Plan Review Details - Permit 19110754
Plan Review Stops For Permit 19110754
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-04-11 Cont ID  
Sent By pvalenti Date 2020-04-11 Time 15:52 Rev Time 0.00
Received By pvalenti Date 2020-04-11 Time 15:51 Sent To  
Notes
2020-04-13 06:37:29PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 APPROVED WITH PROVISO:
  
 THE STRAPPING OF ROOFING RAFTERS SHALL COMPLY WITH
 DESIGNER OF RECORD'S REVISED DETAILS.
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-03-31 Cont ID  
Sent By rmcdouga Date 2020-03-31 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2020-03-31 Time 14:24 Sent To I
Notes
2020-03-31 14:25:05PLAN
 REVIEW COMMENTS
  
 FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A103, THE ROOF FRAMING PLAN SHOWS A 4'
 CANTILEVER OVERHANG. A TYPICAL CANTILEVER REQUIRES 2/3
 RDS OF THE BEAM TO BE FIXED INSIDE THE BUILDING AND 1/3
 RD EXTENDED OUTSIDE. THIS IS NOT THE CASE WITH YOUR
 DESIGN. PROVIDE AN ENGINEER'S ANALYSIS ALONG WITH
 DETAILED CONSTRUCTION DRAWINGS FOR THIS CANTILEVER
 DESIGN. FBC 107.2.1.2
  
 2) THE WIND DESIGN INFORMATION ON SHEET A101 SPECIFIES
 ASCE 7 -16. THIS EDITION HAS NOT BEEN ADOPTED IN THE
 2017 FBC. THE CURRENTLY REFERENCED VERSION IS ASCE 7
 -10. FBC-R CHAPTER 46.
  
 3) THE PRODUCT APPROVAL FOR THE FLAT ROOF, FL16709-R6
 FOR THE CERTAINTEED FLINTLASTIC MODIFIED BITUMEN ROOF
 SYSTEM HAS NOT BEEN MARKUP TO INDICATED WHICH OF THE
 SYSTEMS WILL BE USED. SYSTEMS W-4 & W-5 ON PAGES 11 AND
 13 ARE THE ONLY TWO FOR NON-INSULATED ROOFS AS SHOWN ON
 THE PLANS. W-4 IS FOR SELF ADHERED AND W-5 IS FOR HOT
 ASPHALT APPLIED OR TORCH DOWN. MARK THE APPROPRIATE
 ITEMS ON THE PRODUCT APPROVAL. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-20 Cont ID  
Sent By rmcphers Date 2020-03-20 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2020-03-20 Time 13:15 Sent To  
Notes
2020-03-20 13:19:19ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PRODUCT APPROVAL PROVIDED IS FOR AN UNDERLAYMENT FOR
 SHINGLES. THE ROOF DECK IS A FLAT DECK CANNOT USE
 SHINGLES.
 2) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 ROOFING PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE
 USED. IF NEEDED ---- PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE HIGHER DESIGN PRESSURES THAN THE
 PRODUCT APPROVAL MAY ALLOW. (SEE PRODUCT APPROVAL
 NOTES)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-13 Cont ID  
Sent By rmcphers Date 2020-03-12 Time 16:14 Rev Time 0.00
Received By rmcphers Date 2020-03-11 Time 16:49 Sent To  
Notes
2020-03-12 16:23:29ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 ROOFING PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE
 USED. IF NEEDED ---- PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE HIGHER DESIGN PRESSURES THAN THE
 PRODUCT APPROVAL MAY ALLOW. (SEE PRODUCT APPROVAL
 NOTES)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By dbattles Date 2019-12-17 Time 15:25 Rev Time 0.00
Received By dbattles Date 2019-12-17 Time 10:07 Sent To  
Notes
2019-12-17 15:25:54BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19110754
 REVIEWED: DECEMBER 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502. UNALTERED PORTIONS OF
 THE EXISTING BUILDING OR BUILDING SUPPLY SYSTEM SHALL
 NOT BE REQUIRED TO COMPLY WITH THIS CODE.
 -PLEASE PROVIDE DOCUMENTATION OF HOW YOU ARE COMPLYING
 WITH ENERGY CODE. EITHER PRESCRIPTIVE(502.1.1),
 SIMULATED(R502.1.2) OR ENERGY RATING INDEX(502.2.1.3)
  
 2) 107.5.3 FBC[AMENDED]PLEASE ADD ROOF SLOPE TO PLANS.
 PROVIDE PRODUCT APPROVALS FOR FLAT ROOF, OR INDICATE
 THAT THEY WILL BE PROVIDED WITH THE SUB-PERMIT
 APPLICATION.
  
