| Plan Review Stops For Permit 19110910 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
4 |
Status |
P |
Date |
2020-02-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-02-07 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-02-07 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2020-02-07 13:35:23 | OK-LETTER ADDED TO SUPPORTING DOCUMENTS |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-28 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-28 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2020-01-28 08:56:50 | COMMENT NOT ADDRESSED. | | | PLEASE SEND VIA E-MAIL THE LETTER OF ACKNOWLEDGEMENT AS | | | REQUESTED FROM 2ND REVIEW (SEE BELOW) | | | [email protected] | | | | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM | | | BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME | | | NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION. | | | HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA | | | EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT | | | LINE. | | | | | | W.P.B. PERMIT: 19110910 | | | REVIEWED: DECEMBER 18, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-14 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-14 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2020-01-14 08:26:26 | COMMENT NOT ADDRESSED. | | | PLEASE SEND VIA E-MAIL THE LETTER OF ACKNOWLEDGEMENT AS | | | REQUESTED FROM FIRST REVIEW (SEE BELOW) | | | [email protected] | | | | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM | | | BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME | | | NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION. | | | HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA | | | EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT | | | LINE. | | | | | | W.P.B. PERMIT: 19110910 | | | REVIEWED: DECEMBER 18, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-18 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-18 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2019-12-18 15:51:28 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM | | | BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME | | | NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION. | | | HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA | | | EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT | | | LINE. | | | | | | W.P.B. PERMIT: 19110910 | | | REVIEWED: DECEMBER 18, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-02-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-02-07 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-02-07 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2020-02-07 13:37:52 | PROVISOS: | | | A) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | | REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | B) DEFERRED SUBMITTALS | | | PROVIDE STAIRCASE AND GUARD RAIL ENGINEERING | | | C) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM | | | SAT-SUN |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-28 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-28 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-14 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-13 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-18 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-18 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2019-12-18 15:48:40 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19110910 | | | REVIEWED: DECEMBER 18, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | 1) 301.1 FBC[B]WHAT IS THE OCCUPANCY USE OF GENERATOR, | | | TYPE OF FUEL, AMOUNT OF FUEL AND LOCATION OF FUEL | | | STORAGE. | | | THE GENERATOR WILL BE SEPARATE PERMIT, BUT GENERAL INFO | | | IS NEEDED TO SEE WHAT SEPARATION THE WALLS NEED TO BE. | | | | | | 2) 804.3.2 FBC[A]PLEASE PROVIDE DETAIL OF BREAKROOM TO | | | SHOW COUNTER HEIGHT AND ANY ADDITIONAL DETAILS TO SHOW | | | COMPLIANCE WITH FBC ACCESSIBILITY. | | | | | | 