Plan Review Details - Permit 19110902
Plan Review Stops For Permit 19110902
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-01-08 Cont ID  
Sent By lcrespo Date 2020-01-08 Time 16:38 Rev Time 0.00
Received By lcrespo Date 2020-01-08 Time 16:38 Sent To  
Notes
2020-01-08 16:39:4201/08/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By lcrespo Date 2019-11-21 Time 16:59 Rev Time 0.00
Received By lcrespo Date 2019-11-21 Time 16:59 Sent To  
Notes
2019-11-21 17:00:1711/21/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR GAS TANKLESS EQUIPMENT
 TO VERIFY COMPLIANCE WITH 2014 FBC FG SEC.305.1.
 2. GAS APPLIANCES SUBMITTED ON ORIGINAL PLANS ARE
 DIFFERENT FROM THE GAS ISOMETRIC SUBMITTED (GRID,
 FRYER, RANGE AND CANDY STOVE) AND ON ISO YOU HAVE (CHAR
 BROILER, FRYER AND RANGE) PLEASE CLARIFY AND MAKE NOTES
 ON WHICH ONES ARE BEING USED BY IDENTIFYING THE MODEL
 AND BTU'S PER THE 2014 FBC FG SECS. 402.2 AND 301.3.
 THERE IS ONE COPY OF A GRILL SUBMITTED IS IT A MISTAKE
 OR DOES IT BELONG IN THE PACKAGE BECAUSE YOU WILL NEED
 ONE MORE COPY (SMG-48).
 3. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO
 10.5" WC ON THE TANKLESS. PLEASE SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS AND MARK ON ISOMETRIC. REGULATORS INSTALLED
 ON THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION PER THE 2014 FBC RES. SEC. 410.1.
 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471.
 5. PLEASE SHOW THE EMERGENCY SHUTOUT OFF VALVE ON THE
 SYSTEM AND MARK VALVE PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.1 GENERAL. THE EMERGENCY HOOD SHUT DOWN
 SHUTOFF VALVE SHALL BE BELOW THE CEILING. THE MANUAL
 SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE DOWNSTREAM
 OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA 96-08.
 6. SHOW DRIP LEGS AND UNIONS ON EQUIPMENT INSTALLED PER
 THE 2014 FBC FG 408.2.
 7. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH
 THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.
 8. THE SUBMITTED COMBUSTION AIR CALCULATIONS ARE IN
 SQUARE FEET AND SHOULD BE IN CUBIC FEET. WHERE IS
 COMBUSTION AIR PROVIDED BY THE BUILDING'S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR PER THE 2014 FBC FG SEC.
 304.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
 9. MASTER PLANS SHOW THE COMBUSTION AIR REFERRING TO
 SEC 304.9 MECHANICAL COMBUSTION AIR SUPPLY, WHICH
 SUPPLIED FROM THE OUTDOORS AT A RATE NOT LESS THAN 0.35
 CUBIC FEET PER MINUTE PER 1,000 BTU'S. THERE IS NO
 MECHANICAL SYSTEM IN THE MAIN PLANS TO VERIFY THIS
 METHOD. ON THE ISOMETRIC DRAWING YOU WILL NEED TO NOTE
 WHICH METHOD YOU ARE USING, IF USING STANDARD METHOD
 WITH 50 CUBIC FEET PER 1000 BTU'S SUPPLY THE TOTAL AIR
 AVAILABLE IN CUBIC FT AS REQUESTED ABOVE. ON THE MAIN
 SET OF PLANS SHEET 3.1 HAS A NOTE OF THE DOOR BEING 12"
 AND AN OPENING ABOVE AND BELOW TO THE DINNING ARE,
 PLEASE CLARIFY IF YOU WILL BE USING AIR AND IF THERE IS
 NO OBSTRUCTION FOR AIR FLOW PER THE 2014 FBC FG SEC.
 304.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-08 Cont ID  
Sent By lcrespo Date 2020-01-08 Time 16:39 Rev Time 0.00
Received By lcrespo Date 2020-01-07 Time 10:45 Sent To  
Notes
2020-01-08 10:45:27RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-21 Cont ID  
Sent By lcrespo Date 2019-11-21 Time 17:02 Rev Time 0.00
Received By lcrespo Date 2019-11-19 Time 13:36 Sent To  
Notes
2019-11-20 13:36:56PLUMB <5K


Account Summary | Usage Policy | Privacy Policy