Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 13:34 Rev Time 0.00
Received By dbattles Date 2020-02-07 Time 13:34 Sent To  
Notes
2020-02-07 13:35:23OK-LETTER ADDED TO SUPPORTING DOCUMENTS

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-01-28 Cont ID  
Sent By dbattles Date 2020-01-28 Time 08:56 Rev Time 0.00
Received By dbattles Date 2020-01-28 Time 08:01 Sent To  
Notes
2020-01-28 08:56:50COMMENT NOT ADDRESSED.
 PLEASE SEND VIA E-MAIL THE LETTER OF ACKNOWLEDGEMENT AS
 REQUESTED FROM 2ND REVIEW (SEE BELOW)
 [email protected]
  
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 W.P.B. PERMIT: 19110910
 REVIEWED: DECEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-01-14 Cont ID  
Sent By dbattles Date 2020-01-14 Time 08:21 Rev Time 0.00
Received By dbattles Date 2020-01-14 Time 08:19 Sent To  
Notes
2020-01-14 08:26:26COMMENT NOT ADDRESSED.
 PLEASE SEND VIA E-MAIL THE LETTER OF ACKNOWLEDGEMENT AS
 REQUESTED FROM FIRST REVIEW (SEE BELOW)
 [email protected]
  
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 W.P.B. PERMIT: 19110910
 REVIEWED: DECEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By dbattles Date 2019-12-18 Time 15:48 Rev Time 0.00
Received By dbattles Date 2019-12-18 Time 08:55 Sent To  
Notes
2019-12-18 15:51:28PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 W.P.B. PERMIT: 19110910
 REVIEWED: DECEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 13:35 Rev Time 0.00
Received By dbattles Date 2020-02-07 Time 13:35 Sent To  
Notes
2020-02-07 13:37:52PROVISOS:
 A) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 B) DEFERRED SUBMITTALS
 PROVIDE STAIRCASE AND GUARD RAIL ENGINEERING
 C) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By dbattles Date 2020-01-28 Time 08:52 Rev Time 0.00
Received By dbattles Date 2020-01-28 Time 08:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By dbattles Date 2020-01-14 Time 08:21 Rev Time 0.00
Received By dbattles Date 2020-01-13 Time 12:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By dbattles Date 2019-12-18 Time 15:48 Rev Time 0.00
Received By dbattles Date 2019-12-18 Time 08:55 Sent To  
Notes
2019-12-18 15:48:40BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19110910
 REVIEWED: DECEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 301.1 FBC[B]WHAT IS THE OCCUPANCY USE OF GENERATOR,
 TYPE OF FUEL, AMOUNT OF FUEL AND LOCATION OF FUEL
 STORAGE.
 THE GENERATOR WILL BE SEPARATE PERMIT, BUT GENERAL INFO
 IS NEEDED TO SEE WHAT SEPARATION THE WALLS NEED TO BE.
  
 2) 804.3.2 FBC[A]PLEASE PROVIDE DETAIL OF BREAKROOM TO
 SHOW COUNTER HEIGHT AND ANY ADDITIONAL DETAILS TO SHOW
 COMPLIANCE WITH FBC ACCESSIBILITY.
  
 3) 107.3.4.1 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, ROLL-UP DOOR AND ENTRY DOORS, LOUVERS AND A/C
 STANDS, OR INDICATE THAT THEY WILL BE DEFERRED.
 4) 107.3.4.1 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR
 LOW SLOPE ROOFING, OR INDICATE THAT THEY WILL BE
 DEFERRED.
 PROVISOS: NO COMMENT RESPONSE NEEDED, THESE WILL BE
 ADDED TO APPROVED PLANS.
 A) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 B) DEFERRED SUBMITTALS
 PROVIDE STAIRCASE AND GUARD RAIL ENGINEERING
 C) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-02-12 Cont ID  
Sent By jleahy Date 2020-02-12 Time 08:19 Rev Time 0.00
Received By jleahy Date 2020-02-12 Time 07:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By jpearson Date 2020-01-28 Time 07:18 Rev Time 0.00
Received By jpearson Date 2020-01-28 Time 07:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-10 Cont ID  
Sent By jleahy Date 2020-01-10 Time 15:52 Rev Time 0.00
Received By jleahy Date 2020-01-10 Time 15:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-20 Cont ID  
Sent By jleahy Date 2019-12-20 Time 09:04 Rev Time 0.00
Received By jleahy Date 2019-12-17 Time 14:16 Sent To  
Notes
2019-12-20 09:05:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-9
  