 3) 403.4 FBC[R] EXTERIOR FOOTINGS SHALL BE PLACED NOT
 LESS THAN 12 INCHES BELOW THE UNDISTURBED GROUND
 SURFACE. WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL
 ALSO CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
  
 4) 806.3 FBC[R] VENT AND INSULATION CLEARANCE. WHERE
 EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION SHALL
 NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A 1-INCH
 (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE INSULATION
 AND THE ROOF SHEATHING AND AT THE LOCATION OF THE VENT.
 -SECTION A/3 SHOWS 2X8 RAFTERS WITH R30 BATT. PLEASE
 REVIEW HOW R-30 BATT WOULD FIT IN THE CAVITY AND LEAVE
 1 INCH MINIMUM AT SHEATHING FOR VENTING. ALSO, NOTE
 SAYS VENT TO MATCH EXISTING. SINCE EACH RAFTER CREATES
 ISOLATED SPACE PLEASE CALL FOR A CONTINUOUS SOFFIT
 VENT.
  
 IF AN UNVENTED SPACE IS USED DUE TO CONSTRAINTS, THAN
 PLEASE REVIEW SECTION 806.5 FOR AIR PERMEABLE
 INSULATION NEEDING RIDGID BOARD INSULATION ABOVE
 SHEATHING.
  
 5) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE
 INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL
 ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE
 INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR
 CONDENSATION CONTROL.
  
 IF SPRAY INSULATION IS APPLIED TO ROOF DECK THAN NO
 VENTING OR INSULATION FOR CONDENSATION CONTROL IS
 NEEDED, BUT PROVIDE CUT SHEET FOR ICYNENE(ICC-ES REPORT
 OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH THICKNESS
 NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX.
  
 6) 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
 -ADD NOTE TO PROVIDE TERMITE PROTECTION.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-05 Cont ID  
Sent By jpearson Date 2020-03-05 Time 15:15 Rev Time 0.00
Received By jpearson Date 2020-03-05 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-16 Cont ID  
Sent By jpearson Date 2019-12-16 Time 13:31 Rev Time 0.00
Received By jpearson Date 2019-12-12 Time 07:14 Sent To  
Notes
2019-12-16 13:31:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE BASED
 ON FORMULA PROVIDED IN FBC RESIDENTIAL, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. IF NONE
 ARE EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS.
 FBC RE R314.3, R315.1; WPB FBC 107.2.1
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 5. SHOW ON PLAN LOCATION OF NEW AC. PROVIDE GFCI
 PROTECTED RECEPTACLE OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-13 Cont ID  
Sent By pvalenti Date 2020-04-13 Time 08:05 Rev Time 0.00
Received By pvalenti Date 2020-04-11 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-20 Cont ID  
Sent By rmcphers Date 2020-03-20 Time 13:19 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 15:02 Sent To  
Notes
2020-03-20 13:19:57PLANS TAKEN TO PERMIT LIBRARY
2020-03-18 15:02:18RESUB ROUTED TO RMCPHERSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-12 Cont ID  
Sent By rmcphers Date 2020-03-12 Time 16:23 Rev Time 0.00
Received By rmcphers Date 2020-02-10 Time 14:18 Sent To  
Notes
2020-03-12 16:25:07PLANS TAKEN TO PERMIT LIBRARY
2020-02-11 14:18:26R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-12-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-15 Time 15:09 Sent To  
Notes
2019-11-18 15:09:23R35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-04-16 Cont ID  
Sent By pvalenti Date 2020-04-16 Time 14:46 Rev Time 0.00
Received By pvalenti Date 2020-04-16 Time 14:46 Sent To  
Notes
2020-04-16 14:49:34PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEES REVIEW APPROVED:
  
