Plan Review Details - Permit 19110998
Plan Review Stops For Permit 19110998
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-12-20 Cont ID  
Sent By jpearson Date 2019-12-20 Time 09:58 Rev Time 0.00
Received By jpearson Date 2019-12-20 Time 09:58 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-12 Cont ID  
Sent By jpearson Date 2019-12-12 Time 09:19 Rev Time 0.00
Received By jpearson Date 2019-12-12 Time 09:19 Sent To  
Notes
2019-12-12 09:19:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481 (THE PLAN WAS SIGNED BY DAN DIDIO,
 WHO APPEARS NOT TO BE LICENSED IN THE STATE OF FLORIDA.
 THE RESPONSIBLE PERSON FOR THE DESIGN MUST BE THE
 ELECTRICAL CONTRACTOR QUALIFIER, OR A DESIGN
 PROFESSIONAL, LICENSED IN FLORIDA. PROVIDE CORRECTION.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-01 Cont ID  
Sent By jpearson Date 2019-12-01 Time 12:58 Rev Time 0.00
Received By jpearson Date 2019-12-01 Time 12:58 Sent To I
Notes
2019-12-01 12:58:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-20 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-16 Time 15:15 Sent To  
Notes
2019-12-17 15:15:48RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-10 Time 15:18 Sent To  
Notes
2019-12-11 15:18:18RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-12-01 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-20 Time 10:57 Sent To  
Notes
2019-11-21 10:58:02ROUTED TO ELECTRICAL INBOX