 ALL PANELS SHOWN AS 600 AMPERES

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By rrossano Date 2020-01-28 Time   Rev Time 0.00
Received By rrossano Date 2020-01-28 Time   Sent To I
Notes
2020-01-28 07:40:33CURRENTLY UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL
 E20010005.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2020-01-10 Cont ID  
Sent By rrossano Date 2020-01-10 Time   Rev Time 0.00
Received By rrossano Date 2020-01-10 Time   Sent To  
Notes
2020-01-10 14:40:41PLEASE SUBMIT FOR A FORMAL ENGINEERING SUBMITTAL
 REVIEW.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING
 ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By rrossano Date 2019-12-18 Time   Rev Time 0.00
Received By rrossano Date 2019-12-18 Time   Sent To I
Notes
2019-12-18 15:17:56PLEASE SUBMIT FOR A FORMAL ENGINEERING SUBMITTAL
 REVIEW.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING
 ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-02-10 Cont ID  
Sent By pleduc Date 2020-02-10 Time   Rev Time 0.00
Received By pleduc Date 2020-02-10 Time 10:07 Sent To  
Notes
2020-02-10 10:08:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND.
  
 ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM.
  
 ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
  
 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM.
  
 ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-01-27 Cont ID  
Sent By pleduc Date 2020-01-27 Time   Rev Time 0.00
Received By pleduc Date 2020-01-27 Time 08:51 Sent To  
Notes
2020-01-27 13:43:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND.
  
 ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM.
  
 ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
  
 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM.
  
 ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-13 Cont ID  
Sent By pleduc Date 2020-01-13 Time   Rev Time 0.00
Received By pleduc Date 2020-01-13 Time 14:52 Sent To  
Notes
2020-01-13 14:55:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND.
  
 ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM.
  
 ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
  
 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM.
  
 ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-16 Cont ID  
Sent By pleduc Date 2019-12-16 Time   Rev Time 0.00
Received By pleduc Date 2019-12-16 Time 13:28 Sent To  
Notes
2019-12-16 13:54:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND.
  
 ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM.
  
 ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
  
 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM.
  
 ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE ENSURE COOMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status N Date 2020-02-13 Cont ID  
Sent By tklarge Date 2020-02-13 Time 06:55 Rev Time 0.00
Received By tklarge Date 2020-02-13 Time 06:55 Sent To  
Notes
2020-02-13 06:55:58A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 T.LARGE
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2020-02-07 Time 15:18 Sent To  
Notes
2020-02-07 15:10:524THREVIEW: 19110910
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. THE CIVIL SITE PLAN SHOWS A 1000GAL PROPANE
 UNDERGROUND GAS TANK THE GAS PLAN SHOWS NATURAL GAS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE GAS ISOMETRIC ON SHEET P1 IS UNCLEAR SHT. L01
 SHOWS THE METER RIGHT OUTSIDE GENERATOR ROOM DOES THE
 GALVANIZED SCH 40 PIPING RUN UNDER THE SLAB IF SO IT
 SHALL BE SLEEVED THE ENTIRE LENGTH UNDER THE SLAB
 PROVIDE DETAIL FOR SLEEVING. PER FBC FG 404.14
  
 3. THE SIZING TABLE FOR CSST IS FOR 2PSI SYSTEM THE
 ISOMETRIC DRAWING IS SHOWING THE CSST UPSTREAM OF THE
 REGULATOR SO IT SHOULD BE UNDER 2PSI SYSTEM PLEASE
 CLARIFY WHICH SIZING TABLE YOU USING TO SIZE THE PIPING
 ON THE UNDER 2PSI SYSTEM. PER FBC FG 402.4
  
 4. USING TABLE 402.4(16) FOR 8" WC AS INDICATED ON THE
 GENERATOR WITH BTU LOAD OF 1,389,000 3EHD IS
 UNDERSIZED. PER FBC FG TABLE 402.4(16)
  