3) 107.3.4.1 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, ROLL-UP DOOR AND ENTRY DOORS, LOUVERS AND A/C | | | STANDS, OR INDICATE THAT THEY WILL BE DEFERRED. | | | 4) 107.3.4.1 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR | | | LOW SLOPE ROOFING, OR INDICATE THAT THEY WILL BE | | | DEFERRED. | | | PROVISOS: NO COMMENT RESPONSE NEEDED, THESE WILL BE | | | ADDED TO APPROVED PLANS. | | | A) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | | REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | B) DEFERRED SUBMITTALS | | | PROVIDE STAIRCASE AND GUARD RAIL ENGINEERING | | | C) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM | | | SAT-SUN | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2020-02-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-02-12 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-02-12 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-01-28 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-01-28 |
Time |
07:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-10 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-10 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-12-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-20 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-17 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2019-12-20 09:05:00 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-9 | | | | | | ALL PANELS SHOWN AS 600 AMPERES |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-01-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2020-01-28 |
Time |
|
Sent To |
I |
|
| Notes |
| 2020-01-28 07:40:33 | CURRENTLY UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL | | | E20010005. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-01-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2020-01-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-01-10 14:40:41 | PLEASE SUBMIT FOR A FORMAL ENGINEERING SUBMITTAL | | | REVIEW. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING | | | ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2019-12-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2019-12-18 |
Time |
|
Sent To |
I |
|
| Notes |
| 2019-12-18 15:17:56 | PLEASE SUBMIT FOR A FORMAL ENGINEERING SUBMITTAL | | | REVIEW. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING | | | ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2020-02-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-02-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-02-10 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2020-02-10 10:08:17 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND. | | | | | | ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM. | | | | | | ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | | | | 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM. | | | | | | ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND | | | SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-01-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-01-27 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2020-01-27 13:43:26 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND. | | | | | | ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM. | | | | | | ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | | | | 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM. | | | | | | ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND | | | SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-01-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-01-13 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2020-01-13 14:55:28 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND. | | | | | | ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM. | | | | | | ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | | | | 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM. | | | | | | ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND | | | SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-12-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-16 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2019-12-16 13:54:46 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS INDICATION OF A FIRE LINE UNDERGROUND. | | | | | | ANY FIRE LINE UNDERGROUND SHALL BE UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 24. