| Plan Review Stops For Permit 19110909 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-01-10 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-01-10 |
Time |
17:19 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-12-20 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-12-20 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2019-12-20 16:44:54 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PREVIOUS COMMENTS WERE NOT ADDRESSED. | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PREFABRICATED 'AMERICAST' GENERATOR PAD AND | | | GENERATOR ANCHORING PLANS FROM 'ENGINEERING EXPRESS' | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ENGINEER | | | THAT PREPARED THE DRAWINGS. FAC 61G15-23.003 PROCEDURES | | | FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH | | | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | | ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | 2) THE GENERATOR TABLE THAT IS PROVIDED ON THE | | | GENERATOR PAD PLAN DOES NOT LIST THE KOHLER 38RCLB | | | MODEL IN THE SPECIFICATIONS THAT WERE SUBMITTED. THE | | | KOHLER 38RCL MODEL THAT IS LISTED HAS DIFFERENT | | | DIMENSIONS AND WEIGHT. SUBMIT GENERATOR SPECS. AND PAD | | | PLANS THAT MATCH. FBC 107.2.1 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-12-04 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-12-04 |
Time |
07:57 |
Sent To |
E |
|
| Notes |
| 2019-12-04 08:32:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PREFABRICATED 'AMERICAST' GENERATOR PAD AND | | | GENERATOR ANCHORING PLANS FROM 'ENGINEERING EXPRESS' | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ENGINEER | | | THAT PREPARED THE DRAWINGS. FAC 61G15-23.003 PROCEDURES | | | FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | 2) THE GENERATOR TABLE THAT IS PROVIDED ON THE | | | GENERATOR PAD PLAN DOES NOT LIST THE KOHLER 38RCLB | | | MODEL IN THE SPECIFICATIONS THAT WERE SUBMITTED. THE | | | KOHLER 38RCL MODEL THAT IS LISTED HAS DIFFERENT | | | DIMENSIONS AND WEIGHT. SUBMIT GENERATOR SPECS. AND PAD | | | PLANS THAT MATCH. FBC 107.2.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-12-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-20 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-20 |
Time |
14:33 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-04 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-04 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2019-12-13 09:32:45 | PAGE SUBMITTED BY CARPENTER ELECTRIC (RISER DIAGRAM) IS | | | TO BE SIGNED, PER FBC 107 THE PRINTED NAME AND | | | SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | | THE DESIGN IS TO BE ON THE PLAN. | | | | | | | | 2019-12-04 13:03:43 | PLANS NEED TO BE SIGNED. JLEAHY |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2019-12-24 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2019-12-24 |
Time |
14:00 |
Sent To |
I |
|
| Notes |
| 2019-12-24 14:01:28 | SEPERATE GAS PERMIT REQUIRED FOR GENERATOR |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-11-22 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-11-22 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-11-22 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2019-11-22 17:49:49 | 11/22/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | 2. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS | | | IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER | | | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION | | | ON CONSTRUCTION DOCUMENTS. | | | 3. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF | | | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH | | | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA | | | STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 | | | GENERAL. | | | 4. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC | | | SEC. 107.3.5.3 (12) RESIDENTIAL GAS | | | 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 6. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. | | | 7. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER | | | THE 2017 FBC RES. SEC. G2401.1.3. | | | 8. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 | | | FBC RES. SEC. G2419.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-01-10 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-01-07 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2020-01-08 11:01:36 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-12-24 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-17 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2019-12-18 14:10:22 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-04 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-19 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2019-11-20 13:44:34 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-12-19 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-12-19 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-12-19 |
Time |
11:05 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-11-21 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-11-21 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2019-11-21 15:01:27 | 11/21/19 FAILED. | | | | | | CLEARLY IDENTIFY THE LOCATION OF THE PROPOSED GENERATOR | | | WITH ITS SETBACKS TO THE PROPERTY LINES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: (561) 822-1442 | | | E-MAIL: [email protected] | | | |
|
|