 5. PREVIOUS COMMENT PROVIDE MANUFACTURE SPECIFICATION
 FOR THE REGULATOR AND ISOLATION CONNECTOR FOR THE
 GENERATOR.. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-01-28 Cont ID  
Sent By gjohnson Date 2020-01-28 Time 14:05 Rev Time 0.00
Received By gjohnson Date 2020-01-27 Time 17:44 Sent To  
Notes
2020-01-28 14:05:283RD REVIEW: 19110910
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. THE CIVIL SITE PLAN SHOWS A 1000GAL PROPANE
 UNDERGROUND GAS TANK THE GAS PLAN SHOWS NATURAL GAS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE GAS ISOMETRIC ON SHEET P1 IS UNCLEAR SHT. L01
 SHOWS THE METER RIGHT OUTSIDE GENERATOR ROOM DOES THE
 GALVANIZED SCH 40 PIPING RUN UNDER THE SLAB IF SO IT
 SHALL BE SLEEVED THE ENTIRE LENGTH UNDER THE SLAB
 PROVIDE DETAIL FOR SLEEVING. PER FBC FG 404.14
  
 3. THE SIZING TABLE FOR CSST IS FOR 2PSI SYSTEM THE
 ISOMETRIC DRAWING IS SHOWING THE CSST UPSTREAM OF THE
 REGULATOR SO IT SHOULD BE UNDER 2PSI SYSTEM PLEASE
 CLARIFY WHICH SIZING TABLE YOU USING TO SIZE THE PIPING
 ON THE UNDER 2PSI SYSTEM. PER FBC FG 402.4
  
 4. USING TABLE 402.4(16) FOR 8" WC AS INDICATED ON THE
 GENERATOR WITH BTU LOAD OF 1,389,000 3EHD IS
 UNDERSIZED. PER FBC FG TABLE 402.4(16)
  
 5. PREVIOUS COMMENT PROVIDE MANUFACTURE SPECIFICATION
 FOR THE REGULATOR AND ISOLATION CONNECTOR FOR THE
 GENERATOR.. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-13 Cont ID  
Sent By shill Date 2020-01-13 Time 09:17 Rev Time 0.00
Received By shill Date 2020-01-13 Time 09:17 Sent To  
Notes
2020-01-13 09:17:22GAS 2ND REVIEW**DENIED**19110910**
  
 1) PLEASE CLARIFY WHICH KW GENERATOR YOU ARE USE AS
 SHT. S-1 AND P-1 CALL OUT 100KW BUT SHT. SC CALLS OUT
 150KW. PLEASE CLARIFY FBC 107.2.1
 2) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1
  
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-02-13 Cont ID  
Sent By shill Date 2020-02-13 Time 13:01 Rev Time 0.00
Received By shill Date 2020-02-12 Time 17:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-12 Cont ID  
Sent By jleahy Date 2020-02-12 Time 08:02 Rev Time 0.00
Received By jleahy Date 2020-02-07 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-28 Cont ID  
Sent By rfalcone Date 2020-01-28 Time 14:28 Rev Time 0.00
Received By lmarchan Date 2020-01-26 Time 07:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-14 Cont ID  
Sent By dbattles Date 2020-01-14 Time 08:21 Rev Time 0.00
Received By dbattles Date 2020-01-09 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-06 Cont ID  
Sent By lmarchan Date 2020-01-06 Time 09:05 Rev Time 0.00
Received By lmarchan Date 2019-12-13 Time 13:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-12-18 Cont ID  
Sent By dbattles Date 2019-12-18 Time 15:51 Rev Time 0.00
Received By dbattles Date 2019-12-18 Time 08:56 Sent To  
Notes
2019-12-18 15:52:41NO CHANGE IN OCCUPANCY

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By ccole Date 2020-02-07 Time 11:52 Rev Time 0.00
Received By ccole Date 2020-02-07 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-01-28 Cont ID  
Sent By ccole Date 2020-01-28 Time 11:36 Rev Time 0.00
Received By ccole Date 2020-01-28 Time 07:55 Sent To  
Notes
2020-01-28 11:36:453RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19110910
 1/28/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 (COMMENTS #1, 2, 4, 5 & 6 LISTED BELOW ARE REMAINING
 FROM THE 1ST AND 2ND REVIEW.)
  
 1) THE ENGINEER OF RECORD RESPONSIBLE FOR THE DESIGN
 SHALL PROVIDE AN APPROVAL STAMP ON THE SUBMITTED
 ENERGYGAUGE COMPLIANCE REPORT- SEE SECTION C103.1.1.2
 FBC EC. (THE EOR SHALL ALSO PROVIDE AN APPROVAL STAMP
 ON THE HVAC CALCULATIONS).
  