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | 2) THERE IS INDICATION OF A FIRE SPRINKLER SYSTEM. | | | | | | ANY FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | | | | 2) THERE IS INDICATION OF A FIRE ALARM SYSTEM. | | | | | | ANY FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT AND | | | SHOP DRAWINGS. | | | | | | PLEASE ENSURE COOMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
N |
Date |
2020-02-13 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-02-13 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-02-13 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2020-02-13 06:55:58 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A | | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS | | | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | | | T.LARGE | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2020-02-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2020-02-07 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2020-02-07 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2020-02-07 15:10:52 | 4THREVIEW: 19110910 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | | | 1. THE CIVIL SITE PLAN SHOWS A 1000GAL PROPANE | | | UNDERGROUND GAS TANK THE GAS PLAN SHOWS NATURAL GAS | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. THE GAS ISOMETRIC ON SHEET P1 IS UNCLEAR SHT. L01 | | | SHOWS THE METER RIGHT OUTSIDE GENERATOR ROOM DOES THE | | | GALVANIZED SCH 40 PIPING RUN UNDER THE SLAB IF SO IT | | | SHALL BE SLEEVED THE ENTIRE LENGTH UNDER THE SLAB | | | PROVIDE DETAIL FOR SLEEVING. PER FBC FG 404.14 | | | | | | 3. THE SIZING TABLE FOR CSST IS FOR 2PSI SYSTEM THE | | | ISOMETRIC DRAWING IS SHOWING THE CSST UPSTREAM OF THE | | | REGULATOR SO IT SHOULD BE UNDER 2PSI SYSTEM PLEASE | | | CLARIFY WHICH SIZING TABLE YOU USING TO SIZE THE PIPING | | | ON THE UNDER 2PSI SYSTEM. PER FBC FG 402.4 | | | | | | 4. USING TABLE 402.4(16) FOR 8" WC AS INDICATED ON THE | | | GENERATOR WITH BTU LOAD OF 1,389,000 3EHD IS | | | UNDERSIZED. PER FBC FG TABLE 402.4(16) | | | | | | 5. PREVIOUS COMMENT PROVIDE MANUFACTURE SPECIFICATION | | | FOR THE REGULATOR AND ISOLATION CONNECTOR FOR THE | | | GENERATOR.. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2020-01-28 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2020-01-27 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2020-01-28 14:05:28 | 3RD REVIEW: 19110910 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | 1. THE CIVIL SITE PLAN SHOWS A 1000GAL PROPANE | | | UNDERGROUND GAS TANK THE GAS PLAN SHOWS NATURAL GAS | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. THE GAS ISOMETRIC ON SHEET P1 IS UNCLEAR SHT. L01 | | | SHOWS THE METER RIGHT OUTSIDE GENERATOR ROOM DOES THE | | | GALVANIZED SCH 40 PIPING RUN UNDER THE SLAB IF SO IT | | | SHALL BE SLEEVED THE ENTIRE LENGTH UNDER THE SLAB | | | PROVIDE DETAIL FOR SLEEVING. PER FBC FG 404.14 | | | | | | 3. THE SIZING TABLE FOR CSST IS FOR 2PSI SYSTEM THE | | | ISOMETRIC DRAWING IS SHOWING THE CSST UPSTREAM OF THE | | | REGULATOR SO IT SHOULD BE UNDER 2PSI SYSTEM PLEASE | | | CLARIFY WHICH SIZING TABLE YOU USING TO SIZE THE PIPING | | | ON THE UNDER 2PSI SYSTEM. PER FBC FG 402.4 | | | | | | 4. USING TABLE 402.4(16) FOR 8" WC AS INDICATED ON THE | | | GENERATOR WITH BTU LOAD OF 1,389,000 3EHD IS | | | UNDERSIZED. PER FBC FG TABLE 402.4(16) | | | | | | 5. PREVIOUS COMMENT PROVIDE MANUFACTURE SPECIFICATION | | | FOR THE REGULATOR AND ISOLATION CONNECTOR FOR THE | | | GENERATOR.. