Plan Review Details - Permit 19110717
Plan Review Stops For Permit 19110717
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-15 Cont ID  
Sent By dbattles Date 2020-01-15 Time 08:59 Rev Time 0.00
Received By dbattles Date 2020-01-15 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-11-20 Cont ID  
Sent By dbattles Date 2019-11-20 Time 13:31 Rev Time 0.00
Received By dbattles Date 2019-11-20 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-22 Cont ID  
Sent By jleahy Date 2020-01-22 Time 08:18 Rev Time 0.00
Received By jleahy Date 2020-01-22 Time 08:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-12 Cont ID  
Sent By jleahy Date 2019-12-12 Time 13:27 Rev Time 0.00
Received By jleahy Date 2019-12-12 Time 13:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By pleduc Date 2020-01-14 Time   Rev Time 0.00
Received By pleduc Date 2020-01-14 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By pleduc Date 2019-11-18 Time   Rev Time 0.00
Received By pleduc Date 2019-11-18 Time 11:02 Sent To  
Notes
2019-11-18 11:09:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE REVISION APPLICATION INDICATED "ELIMINATE FIRE
 PUMP AND FIRE PUMP ROOM"
  
 THERE IS VIRTUALLY NO INFORMATION REGARDING THE FIRE
 PUMP NOR FIRE PUUMP ROOM AON THE SUBMITTED PLAN SHEETS.
 THERE IS SITE WORK, ROOF DECK, HVAC, ELECTRICAL, DOOR
 SCHEDULE, ETC, HOWEVER, NO FIRE PUMP/ROOM.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
 2) THE ARE NO HYDRAULIC CLACULATIONS OR OTHER SIGNED
 AND SEALED ENGINEERENING REVIEW DOCUMENTATION
 INDICATING THAT A FIRE PUMP IS NOT REQUIRED.
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILED INFORMATION
 SIGNED AND SEALED BY A ENGINEER FOR OFFICIAL REVIEW.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-28 Cont ID  
Sent By lmarchan Date 2020-01-28 Time 13:11 Rev Time 0.00
Received By lmarchan Date 2020-01-10 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-18 Cont ID  
Sent By shill Date 2019-12-18 Time 10:52 Rev Time 0.00
Received By shill Date 2019-11-15 Time 13:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-01-21 Cont ID  
Sent By ccole Date 2020-01-21 Time 17:16 Rev Time 0.00
Received By ccole Date 2020-01-21 Time 17:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-10 Cont ID  
Sent By ccole Date 2019-12-10 Time 10:57 Rev Time 0.00
Received By ccole Date 2019-12-10 Time 10:09 Sent To  
Notes
2019-12-10 11:00:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110717
 12/10/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 20177
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMPLY WITH FIRE REVIEW COMMENTS AND ALSO PROVIDE A
 NARRATIVE FROM THE ENGINEER OF RECORD TO CLARIFY WHY
 THE FIRE PUMP IS BEING ELIMINATED- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-25 Cont ID  
Sent By gjohnson Date 2020-01-25 Time 11:09 Rev Time 0.00
Received By gjohnson Date 2020-01-25 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-11 Cont ID  
Sent By gjohnson Date 2019-12-11 Time 06:47 Rev Time 0.00
Received By shill Date 2019-12-11 Time 06:47 Sent To  
Notes
2019-12-11 06:47:41PLUMBING 1ST REVIEW**DENIED**19110717
  
 REVISION IS FOR THE REMOVAL OF THE FIRE PUMP AND FIRE
 PUMP ROOM BUT IT APPEARS MORE IS BEING REVISED THEN
 CLAIMED. PROVIDE A COMPLETE NARRATIVE OF WHAT IS
 CHANGING AND REMOVE ANY SHEETS OR DETAILS ON SHEETS
 THAT DO NOT PERTAIN TO THE REVISION. ANY CHANGES TO
 SHEETS THAT BEAR THE SIGN AND SEAL OF THE ENGINEER OF
 RECORD SHALL ONLY BE CHANGED BY HIM/ HER. FBC 107.3.5,
 F.S 471
  
  
  
 TIM HUNT
  
  
 PLUMBING PLANS EXAMINER
  
  
 CITY OF WEST PALM BEACH
  
  
 [email protected]
  
  
 561-248-2703
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-01-15 Cont ID  
Sent By dbattles Date 2020-01-15 Time 09:04 Rev Time 0.00
Received By dbattles Date 2020-01-15 Time 09:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-11-20 Cont ID  
Sent By dbattles Date 2019-11-20 Time 13:31 Rev Time 0.00
Received By dbattles Date 2019-11-20 Time 13:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-28 Cont ID  
Sent By eschneid Date 2020-01-28 Time 13:08 Rev Time 0.25
Received By eschneid Date 2020-01-28 Time 12:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By eschneid Date 2019-12-17 Time 14:49 Rev Time 0.50
Received By eschneid Date 2019-12-17 Time 13:45 Sent To  
Notes
2019-12-17 14:49:03FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE.
  
 1) THE REVISION IS FOR THE REMOVAL OF THE FIRE PUMP AND
 FIRE PUMP ROOM, YET A SHEET HAS BEEN INSERTED FOR THE
 DECK FRAMING PLAN, THE DECK, THE DECK DETAILS AND THE
 DECK SECTION. THESE ITEMS ARE NOT PART OF THE BUILDING,
 SO THEY NEED TO BE SUBMITTED AS A SEPARATE DECK PERMIT,
 WHICH ACCURATELY SHOWS THE VALUE OF THE DECK. NOTE:
 ZONING MADE PROVIDED THE COMMENT THAT THE DECK REQUIRES
 A SEPARATE PERMIT AS PART OF THE BUILDING REVIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  
  