 2) THE WIND FORCE CALCULATIONS SHALL BE ELECTRONICALLY
 SIGNED AND SEALED BY THE ENGINEER- FL. STATUTE 471.025
 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 4) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE THE
 SUPPLY AIR SYSTEMS OF AHU'S 1, 2, 3, 4, 5, 6, & 7-
 SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION
 FOR THE DETECTORS IN THE SUPPLY CAN BE APPLIED IF THE
 MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR
 HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
 (THE EOR RESPONSE NARRATIVE INDICATES AREA SMOKE
 DETECTORS PROVIDED IN LIEU OF REQUIRED DS DETECTORS IN
 THE SUPPLY SYSTEMS. PLEASE REVIEW THE SUBMITTED FA
 PLANS SHOWING 9 DS DETECTORS IN THE RETURNS, AND ONLY 3
 AREA SMOKE DETECTORS FOR THE ENTIRE OCCUPANCY. PLEASE
 SEE DS DETECTOR NOTE ON SHEET M2).
  
 5) M1 & M2: IT APPEARS THAT VEHICLES WILL EITHER DRIVE
 INTO OR BE STORED IN THE "PROPOSED LOADING" AREA WHERE
 THE LARGE BAY DOORS ARE. PROVIDE AN EXHAUST VENTILATION
 SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1 AND SECTION
 404.1 FBC M.
 (SHEET M1 & M2: INDICATE SEQUENCE OF OPERATION FOR THE
 EXHAUST VENTILATION SYSTEM- REFER TO SECTION 404.1 FBC
 M).
  
 6) M1: PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT
 THE EMERGENCY GENERATOR WILL BE INSTALLED UNDER A
 SEPARATE PERMIT- SECTION 107.2.1 FBC M.
  
 NEW COMMENT:
  
 1) THE HVAC CALCULATIONS INDICATE 48 KW OF HEAT
 REQUIRED IN THE MAIN WAREHOUSE AND 5KW IN THE SECURE
 STORAGE AREA. ACCORDING TO THE AC EQUIPMENT SCHEDULE
 THERE WILL BE A SHORTAGE OF 8KW IN THE WAREHOUSE AND
 5KW IN THE STORAGE AREA- SECTION C403.2.1 FBC EC.
  
 2) ADVISORY: THE REQUIRED SENSORS FOR THE LOADING DOCK
 EXHAUST SYSTEM, AND THE SHOP DRAWINGS FOR THE CONDENSER
 SERVICE PLATFORMS AND GUARDRAILS MAY BE DEFERRED
 SUBMITTALS. PLEASE NOTE THAT EACH SUBMITTAL SHALL BEAR
 THE APPROVAL STAMP OF THE EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By ccole Date 2020-01-13 Time 12:35 Rev Time 0.00
Received By ccole Date 2020-01-13 Time 07:44 Sent To  
Notes
2020-01-13 13:19:452ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19110910
 1/13/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD RESPONSIBLE FOR THE DESIGN
 SHALL PROVIDE AN APPROVAL STAMP ON THE SUBMITTED
 ENERGYGAUGE COMPLIANCE REPORT- SEE SECTION C103.1.1.2
 FBC EC.
  
 2) THE WIND FORCE CALCULATIONS SHALL BE ELECTRONICALLY
 SIGNED AND SEALED BY THE ENGINEER- FL. STATUTE 471.025
 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 3) SHEETS M1 & M2: THE O/A CALCULATIONS ARE INDICATING
 MECHANICAL VENTILATION WILL BE PROVIDED FOR THE THE NEW
 WORK SHOP HOWEVER NO MECHANICAL VENTILATION IS SHOWN ON
 THE PLAN. PLEASE NOTE THAT THE MECHANICAL CALCULATION
 DOES NOT SHOW THE REQUIRED ,18 CFMS PER SF. HAS BEEN
 ADDED IN. AS PREVIOUSLY REQUESTED, INDICATE ON THE PLAN
 WHAT TYPE OF WORK WILL BE PERFOMED IN THE SHOP AND ALSO
 WHAT TYPE OF EQUIPMENT WILL BE USED. PROVIDE A LAYOUT
 PLAN AND A EQUIPMENT SCHEDULE
  
