULD NOT BE INCLUDED IN THIS CONDUIT. PROVIDE
 CORRECTION. NEC 250.6; FBC RE E3610.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-09-17 Cont ID  
Sent By cthroop Date 2020-09-17 Time 08:07 Rev Time 0.00
Received By cthroop Date 2020-09-16 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 14:40 Rev Time 0.00
Received By shill Date 2020-08-24 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-07 Cont ID  
Sent By cpuell Date 2020-08-07 Time 10:45 Rev Time 0.00
Received By cpuell Date 2020-07-01 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-01 Cont ID  
Sent By shill Date 2020-07-01 Time 15:22 Rev Time 0.00
Received By shill Date 2020-06-15 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-30 Cont ID  
Sent By jgomez Date 2020-03-30 Time 13:28 Rev Time 0.00
Received By jgomez Date 2020-02-26 Time 13:40 Sent To I
Notes
2020-02-27 13:40:27R39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-24 Cont ID  
Sent By cthroop Date 2019-12-24 Time 12:06 Rev Time 0.00
Received By cthroop Date 2019-11-21 Time 15:43 Sent To  
Notes
2019-12-04 15:43:47R39

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2020-10-09 Cont ID  
Sent By ccarvaja Date 2020-10-09 Time 18:46 Rev Time 0.00
Received By ccarvaja Date 2020-09-26 Time 07:07 Sent To  
Notes
2020-10-09 18:46:02RECEIPT MU - 2020 - 037890 - 0000 - $9,401.07 - PAID
2020-09-26 07:07:56EMAILED IMPACT OFFICE FOR REVIEW. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 13:47 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 13:47 Sent To  
Notes
2020-06-24 13:47:53IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-03-30 Cont ID  
Sent By jgomez Date 2020-03-30 Time 13:23 Rev Time 0.00
Received By jgomez Date 2020-03-30 Time 13:23 Sent To  
Notes
2020-03-30 13:24:05IMPACT FEES -
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By cthroop Date 2019-12-24 Time 09:30 Rev Time 0.00
Received By cthroop Date 2019-12-23 Time 14:45 Sent To  
Notes
2019-12-24 09:31:56IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-08-25 Cont ID  
Sent By medwards Date 2020-08-25 Time 14:52 Rev Time 0.00
Received By medwards Date 2020-08-25 Time 14:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 09:39 Rev Time 0.00
Received By cthroop Date 2020-07-02 Time 07:27 Sent To  
Notes
2020-07-06 09:39:50PLAN REVIEW - MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MECHANICAL PLAN MISSING FROM SUBMITTAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 15:14 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 12:02 Sent To  
Notes
2020-06-24 15:16:06PLAN REVIEW - MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MECHANICAL PLAN MISSING FROM SUBMITTAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-24 Cont ID  
Sent By medwards Date 2020-03-24 Time 11:52 Rev Time 0.00
Received By medwards Date 2020-03-24 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By cthroop Date 2019-12-24 Time 12:01 Rev Time 0.00
Received By cthroop Date 2019-12-23 Time 14:45 Sent To  
Notes
2019-12-24 12:06:32PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONTRACTOR OR DESIGNER OF RECORD TO PLACE TITLE
 BLOCK AND SIGN PLAN.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 2. PROVIDE BALANCED RETURN AIR PER M1602.3. RETURN AIR
 DUCTS IN BEDROOMS 1 AND 2 ARE UNDERSIZED.
  
 1.TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 15:37 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 12:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By jbaker Date 2020-03-19 Time 14:22 Rev Time 0.00
Received By jbaker Date 2020-03-19 Time 14:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-06 Cont ID  
Sent By lcrespo Date 2019-12-06 Time 16:07 Rev Time 0.00
Received By lcrespo Date 2019-12-06 Time 16:07 Sent To  
Notes
2019-12-06 16:07:2111/06/2019 1ST PLUMBING/ REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLUMBING SANITARY RISER HAS SHOWER AND LAV NOT
 VENTED CORRECTLY, SHOW LAV OFF VENT BETWEEN WATER
 CLOSET AND SHOWER OR IN A DOUBLE WYE PATTERN STRAIGHT
 TO WC AND USE ONE SIDE FOR LAV AND THE OTHER FOR SHOWER
 THAT WAY TRAP SEAL ARE PER 2017 FBC SEC. R3201.2.1 TRAP
 SEAL PROTECTION.
 2. LAV IN MASTER ON AAV NOT SHOWN ON ISOMETRIC DRAWING
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. WASHING MACHINE NOT VENTED OR P-TRAP SHOWN ON
 ISOMETRIC DRAWING NEED AAV OR VTR PER THE 2017 FBC SEC.
 R3201.2.1 TRAP SEAL PROTECTION/.
 4. KITCHEN DRAIN SHOWN AS AN 1 1/2" BUT IN MOST CASES A
 2 " LINE WORK BETTER FOR GREASE STOPPAGE REASON, NOT
 REQUIRED BUT RECOMMEND.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 09:35 Rev Time 0.00
Received By cthroop Date 2020-07-02 Time 07:26 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 15:19 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 12:02 Sent To  
Notes
2020-06-24 15:35:32PLAN REVIEW - ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PRIOR COMMENTS FROM 2ND REVIEW HAVE NOT BEEN ADDRESSED.
 BELOW IS A COPY OF 2ND REVIEW COMMENTS:
  