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-01-13 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-01-13 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2020-01-13 09:17:22 | GAS 2ND REVIEW**DENIED**19110910** | | | | | | 1) PLEASE CLARIFY WHICH KW GENERATOR YOU ARE USE AS | | | SHT. S-1 AND P-1 CALL OUT 100KW BUT SHT. SC CALLS OUT | | | 150KW. PLEASE CLARIFY FBC 107.2.1 | | | 2) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLAN REVIEW | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | 561-248-2703 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2020-02-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-02-13 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-02-12 |
Time |
17:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-02-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-02-12 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-02-07 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-01-28 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-01-26 |
Time |
07:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-14 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-09 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-01-06 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-13 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-18 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-18 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2019-12-18 15:52:41 | NO CHANGE IN OCCUPANCY |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2020-02-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-02-07 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-02-07 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-28 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-28 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2020-01-28 11:36:45 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #19110910 | | | 1/28/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | (COMMENTS #1, 2, 4, 5 & 6 LISTED BELOW ARE REMAINING | | | FROM THE 1ST AND 2ND REVIEW.) | | | | | | 1) THE ENGINEER OF RECORD RESPONSIBLE FOR THE DESIGN | | | SHALL PROVIDE AN APPROVAL STAMP ON THE SUBMITTED | | | ENERGYGAUGE COMPLIANCE REPORT- SEE SECTION C103.1.1.2 | | | FBC EC. (THE EOR SHALL ALSO PROVIDE AN APPROVAL STAMP | | | ON THE HVAC CALCULATIONS). | | | | | | 2) THE WIND FORCE CALCULATIONS SHALL BE ELECTRONICALLY | | | SIGNED AND SEALED BY THE ENGINEER- FL. STATUTE 471.025 | | | AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. | | | | | | 4) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE THE | | | SUPPLY AIR SYSTEMS OF AHU'S 1, 2, 3, 4, 5, 6, & 7- | | | SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION | | | FOR THE DETECTORS IN THE SUPPLY CAN BE APPLIED IF THE | | | MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR | | | HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF | | | SUPPLY AIR. | | | (THE EOR RESPONSE NARRATIVE INDICATES AREA SMOKE | | | DETECTORS PROVIDED IN LIEU OF REQUIRED DS DETECTORS IN | | | THE SUPPLY SYSTEMS. PLEASE REVIEW THE SUBMITTED FA | | | PLANS SHOWING 9 DS DETECTORS IN THE RETURNS, AND ONLY 3 | | | AREA SMOKE DETECTORS FOR THE ENTIRE OCCUPANCY. PLEASE | | | SEE DS DETECTOR NOTE ON SHEET M2). | | | | | | 5) M1 & M2: IT APPEARS THAT VEHICLES WILL EITHER DRIVE | | | INTO OR BE STORED IN THE "PROPOSED LOADING" AREA WHERE | | | THE LARGE BAY DOORS ARE. PROVIDE AN EXHAUST VENTILATION | | | SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1 AND SECTION | | | 404.1 FBC M. | | | (SHEET M1 & M2: INDICATE SEQUENCE OF OPERATION FOR THE | | | EXHAUST VENTILATION SYSTEM- REFER TO SECTION 404.1 FBC | | | M). | | | | | | 6) M1: PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT | | | THE EMERGENCY GENERATOR WILL BE INSTALLED UNDER A | | | SEPARATE PERMIT- SECTION 107.2.1 FBC M. | | | | | | NEW COMMENT: | | | | | | 1) THE HVAC CALCULATIONS