 4) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE THE
 SUPPLY AIR SYSTEMS OF AHU'S 1, 2, 3, 4, 5, 6, & 7-
 SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION
 FOR THE DETECTORS IN THE SUPPLY CAN BE APPLIED IF THE
 MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR
 HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 5) M1 & M2: IT APPEARS THAT VEHICLES WILL EITHER DRIVE
 INTO OR BE STORED IN THE "PROPOSED LOADING" AREA WHERE
 THE LARGE BAY DOORS ARE. PROVIDE AN EXHAUST VENTILATION
 SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1 AND SECTION
 404.1 FBC M.
  
 6) M1: PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT
 THE EMERGENCY GENERATOR WILL BE INSTALLED UNDER A
 SEPARATE PERMIT- SECTION 107.2.1 FBC M.
  
 7) M2: PLEASE PROVIDE DIMENSIONED DETAILS OF THE CU
 ACCESS PLATFORMS AND REQUIRED GUARDRAILS AROUND THEM-
 SECTIONS 304.11 SND 306.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By ccole Date 2019-12-18 Time 11:34 Rev Time 0.00
Received By ccole Date 2019-12-18 Time 10:50 Sent To  
Notes
2019-12-18 12:02:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110910
 12/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REQUIRED CALCULATIONS FOR THE PROJECT
  
 A) AC COOLING AND HEATING CALCULATIONS IN ACCORDANCE
 WITH SECTION C403.2.1 FBC EC.
  
 B) ENERGY CALCULATIONS- THE PROPOSED PROJECT IS
 CLASSIFED AS A CHANGE OF OCCUPANCY, AND IS ALSO A
 PREVIOUSLY UNCONDITONED SPACE NOW BEING CONDITIONED.
 REFER TO SECTIONS C101.4.5, C503.2 , & C505.1 AND
 SUBMIT AN ENERGY COMPLIANCE REPORT.
  
 2) SHEET M1: PLEASE PROVIDE NEW ROOM AND AREA
 IDENTIFICATIONS FOR THE "EXISTING WAREHOUSE AND
 EXISTING LOADING" SPACES. IN ORDER TO PROVIDE PROPER
 VENTILATION, ITS IS IMPORTANT TO INDICATE WHAT
 ACTIVITIES WILL OCCUR IN THESE AREAS- SECTION 107.2.1
 WPB.
  
 3) M1, NEW WORK SHOP: PROVIDE O/A AND EXHAUST
 VENTILATION CALCULATIONS FOR THE SHOP PER TABLE
 403.3.1.1 FBC M. CLARIFY WHAT FUNCTIONS OR PROCESSES
 OCCUR IN THE SHOP- SECTION 107.2.1 WPB.
  
 4) M1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ERV SYSTEM
 ON THE PLAN.- SEE SECTION C403.2.7 FBC EC.
  
 5) MISSING PLANS AND DETAILS- SECTION 107.2.1 WPB
  
 A) RCP
  
 B) AIR DISTRIBUTION AND AIR DEVICE SCHEDULE.
  
 C) ENLARGED GENERATOR ROOM PLAN. THERE ARE NO
 SPECIFICATIONS SUBMITTED FOR THE GENERATOR. CLARIFY IF
 THE SYSTEM IS TO BE UNDER THIS PERMIT OR SEPARATE
 PERMIT. PLEASE NOTE THAT A COMPLETE SUBMITTAL PACKAGE
 AND COMPLETE ELECTRICAL AND MECHANICAL DRAWINGS ARE
 REQUIRED- SECTION 107.2.1 WPB.
  
 D) AIR HANDLER SUPPORT DETAILS.
  
 E) PRIMARY AND SECONDARY CONDENSATE DISPOSAL
  
 6) M1 & S5: THE CONDENSERS ON THE NEW SHOP ROOF APPEAR
 TO BE LESS THAN 10' FROM THE ROOF EDGE WHICH WOULD
 REQUIRE GUARDS TO BE INSTALLED- SEE SECTION 304.11 FBC
 M.
  
