| Plan Review Stops For Permit 19110717 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-01-15 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-15 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-15 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-20 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-20 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-01-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-22 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-22 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-12-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-12 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-12 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-01-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-01-14 |
Time |
15:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-11-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-11-18 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2019-11-18 11:09:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE REVISION APPLICATION INDICATED "ELIMINATE FIRE | | | PUMP AND FIRE PUMP ROOM" | | | | | | THERE IS VIRTUALLY NO INFORMATION REGARDING THE FIRE | | | PUMP NOR FIRE PUUMP ROOM AON THE SUBMITTED PLAN SHEETS. | | | THERE IS SITE WORK, ROOF DECK, HVAC, ELECTRICAL, DOOR | | | SCHEDULE, ETC, HOWEVER, NO FIRE PUMP/ROOM. | | | | | | PLEASE REVIEW AND CORRECT OR CLARIFY. | | | | | | | | | 2) THE ARE NO HYDRAULIC CLACULATIONS OR OTHER SIGNED | | | AND SEALED ENGINEERENING REVIEW DOCUMENTATION | | | INDICATING THAT A FIRE PUMP IS NOT REQUIRED. | | | | | | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILED INFORMATION | | | SIGNED AND SEALED BY A ENGINEER FOR OFFICIAL REVIEW. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-01-28 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-01-10 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-18 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-15 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-21 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-21 |
Time |
17:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-10 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-10 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2019-12-10 11:00:21 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19110717 | | | 12/10/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 20177 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMPLY WITH FIRE REVIEW COMMENTS AND ALSO PROVIDE A | | | NARRATIVE FROM THE ENGINEER OF RECORD TO CLARIFY WHY | | | THE FIRE PUMP IS BEING ELIMINATED- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-01-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2020-01-25 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2020-01-25 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-12-11 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-11 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2019-12-11 06:47:41 | PLUMBING 1ST REVIEW**DENIED**19110717 | | | | | | REVISION IS FOR THE REMOVAL OF THE FIRE PUMP AND FIRE | | | PUMP ROOM BUT IT APPEARS MORE IS BEING REVISED THEN | | | CLAIMED. PROVIDE A COMPLETE NARRATIVE OF WHAT IS | | | CHANGING AND REMOVE ANY SHEETS OR DETAILS ON SHEETS | | | THAT DO NOT PERTAIN TO THE REVISION. ANY CHANGES TO | | | SHEETS THAT BEAR THE SIGN AND SEAL OF THE ENGINEER OF | | | RECORD SHALL ONLY BE CHANGED BY HIM/ HER. FBC 107.3.5, | | | F.S 471 | | | | | | | | | | | | TIM HUNT | | | | | | | | | PLUMBING PLANS EXAMINER | | | | | | | | | CITY OF WEST PALM BEACH | | | | | | | | | [email protected] | | | | | | | | | 561-248-2703 | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-01-15 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-15 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-15 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-20 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-20 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-01-28 |
Time |
13:08 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2020-01-28 |
Time |
12:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-12-17 |
Time |
14:49 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2019-12-17 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2019-12-17 14:49:03 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSE. | | | | | | 1) THE REVISION IS FOR THE REMOVAL OF THE FIRE PUMP AND | | | FIRE PUMP ROOM, YET A SHEET HAS BEEN INSERTED FOR THE | | | DECK FRAMING PLAN, THE DECK, THE DECK DETAILS AND THE | | | DECK SECTION. THESE ITEMS ARE NOT PART OF THE BUILDING, | | | SO THEY NEED TO BE SUBMITTED AS A SEPARATE DECK PERMIT, | | | WHICH ACCURATELY SHOWS THE VALUE OF THE DECK. NOTE: | | | ZONING MADE PROVIDED THE COMMENT THAT THE DECK REQUIRES | | | A SEPARATE PERMIT AS PART OF THE BUILDING REVIEW. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | | | | |
|
|