INDICATE 48 KW OF HEAT | | | REQUIRED IN THE MAIN WAREHOUSE AND 5KW IN THE SECURE | | | STORAGE AREA. ACCORDING TO THE AC EQUIPMENT SCHEDULE | | | THERE WILL BE A SHORTAGE OF 8KW IN THE WAREHOUSE AND | | | 5KW IN THE STORAGE AREA- SECTION C403.2.1 FBC EC. | | | | | | 2) ADVISORY: THE REQUIRED SENSORS FOR THE LOADING DOCK | | | EXHAUST SYSTEM, AND THE SHOP DRAWINGS FOR THE CONDENSER | | | SERVICE PLATFORMS AND GUARDRAILS MAY BE DEFERRED | | | SUBMITTALS. PLEASE NOTE THAT EACH SUBMITTAL SHALL BEAR | | | THE APPROVAL STAMP OF THE EOR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-13 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-13 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2020-01-13 13:19:45 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19110910 | | | 1/13/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER OF RECORD RESPONSIBLE FOR THE DESIGN | | | SHALL PROVIDE AN APPROVAL STAMP ON THE SUBMITTED | | | ENERGYGAUGE COMPLIANCE REPORT- SEE SECTION C103.1.1.2 | | | FBC EC. | | | | | | 2) THE WIND FORCE CALCULATIONS SHALL BE ELECTRONICALLY | | | SIGNED AND SEALED BY THE ENGINEER- FL. STATUTE 471.025 | | | AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. | | | | | | 3) SHEETS M1 & M2: THE O/A CALCULATIONS ARE INDICATING | | | MECHANICAL VENTILATION WILL BE PROVIDED FOR THE THE NEW | | | WORK SHOP HOWEVER NO MECHANICAL VENTILATION IS SHOWN ON | | | THE PLAN. PLEASE NOTE THAT THE MECHANICAL CALCULATION | | | DOES NOT SHOW THE REQUIRED ,18 CFMS PER SF. HAS BEEN | | | ADDED IN. AS PREVIOUSLY REQUESTED, INDICATE ON THE PLAN | | | WHAT TYPE OF WORK WILL BE PERFOMED IN THE SHOP AND ALSO | | | WHAT TYPE OF EQUIPMENT WILL BE USED. PROVIDE A LAYOUT | | | PLAN AND A EQUIPMENT SCHEDULE | | | | | | 4) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE THE | | | SUPPLY AIR SYSTEMS OF AHU'S 1, 2, 3, 4, 5, 6, & 7- | | | SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION | | | FOR THE DETECTORS IN THE SUPPLY CAN BE APPLIED IF THE | | | MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR | | | HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF | | | SUPPLY AIR. | | | | | | 5) M1 & M2: IT APPEARS THAT VEHICLES WILL EITHER DRIVE | | | INTO OR BE STORED IN THE "PROPOSED LOADING" AREA WHERE | | | THE LARGE BAY DOORS ARE. PROVIDE AN EXHAUST VENTILATION | | | SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1 AND SECTION | | | 404.1 FBC M. | | | | | | 6) M1: PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT | | | THE EMERGENCY GENERATOR WILL BE INSTALLED UNDER A | | | SEPARATE PERMIT- SECTION 107.2.1 FBC M. | | | | | | 7) M2: PLEASE PROVIDE DIMENSIONED DETAILS OF THE CU | | | ACCESS PLATFORMS AND REQUIRED GUARDRAILS AROUND THEM- | | | SECTIONS 304.11 SND 306.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-18 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-18 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2019-12-18 12:02:28 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19110910 | | | 12/18/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REQUIRED CALCULATIONS FOR THE PROJECT | | | | | | A) AC COOLING AND HEATING CALCULATIONS IN ACCORDANCE | | | WITH SECTION C403.2.1 FBC EC. | | | | | | B) ENERGY CALCULATIONS- THE PROPOSED PROJECT IS | | | CLASSIFED AS A CHANGE OF OCCUPANCY, AND IS ALSO A | | | PREVIOUSLY UNCONDITONED SPACE NOW BEING CONDITIONED. | | | REFER TO SECTIONS C101.4.5, C503.2 , & C505.1 AND | | | SUBMIT AN ENERGY COMPLIANCE REPORT. | | | | | | 2) SHEET M1: PLEASE PROVIDE NEW ROOM AND AREA | | | IDENTIFICATIONS FOR THE "EXISTING WAREHOUSE AND | | | EXISTING LOADING" SPACES. IN ORDER TO PROVIDE PROPER | | | VENTILATION, ITS IS IMPORTANT TO INDICATE WHAT | | | ACTIVITIES WILL OCCUR IN THESE AREAS- SECTION 107.2.1 | | | WPB. | | | | | | 3) M1, NEW WORK SHOP: PROVIDE O/A AND EXHAUST | | | VENTILATION CALCULATIONS FOR THE SHOP PER TABLE | | | 403.3.1.1 FBC M. CLARIFY WHAT FUNCTIONS OR PROCESSES | | | OCCUR IN THE SHOP- SECTION 107.2.1 WPB. | | | | | | 4) M1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ERV SYSTEM | | | ON THE PLAN.