 7) M1 & S5: AN ACCESS PLATFORM IS REQUIRED FOR THE
 CONDENSERS MOUNTED ON THE EXTERIOR WALLS PER SECTION
 306.1 FBC M. PLEASE NOTE THAT A PERMANENT LADDER IS
 REQUIRED IF THE CONDENSERS ARE MOUNTED HIGHER THAN 16'
 FROM GRADE- SECTION 306.5 FBC M.
  
 8) PROVIDE COMPLETE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE ROOF AND WALL MOUNTED CONDENSERS-
 SECTION 301.15 FBC M. SUBMIT MIAMI-DADE NOA'S AND/OR
 FL. PRODUCT APPROVALS FOR THE CONDENSER STANDS AND WALL
 BRACKET- RULE 9N-3 FAC.
  
 9) THE $616,520.00 PROJECT VALUE APPEARS LOW FOR A
 20515 SF. RENOVATION. PLEASE PROVIDE SA COPY OF THE
 CONTRACT AND AN ITEMIZED COST BREAKDOWN FOR THE ENTIRE
 PROJECT. THE TOTAL VALUE IS BASED ON LABOR, MATERIALS,
 EUIPMENT AND FIXTURES FOR ALL TRADES AND PHASES OF THE
 PROJECT, AND SHALL ALSO INCLUDE SITE WORK AND DESIGN
 FEES- SECTION 109.3 WPB.THAT INCLUDES ALL OF THE TRADE
 COSTS,
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 15:13 Rev Time 0.00
Received By gjohnson Date 2020-02-07 Time 15:13 Sent To  
Notes
2020-02-07 15:13:20 
 PLUMBING PROVISO
  
 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR
 THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE
 SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN
 WILL SUFFICE. PER FBC PL 416.5
  
 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE
 ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS
 REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE
 NOTE ON THE PLAN
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-01-28 Cont ID  
Sent By gjohnson Date 2020-01-28 Time 12:23 Rev Time 0.00
Received By gjohnson Date 2020-01-27 Time 17:43 Sent To  
Notes
2020-01-28 12:23:523RD REVIEW:19120803
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: NO RESPONSE LETTER WAS PROVIDED FOR
 PREVIOUS COMMENTS IT WAS UNCLEAR HOW ALL THE COMMENTS
 WERE ANSWERED.
  
 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR
 THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE
 SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN
 WILL SUFFICE. PER FBC PL 416.5
  
 3. PLEASE IDENTIFY THE THERMAL EXPANSION DEVICE IT CAN
 NOT BE APPROVED UNTIL IT IS IDENTIFIED PROVIDE
 MANUFACTURE SPECIFICATIONS FOR A VALVE OR MODEL NUMBER
 OF A TANK. PER FBC PL 607.3
  
 4. THE EYE WASH IS NOT VENTED PLEASE PROVIDE A VENT PER
 FBC PL 901.2.1
  
 5. SHT. P1 NOTE ON H.C. RESTROOM PLAN LAYOUT STATES
 GRAB BARS TO BE MEASURED TO THE CENTERLINE THEY SHALL
 BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC
 ACC 609.4
  
