| 2019-11-21 17:00:17 | 11/21/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR GAS TANKLESS EQUIPMENT |
| | TO VERIFY COMPLIANCE WITH 2014 FBC FG SEC.305.1. |
| | 2. GAS APPLIANCES SUBMITTED ON ORIGINAL PLANS ARE |
| | DIFFERENT FROM THE GAS ISOMETRIC SUBMITTED (GRID, |
| | FRYER, RANGE AND CANDY STOVE) AND ON ISO YOU HAVE (CHAR |
| | BROILER, FRYER AND RANGE) PLEASE CLARIFY AND MAKE NOTES |
| | ON WHICH ONES ARE BEING USED BY IDENTIFYING THE MODEL |
| | AND BTU'S PER THE 2014 FBC FG SECS. 402.2 AND 301.3. |
| | THERE IS ONE COPY OF A GRILL SUBMITTED IS IT A MISTAKE |
| | OR DOES IT BELONG IN THE PACKAGE BECAUSE YOU WILL NEED |
| | ONE MORE COPY (SMG-48). |
| | 3. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO |
| | 10.5" WC ON THE TANKLESS. PLEASE SUBMIT THE |
| | MANUFACTURER'S SPECIFICATIONS FOR THE PRESSURE |
| | REGULATORS AND MARK ON ISOMETRIC. REGULATORS INSTALLED |
| | ON THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR |
| | OUTDOOR INSTALLATION PER THE 2014 FBC RES. SEC. 410.1. |
| | 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471. |
| | 5. PLEASE SHOW THE EMERGENCY SHUTOUT OFF VALVE ON THE |
| | SYSTEM AND MARK VALVE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.1 GENERAL. THE EMERGENCY HOOD SHUT DOWN |
| | SHUTOFF VALVE SHALL BE BELOW THE CEILING. THE MANUAL |
| | SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE DOWNSTREAM |
| | OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA 96-08. |
| | 6. SHOW DRIP LEGS AND UNIONS ON EQUIPMENT INSTALLED PER |
| | THE 2014 FBC FG 408.2. |
| | 7. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH |
| | THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. |
| | 8. THE SUBMITTED COMBUSTION AIR CALCULATIONS ARE IN |
| | SQUARE FEET AND SHOULD BE IN CUBIC FEET. WHERE IS |
| | COMBUSTION AIR PROVIDED BY THE BUILDING'S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR PER THE 2014 FBC FG SEC. |
| | 304.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR |
| | SYSTEM. |
| | 9. MASTER PLANS SHOW THE COMBUSTION AIR REFERRING TO |
| | SEC 304.9 MECHANICAL COMBUSTION AIR SUPPLY, WHICH |
| | SUPPLIED FROM THE OUTDOORS AT A RATE NOT LESS THAN 0.35 |
| | CUBIC FEET PER MINUTE PER 1,000 BTU'S. THERE IS NO |
| | MECHANICAL SYSTEM IN THE MAIN PLANS TO VERIFY THIS |
| | METHOD. ON THE ISOMETRIC DRAWING YOU WILL NEED TO NOTE |
| | WHICH METHOD YOU ARE USING, IF USING STANDARD METHOD |
| | WITH 50 CUBIC FEET PER 1000 BTU'S SUPPLY THE TOTAL AIR |
| | AVAILABLE IN CUBIC FT AS REQUESTED ABOVE. ON THE MAIN |
| | SET OF PLANS SHEET 3.1 HAS A NOTE OF THE DOOR BEING 12" |
| | AND AN OPENING ABOVE AND BELOW TO THE DINNING ARE, |
| | PLEASE CLARIFY IF YOU WILL BE USING AIR AND IF THERE IS |
| | NO OBSTRUCTION FOR AIR FLOW PER THE 2014 FBC FG SEC. |
| | 304. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |