Plan Review Details - Permit 19110913
| Plan Review Stops For Permit 19110913 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-12-03 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-12-02 |
Time |
18:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-21 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2019-11-21 10:35:59 | CONVENTIONAL SHORING AND RESHORING PLANS, BUILDING | | | REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PLANS SUBMITTED ARE COPIES. NEED TO PROVIDE PLANS | | | WITH ORIGINAL DIGITAL SIGNATURE AS REQUIRED BY CHAPTER | | | 471 F.S. | | | NOTE: DRAWINGS NEED TO BE ON THE RIGHT ORIENTATION TO | | | BE OPENED AND READ WITHOUT HAVING TO ROTATE EACH | | | DRAWING. | | | | | | 2- INFORMATION SUBMITTED IS NOT PROPERLY DOWNLOADED. IF | | | SUBMITTING DRAWINGS, THEN THEY NEED TO BE UPLOADED | | | INDIVIDUALLY IN THE DRAWING FILE. OR IF YOU PREFER TO | | | DOWNLOAD FILE IN THE SUPPORTING DOCUMENTS, THEN ALL | | | DRAWINGS NEED TO BE SUBMITTED ON THE RIGHT ORIENTATION | | | TO BE READ WITHOUT HAVING TO ROTATE EACH DRAWING. | | | PLEASE COORDINATE WITH LIBRARIAN FOR PROPER DOWNLOADING | | | PROCEDURE. SEC. 107.2.1.2 CITY AMENDMENTS. | | | NOTE: PLEASE MAKE SURE ALL SUBMITTED DRAWINGS ARE THE | | | ONES REVIEWED/APPROVED BY THE ENGINEER OF RECORD. | | | | | | 3- IT LOOKS LIKE THE SHORING AND RESHORING DRAWINGS ARE | | | NOT FOR ALL FLOORS. CLEARLY SPECIFY ON THE SUBMITTAL | | | FORM WHAT FLOORS ARE COVERED IN THIS SUBMITTAL. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-12-03 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-25 |
Time |
10:58 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-19 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-12-03 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-12-03 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-21 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2019-11-21 10:36:22 | 1- PLANS SUBMITTED ARE COPIES. NEED TO PROVIDE PLANS | | | WITH ORIGINAL DIGITAL SIGNATURE AS REQUIRED BY CHAPTER | | | 471 F.S. | | | NOTE: DRAWINGS NEED TO BE ON THE RIGHT ORIENTATION TO | | | BE OPENED AND READ WITHOUT HAVING TO ROTATE EACH | | | DRAWING. |
|
|
|