 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE
 ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS
 REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE
 NOTE ON THE PLAN
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By shill Date 2020-01-13 Time 09:16 Rev Time 0.00
Received By shill Date 2020-01-10 Time 18:00 Sent To  
Notes
2020-01-13 09:16:30PLUMBING 2ND REVIEW**DENIED**19110910
 1) SHT. S6 PLEASE SHOW THE MIRROR 40?MAX AS TO THE
 REFLECTIVE SURFACE NOT THE BOTTOM EDGE OF MIRROR.
 FBC-ACC 603.3.
 2) SHOW TOILET PAPER HOLD AS BEING 7?-9? FROM THE FRONT
 EDGE OF THE TOILET. FBC-ACC 604.7
 3) PLEASE PROVIDE THE GRAB BAR DETAIL MEASUREMENTS AS
 CALLED OUT IN FBC-ACC 604.5.1, 604.5.2
 4) (A) SHOW THE ADA SHOW AS A TRANSFER SHOWER NOT AS
 ADA. THE 36? IS NOT THE MIN THIS IS AN ABSOLUTE
 MEASUREMENT. FBC-ACC 608.2
 (B) THE GRAB BAR SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE NOT TO THE CENTER. FBC-ACC 609.4
 (C) SHOW SHOWER PAN MATERIAL BEING USED. FBC-PLB
 417.5.2
 (D) THE CONTROL WALL SHALL BE ACROSS FROM THE TRANSFER
 SHOWER SEAT NOT ADJACENT TO THE SEAT AS SHOWN. FBC-ACC
 608.2.1
 (E) HEIGHT FOR THE SHOWER VALVE AND SHOWER HEAD/ HAND
 HELD SHALL BE MAX 48?. FBC-ACC 608.6
 (F) SHOW THE PRE-PITCH OF THE SHOWER AS 2% / ?? PER
 FOOT MIN. FBC-PLB 417.5.2
 5) THE WATER HEATER RELIEF LINE SHALL DISCHARGE INTO
 THE DRAIN PAN WITH IN THE ROOM. FBC-PLB 504.6
 6) PAN DRAIN MATERIAL SHALL BE OF MATERIALS CALLED OUT
 IN THE WATER DISTRIBUTION TABLE FBC-PLB 605.4. PVC
 PIPING IS NOT PERMITTED.
 7) SHOW ALL HOT WATER PIPING AS BEING INSULATED AS
 CALLED OUT IN FBC-ENERGY C404.4.
 8) PROVIDE MEANS OF THERMO EXPANSION. FBC-PLB 607.3
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-19 Cont ID  
Sent By shill Date 2019-12-19 Time 20:50 Rev Time 0.00
Received By shill Date 2019-12-16 Time 17:27 Sent To  
Notes
2019-12-19 20:51:01PLUMBING 1ST REVIEW**DENIED**19110910
  
 1) NO GAS REVIEW PERFORMED AS GENERATOR IS REQUIRED TO
 HAVE A SEPARATE PERMIT PACKET TO INCLUDE THE GEN, SLAB,
 ELEC, AND GAS SUBMITTED TOGETHER. WPB AMEND 105.1
 2) SHT MP-1 NOTE #1.3 CALLS OUT CONDENSATE LINE AS PVC
 BUT NOTE 2.3 CALLS OUT COPPER. PLEASE CLARIFY 107.2.1
 3) PLUMBING FLAT AND ISOMETRIC SHOWS OTHER THEN
 BATHROOM FIXTURES DISCHARGING INTO THE BATHROOM GROUP
 WET VENT. PLEASE SHOW THESE FIXTURES CONNECTING DOWN
 STREAM OF THE BATHROOM GROUP WET VENT. FBC-912.1,
 912.1.1, 912.2.1
 4) SHOW BREAK ROOM SINK DETAIL SHOWING MAX CABINET
 HEIGHT AS 34? TO COMPLY WITH FLORIDA ACCESSIBILITY.
 5) PROVIDE DIMENSIONS OF ALL NEW ROOMS. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2020-01-14 Cont ID  
Sent By dbattles Date 2020-01-14 Time 08:05 Rev Time 0.00
Received By dbattles Date 2020-01-14 Time 08:05 Sent To  
Notes
2020-01-14 08:06:10PRODUCT APPROVALS DUE WITH SUB PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-12-18 Cont ID  
Sent By dbattles Date 2019-12-18 Time 15:36 Rev Time 0.00
Received By dbattles Date 2019-12-18 Time 15:36 Sent To  
Notes
2019-12-18 15:37:10SEE BUILDING COMMENT #4

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By dbattles Date 2020-02-07 Time 13:41 Rev Time 0.00
Received By dbattles Date 2020-02-07 Time 13:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By dbattles Date 2020-01-28 Time 08:46 Rev Time 0.00
Received By dbattles Date 2020-01-28 Time 08:46 Sent To  
Notes
2020-01-28 08:47:38ALL SHEETS - OK
2020-01-28 07:17:45ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-01-13 Cont ID  
Sent By dbattles Date 2020-01-13 Time 12:49 Rev Time 0.00
Received By dbattles Date 2020-01-13 Time 12:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By shill Date 2019-12-17 Time 14:19 Rev Time 0.00
Received By shill Date 2019-12-17 Time 14:15 Sent To  
Notes
2019-12-19 08:02:32THE EOR SINCLAIR CANNOT SELF-CERTIFY HIS ELECTRONIC
 SIGNATURE AND SEAL. THIRD PARTY CETIFICATION IS
 REQUIRED.
2019-12-17 14:20:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, FIRE ALARM PAGES ARE NOT DIGITALLY SIGNED.
 EITHER PROVIDE DIGITALLY SIGNED DOCUMENTS, OR SUBMIT A
 PAPER SIGNED, SEALED DATED ORGINAL TO THE BUILDING
 DIVISION. A SUBMITTAL FORM WILL BE REQUIRED TO BE
 SUBMITTED WITH THE PLANS.
  