- SEE SECTION C403.2.7 FBC EC. | | | | | | 5) MISSING PLANS AND DETAILS- SECTION 107.2.1 WPB | | | | | | A) RCP | | | | | | B) AIR DISTRIBUTION AND AIR DEVICE SCHEDULE. | | | | | | C) ENLARGED GENERATOR ROOM PLAN. THERE ARE NO | | | SPECIFICATIONS SUBMITTED FOR THE GENERATOR. CLARIFY IF | | | THE SYSTEM IS TO BE UNDER THIS PERMIT OR SEPARATE | | | PERMIT. PLEASE NOTE THAT A COMPLETE SUBMITTAL PACKAGE | | | AND COMPLETE ELECTRICAL AND MECHANICAL DRAWINGS ARE | | | REQUIRED- SECTION 107.2.1 WPB. | | | | | | D) AIR HANDLER SUPPORT DETAILS. | | | | | | E) PRIMARY AND SECONDARY CONDENSATE DISPOSAL | | | | | | 6) M1 & S5: THE CONDENSERS ON THE NEW SHOP ROOF APPEAR | | | TO BE LESS THAN 10' FROM THE ROOF EDGE WHICH WOULD | | | REQUIRE GUARDS TO BE INSTALLED- SEE SECTION 304.11 FBC | | | M. | | | | | | 7) M1 & S5: AN ACCESS PLATFORM IS REQUIRED FOR THE | | | CONDENSERS MOUNTED ON THE EXTERIOR WALLS PER SECTION | | | 306.1 FBC M. PLEASE NOTE THAT A PERMANENT LADDER IS | | | REQUIRED IF THE CONDENSERS ARE MOUNTED HIGHER THAN 16' | | | FROM GRADE- SECTION 306.5 FBC M. | | | | | | 8) PROVIDE COMPLETE WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE ROOF AND WALL MOUNTED CONDENSERS- | | | SECTION 301.15 FBC M. SUBMIT MIAMI-DADE NOA'S AND/OR | | | FL. PRODUCT APPROVALS FOR THE CONDENSER STANDS AND WALL | | | BRACKET- RULE 9N-3 FAC. | | | | | | 9) THE $616,520.00 PROJECT VALUE APPEARS LOW FOR A | | | 20515 SF. RENOVATION. PLEASE PROVIDE SA COPY OF THE | | | CONTRACT AND AN ITEMIZED COST BREAKDOWN FOR THE ENTIRE | | | PROJECT. THE TOTAL VALUE IS BASED ON LABOR, MATERIALS, | | | EUIPMENT AND FIXTURES FOR ALL TRADES AND PHASES OF THE | | | PROJECT, AND SHALL ALSO INCLUDE SITE WORK AND DESIGN | | | FEES- SECTION 109.3 WPB.THAT INCLUDES ALL OF THE TRADE | | | COSTS, | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-02-07 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2020-02-07 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2020-02-07 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2020-02-07 15:13:20 | | | | PLUMBING PROVISO | | | | | | 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR | | | THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE | | | SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2) | | | | | | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN | | | WILL SUFFICE. PER FBC PL 416.5 | | | | | | 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE | | | ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS | | | REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL | | | A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE | | | NOTE ON THE PLAN | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2020-01-28 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2020-01-27 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2020-01-28 12:23:52 | 3RD REVIEW:19120803 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: NO RESPONSE LETTER WAS PROVIDED FOR | | | PREVIOUS COMMENTS IT WAS UNCLEAR HOW ALL THE COMMENTS | | | WERE ANSWERED. | | | | | | 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR | | | THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE | | | SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2) | | | | | | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN | | | WILL SUFFICE. PER FBC PL 416.5 | | | | | | 3. PLEASE IDENTIFY THE THERMAL EXPANSION DEVICE IT CAN | | | NOT BE APPROVED UNTIL IT IS IDENTIFIED PROVIDE | | | MANUFACTURE SPECIFICATIONS FOR A VALVE OR MODEL NUMBER | | | OF A TANK. PER FBC PL 607.3 | | | | | | 4. THE EYE WASH IS NOT VENTED PLEASE PROVIDE A VENT PER | | | FBC PL 901.2.1 | | | | | | 5. SHT. P1 NOTE ON H.C. RESTROOM PLAN LAYOUT STATES | | | GRAB BARS TO BE MEASURED TO THE CENTERLINE