 ROOFING REVIEW:
  
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) METAL ROOFING. FLORIDA PRODUCT APPROVAL FL21082-R2
 WAS SUBMITTED WITH INFORMATION FOR CONCRETE TILE AND IS
 MISSING THE INFORMATION FOR THE METAL ROOF. PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS FOR THE METAL ROOF.
  
 B) ROOFING TILES. FLORIDA PRODUCT APPROVAL FL7849-R11
 SUBMITTED IS INCOMPLETE. PROVIDE COMPLETE INSTALLATION
 INSTRUCTIONS AND CLEARLY MARK FASTENING METHOD. NOTE:
 SEE PLANS FOR LOCATION OF PROPOSED INSTALLATION.
 ADDITIONAL PRODUCT APPROVALS MAY BE REQUIRED BASED ON
 THE PROPOSED INSTALLATION METHOD. SEE ARCHITECT'S
 EXTERIOR ELEVATIONS.
  
 C) FLAT ROOF FOR THE PORTE COCHERE. AND, CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-03-30 Cont ID  
Sent By jgomez Date 2020-03-30 Time 13:25 Rev Time 0.00
Received By jgomez Date 2020-03-30 Time 13:24 Sent To  
Notes
2020-03-30 13:26:34ROOFING REVIEW:
  
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) METAL ROOFING. FLORIDA PRODUCT APPROVAL FL21082-R2
 WAS SUBMITTED WITH INFORMATION FOR CONCRETE TILE AND IS
 MISSING THE INFORMATION FOR THE METAL ROOF. PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS FOR THE METAL ROOF.
  
 B) ROOFING TILES. FLORIDA PRODUCT APPROVAL FL7849-R11
 SUBMITTED IS INCOMPLETE. PROVIDE COMPLETE INSTALLATION
 INSTRUCTIONS AND CLEARLY MARK FASTENING METHOD. NOTE:
 SEE PLANS FOR LOCATION OF PROPOSED INSTALLATION.
 ADDITIONAL PRODUCT APPROVALS MAY BE REQUIRED BASED ON
 THE PROPOSED INSTALLATION METHOD. SEE ARCHITECT'S
 EXTERIOR ELEVATIONS.
  
 C) FLAT ROOF FOR THE PORTE COCHERE. AND, CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By cthroop Date 2019-12-24 Time 09:32 Rev Time 0.00
Received By cthroop Date 2019-12-23 Time 14:45 Sent To  
Notes
2019-12-24 09:36:27PLAN REVIEW - ROOFING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER TO SELECT METAL ROOFING SYSTEM TO BE
 INSTALLED.
 2. PROVIDE PRODUCT APPROVALS FOR SPANISH TILE.
 3. DESIGNER TO REVIEW AND APPROVE PRODUCT APPROVALS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-25 Cont ID  
Sent By medwards Date 2020-08-25 Time 14:57 Rev Time 0.00
Received By medwards Date 2020-08-25 Time 14:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 09:36 Rev Time 0.00
Received By cthroop Date 2020-07-02 Time 07:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-24 Cont ID  
Sent By cthroop Date 2020-06-24 Time 15:38 Rev Time 0.00
Received By cthroop Date 2020-06-24 Time 12:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-09-01 Cont ID  
Sent By rthermid Date 2020-09-01 Time   Rev Time 0.00
Received By rthermid Date 2020-09-01 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-08-06 Cont ID  
Sent By rthermid Date 2020-08-06 Time   Rev Time 0.00
Received By rthermid Date 2020-08-06 Time   Sent To I
Notes
2020-08-06 15:32:37ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/6/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE INDICATE THE SETBACKS FOR THE POSTS OF THE
 CARPORT.THE POSTS MUST MEET THE SETBACK REQUIREMENTS
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By rfalcone Date 2020-03-11 Time 12:40 Rev Time 0.00
Received By rfalcone Date 2020-03-11 Time 12:40 Sent To I
Notes
2020-03-11 12:40:48ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 3/11/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A SURVEY OF THE SUBJECT SITE.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-10 Cont ID  
Sent By rfalcone Date 2019-12-10 Time 15:15 Rev Time 0.00
Received By rfalcone Date 2019-12-10 Time 15:15 Sent To I
Notes
***NONE***