 IN THE FUTURE DO NOT UPLOAD SCANNED PLANS, PLEASE
 UPLOAD THE ORIGINAL PDF. A SCAN OF A SEAL AND SIGNATURE
 IS NOT IN COMPLIANCE WITH FS471.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By rfalcone Date 2020-01-28 Time 08:08 Rev Time 0.00
Received By rfalcone Date 2020-01-28 Time 08:08 Sent To I
Notes
2020-01-28 14:29:371/28/20 PASSED.
  
 I SPOKE WITH THE APPLICANT AND HE CLARIFIED THAT THE
 WORK IS INTERNAL AND NO ADDITIONS WILL BE ADDING ONTO
 THE STRUCTURE. PARKING WILL BE A SEPERATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
2020-01-28 08:08:591/28/20 FAILED.
  
 PLEASE ADDRESS PREVIOUS COMMENTS.
  
 ******
  
 1/10/20 FAILED.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
 1. THE PROPOSED ADDITION IS ENROACHING OUTSIDE OF THE
 PROPERTY LINES, PLEASE PROVIDE A COPY OF DEED BOOK
 (D.B) 1052, PG. 264 SHOWN ON THE SURVEY TO PROVE THE
 "R/W & EASMENT FOR RAILROAD SIDING" HAS BEEN REVERTED
 BACK TO THE SUBJECT PROPERTY.
 2. PROVIDE THE SQUARE FOOTAGE OF THE PROPOSED ADDITION.
 3. BASED ON THE PROPOSED SQUARE FOOTAGE, ADDITIONAL
 PARKING WILL BE REQUIRED FOR THE SUBJECT SITE. SHOW THE
 AMOUNT OF REQUIRED PARKING SPACES THAT WILL NEED TO BE
 PROVIDED BASED ON THE ADDITION.
  
 **THE PROPOSED PARKING LOT IMPROVEMENTS MUST BE
 SUBMITTED AS A SEPERATE PERMIT **
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME
 NTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-01-10 Cont ID  
Sent By rfalcone Date 2020-01-10 Time 15:13 Rev Time 0.00
Received By rfalcone Date 2020-01-10 Time 15:13 Sent To I
Notes
2020-01-10 15:46:371/10/20 FAILED.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
 1. THE PROPOSED ADDITION IS ENROACHING OUTSIDE OF THE
 PROPERTY LINES, PLEASE PROVIDE A COPY OF DEED BOOK
 (D.B) 1052, PG. 264 SHOWN ON THE SURVEY TO PROVE THE
 "R/W & EASMENT FOR RAILROAD SIDING" HAS BEEN REVERTED
 BACK TO THE SUBJECT PROPERTY.
 2. PROVIDE THE SQUARE FOOTAGE OF THE PROPOSED ADDITION.
 3. BASED ON THE PROPOSED SQUARE FOOTAGE, ADDITIONAL
 PARKING WILL BE REQUIRED FOR THE SUBJECT SITE. SHOW THE
 AMOUNT OF REQUIRED PARKING SPACES THAT WILL NEED TO BE
 PROVIDED BASED ON THE ADDITION.
  
 **THE PROPOSED PARKING LOT IMPROVEMENTS MUST BE
 SUBMITTED AS A SEPERATE PERMIT **
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME
 NTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By rfalcone Date 2020-01-06 Time 08:36 Rev Time 0.00
Received By rfalcone Date 2019-12-20 Time 15:37 Sent To I
Notes
2020-01-06 08:39:3801/06/2020 FAILED.
  
 PLEASE PROVIDE A PARKING DETAIL FOR THE PROPOSED
 PARKING SPACES (I.E. COLOR OF STRIPES,WIDTH OF HANDICAP
 AISLE, ETC.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  
2019-12-20 15:37:4012/20/19
  
 WAITING FOR THE APPLICANT TO CALL BACK - NEED
 CLARIFICATION ON THE PERMIT.
  
 RACHEL FALCONE