THEY SHALL | | | BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC | | | ACC 609.4 | | | | | | 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE | | | ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS | | | REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL | | | A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE | | | NOTE ON THE PLAN | | | | | | END OF COMMENTS | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-01-13 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-01-10 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2020-01-13 09:16:30 | PLUMBING 2ND REVIEW**DENIED**19110910 | | | 1) SHT. S6 PLEASE SHOW THE MIRROR 40?MAX AS TO THE | | | REFLECTIVE SURFACE NOT THE BOTTOM EDGE OF MIRROR. | | | FBC-ACC 603.3. | | | 2) SHOW TOILET PAPER HOLD AS BEING 7?-9? FROM THE FRONT | | | EDGE OF THE TOILET. FBC-ACC 604.7 | | | 3) PLEASE PROVIDE THE GRAB BAR DETAIL MEASUREMENTS AS | | | CALLED OUT IN FBC-ACC 604.5.1, 604.5.2 | | | 4) (A) SHOW THE ADA SHOW AS A TRANSFER SHOWER NOT AS | | | ADA. THE 36? IS NOT THE MIN THIS IS AN ABSOLUTE | | | MEASUREMENT. FBC-ACC 608.2 | | | (B) THE GRAB BAR SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE NOT TO THE CENTER. FBC-ACC 609.4 | | | (C) SHOW SHOWER PAN MATERIAL BEING USED. FBC-PLB | | | 417.5.2 | | | (D) THE CONTROL WALL SHALL BE ACROSS FROM THE TRANSFER | | | SHOWER SEAT NOT ADJACENT TO THE SEAT AS SHOWN. FBC-ACC | | | 608.2.1 | | | (E) HEIGHT FOR THE SHOWER VALVE AND SHOWER HEAD/ HAND | | | HELD SHALL BE MAX 48?. FBC-ACC 608.6 | | | (F) SHOW THE PRE-PITCH OF THE SHOWER AS 2% / ?? PER | | | FOOT MIN. FBC-PLB 417.5.2 | | | 5) THE WATER HEATER RELIEF LINE SHALL DISCHARGE INTO | | | THE DRAIN PAN WITH IN THE ROOM. FBC-PLB 504.6 | | | 6) PAN DRAIN MATERIAL SHALL BE OF MATERIALS CALLED OUT | | | IN THE WATER DISTRIBUTION TABLE FBC-PLB 605.4. PVC | | | PIPING IS NOT PERMITTED. | | | 7) SHOW ALL HOT WATER PIPING AS BEING INSULATED AS | | | CALLED OUT IN FBC-ENERGY C404.4. | | | 8) PROVIDE MEANS OF THERMO EXPANSION. FBC-PLB 607.3 | | | | | | TIM HUNT | | | PLUMBING PLAN REVIEW | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | 561-248-2703 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-19 |
Time |
20:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-16 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2019-12-19 20:51:01 | PLUMBING 1ST REVIEW**DENIED**19110910 | | | | | | 1) NO GAS REVIEW PERFORMED AS GENERATOR IS REQUIRED TO | | | HAVE A SEPARATE PERMIT PACKET TO INCLUDE THE GEN, SLAB, | | | ELEC, AND GAS SUBMITTED TOGETHER. WPB AMEND 105.1 | | | 2) SHT MP-1 NOTE #1.3 CALLS OUT CONDENSATE LINE AS PVC | | | BUT NOTE 2.3 CALLS OUT COPPER. PLEASE CLARIFY 107.2.1 | | | 3) PLUMBING FLAT AND ISOMETRIC SHOWS OTHER THEN | | | BATHROOM FIXTURES DISCHARGING INTO THE BATHROOM GROUP | | | WET VENT. PLEASE SHOW THESE FIXTURES CONNECTING DOWN | | | STREAM OF THE BATHROOM GROUP WET VENT. FBC-912.1, | | | 912.1.1, 912.2.1 | | | 4) SHOW BREAK ROOM SINK DETAIL SHOWING MAX CABINET | | | HEIGHT AS 34? TO COMPLY WITH FLORIDA ACCESSIBILITY. | | | 5) PROVIDE DIMENSIONS OF ALL NEW ROOMS. FBC 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-14 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-14 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2020-01-14 08:06:10 | PRODUCT APPROVALS DUE WITH SUB PERMIT APPLICATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-18 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-18 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2019-12-18 15:37:10 | SEE BUILDING COMMENT #4 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2020-02-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-02-07 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-02-07 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-28 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-28 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2020-01-28 08:47:38 | ALL SHEETS - OK | | 2020-01-28 07:17:45 | ELECTRICAL SHEETS OK. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-13 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-13 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-17 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-17 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2019-12-19 08:02:32 | THE EOR SINCLAIR CANNOT SELF-CERTIFY HIS ELECTRONIC | | | SIGNATURE AND SEAL. THIRD PARTY CETIFICATION IS | | | REQUIRED. | | 2019-12-17 14:20:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FS471, FIRE ALARM PAGES ARE NOT DIGITALLY SIGNED. | | | EITHER PROVIDE DIGITALLY SIGNED DOCUMENTS, OR SUBMIT A | | | PAPER SIGNED, SEALED DATED ORGINAL TO THE BUILDING | | | DIVISION. A SUBMITTAL FORM WILL BE REQUIRED TO BE | | | SUBMITTED WITH THE PLANS. | | | | | | IN THE FUTURE DO NOT UPLOAD SCANNED PLANS, PLEASE | | | UPLOAD THE ORIGINAL PDF. A SCAN OF A SEAL AND SIGNATURE | | | IS NOT IN COMPLIANCE WITH FS471. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-01-28 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-01-28 |
Time |
08:08 |
Sent To |
I |
|
| Notes |
| 2020-01-28 14:29:37 | 1/28/20 PASSED. | | | | | | I SPOKE WITH THE APPLICANT AND HE CLARIFIED THAT THE | | | WORK IS INTERNAL AND NO ADDITIONS WILL BE ADDING ONTO | | | THE STRUCTURE. PARKING WILL BE A SEPERATE PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | 2020-01-28 08:08:59 | 1/28/20 FAILED. | | | | | | PLEASE ADDRESS PREVIOUS COMMENTS. | | | | | | ****** | | | | | | 1/10/20 FAILED. | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | 1. THE PROPOSED ADDITION IS ENROACHING OUTSIDE OF THE | | | PROPERTY LINES, PLEASE PROVIDE A COPY OF DEED BOOK | | | (D.B) 1052, PG. 264 SHOWN ON THE SURVEY TO PROVE THE | | | "R/W & EASMENT FOR RAILROAD SIDING" HAS BEEN REVERTED | | | BACK TO THE SUBJECT PROPERTY. | | | 2. PROVIDE THE SQUARE FOOTAGE OF THE PROPOSED ADDITION. | | | 3. BASED ON THE PROPOSED SQUARE FOOTAGE, ADDITIONAL | | | PARKING WILL BE REQUIRED FOR THE SUBJECT SITE. SHOW THE | | | AMOUNT OF REQUIRED PARKING SPACES THAT WILL NEED TO BE | | | PROVIDED BASED ON THE ADDITION. | | | | | | **THE PROPOSED PARKING LOT IMPROVEMENTS MUST BE | | | SUBMITTED AS A SEPERATE PERMIT ** | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME | | | NTS/DEVELOPMENT-SERVICES/OVERVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-01-10 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-01-10 |
Time |
15:13 |
Sent To |
I |
|
| Notes |
| 2020-01-10 15:46:37 | 1/10/20 FAILED. | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | 1. THE PROPOSED ADDITION IS ENROACHING OUTSIDE OF THE | | | PROPERTY LINES, PLEASE PROVIDE A COPY OF DEED BOOK | | | (D.B) 1052, PG. 264 SHOWN ON THE SURVEY TO PROVE THE | | | "R/W & EASMENT FOR RAILROAD SIDING" HAS BEEN REVERTED | | | BACK TO THE SUBJECT PROPERTY. | | | 2. PROVIDE THE SQUARE FOOTAGE OF THE PROPOSED ADDITION. | | | 3. BASED ON THE PROPOSED SQUARE FOOTAGE, ADDITIONAL | | | PARKING WILL BE REQUIRED FOR THE SUBJECT SITE. SHOW THE | | | AMOUNT OF REQUIRED PARKING SPACES THAT WILL NEED TO BE | | | PROVIDED BASED ON THE ADDITION. | | | | | | **THE PROPOSED PARKING LOT IMPROVEMENTS MUST BE | | | SUBMITTED AS A SEPERATE PERMIT ** | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME | | | NTS/DEVELOPMENT-SERVICES/OVERVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-01-06 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-12-20 |
Time |
15:37 |
Sent To |
I |
|
| Notes |
| 2020-01-06 08:39:38 | 01/06/2020 FAILED. | | | | | | PLEASE PROVIDE A PARKING DETAIL FOR THE PROPOSED | | | PARKING SPACES (I.E. COLOR OF STRIPES,WIDTH OF HANDICAP | | | AISLE, ETC.) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | | | 2019-12-20 15:37:40 | 12/20/19 | | | | | | WAITING FOR THE APPLICANT TO CALL BACK - NEED | | | CLARIFICATION ON THE PERMIT. | | | | | | RACHEL FALCONE |
|
|