 MU-2020-012857-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By pvalenti Date 2020-04-13 Time 08:01 Rev Time 0.00
Received By pvalenti Date 2020-04-13 Time 08:01 Sent To  
Notes
2020-04-13 08:01:58PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By dbattles Date 2019-12-17 Time 10:43 Rev Time 0.00
Received By dbattles Date 2019-12-17 Time 10:43 Sent To  
Notes
2019-12-17 10:43:36109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-19 Cont ID  
Sent By ccole Date 2020-02-19 Time 08:28 Rev Time 0.00
Received By ccole Date 2020-02-19 Time 07:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-19 Cont ID  
Sent By ccole Date 2019-12-19 Time 15:22 Rev Time 0.00
Received By ccole Date 2019-12-19 Time 15:20 Sent To I
Notes
2019-12-19 15:42:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110754
 12/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TABLE R402B ON PAGE 2 OF THE ENERGY FORM R402-2017
 HAS NOT BEEN FILLED OUT. THE LANGUAGE ON THE FORM
 STATES "TO COMPLY, A BUILDING MUST MEET OR EXCEED ALL
 OF THE ENERGY EFFICIENCY REQUIREMENTS ON TABLE R402A
 AND ALL APPLICABLE MANDATORY REQUIREMENTS SUMMARIZED IN
 TABLE R402B OF THIS FORM." IN TABLE R402A PLEASE
 PROVIDE THE INSTALLED VALUES FOR THE WINDOWS, THE DOOR,
 THE WALL AND AND CEILING INSULATIONS, THE DUCT R-VALUE,
 AND THE AC SYSTEM, MANDATORY REQUIREMENTS CHECKLLIST-
 TABLE R402B WAS NOT PROVIDED WITH THE FORM SUBMITTAL.
  
 2) THE AC CALCULATIONS ARE INDICATING THE FRONT DOOR IS
 FACING EAST, HOWEVER ACCORDING TO PALM BEACH COUNTY
 RECORDS THE FRONT DOOR IS FACING NORTH- PLEASE REVISE
 THE CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-12-03 Cont ID  
Sent By lcrespo Date 2019-12-03 Time 15:19 Rev Time 0.00
Received By lcrespo Date 2019-12-03 Time 15:19 Sent To  
Notes
2019-12-03 15:21:22NO PLUMBING IN THE NEW AREA OF CONSTRUCTION,

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-04-11 Cont ID  
Sent By pvalenti Date 2020-04-11 Time 15:52 Rev Time 0.00
Received By pvalenti Date 2020-04-11 Time 15:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-03-20 Cont ID  
Sent By rmcphers Date 2020-03-20 Time 13:20 Rev Time 0.00
Received By rmcphers Date 2020-03-20 Time 13:20 Sent To  
Notes
2020-03-20 13:20:39SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By rmcphers Date 2020-03-12 Time 16:28 Rev Time 0.00
Received By rmcphers Date 2020-03-12 Time 16:28 Sent To  
Notes
2020-03-12 16:28:37SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By llouie Date 2020-02-14 Time   Rev Time 0.00
Received By llouie Date 2020-02-14 Time   Sent To  
Notes
2020-02-14 15:40:05* NEW FAMILY ROOM.
  
 * SCOPE OF WORK DOES NOT EXCEED 50% VALUE OF EXISTING
 STRUCTURE (PAPA).
  
 * PALM CLUB RPD - VILLAGE 3; REFERENCE ORDINANCE NO.
 1881-85.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-11-25 Cont ID  
Sent By llouie Date 2019-11-25 Time   Rev Time  
Received By llouie Date 2019-11-25 Time   Sent To  
Notes
2019-11-25 16:00:19** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS
 REQUIRED.
  
 2.) CLEARLY SHOW THE EXTENT OF THE PROPOSED ENCLOSURE
 IN THE SITE PLAN.
  
 3.) WHAT IS THE DISTANCE MEASURED FROM THE PROPOSED
 ENCLOSURE TO THE ADJACENT BUILDING ON THE EAST SIDE? A
 MINIMUM DISTANCE SEPARATION BETWEEN BUILDINGS IS 15 FT.
  
  
 NOTES:
  
 * SCOPE OF WORK DOES NOT EXCEED 50% VALUE OF THE
 EXISTING STRUCTURE, PER PAPA.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (PALM CLUB - VILLAGE 3)
  
 * REFERENCE: ORDINANCE NO. 1881-85 (REAR: 15 FT. AND
 BETWEEN BUILDINGS: 15 FT.)
  