Plan Review Details - Permit 19110674
Plan Review Stops For Permit 19110674
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-03 Cont ID  
Sent By jpearson Date 2019-12-03 Time 08:04 Rev Time 0.00
Received By jpearson Date 2019-12-03 Time 08:03 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By jpearson Date 2019-11-18 Time 09:21 Rev Time 0.00
Received By jpearson Date 2019-11-18 Time 09:21 Sent To  
Notes
2019-11-18 09:21:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE PLANS SUBMITTED FOR REVISION DO NOT EXIST IN THE
 CURENT APPROVED DRAWINGS ON FILE. THE ENGINEER OF
 RECORD (EOR), SHOWN AS L J SAMADI PE, MUST PROVIDE ANY
 REVISED DOCUMENTS WITH THE PROPER SIGNATURE AND SEAL
 PER FLORIDA STATUTES. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2.1; FS 471
 2. THE LOAD CALCULATION PROVIDED DOES NOT MATCH THE
 ORIGINAL PROVIDED BY THE EOR. IF THE LOADS HAVE
 CHANGED, PROVIDE DOCUMENTATION TO SUPPORT THESE
 CHANGES. THE LOAD CALCULATION PROVIDED IS NOT CODE
 COMPLIANT. ALSO, A LOAD CALCULATION FOR THE ENTIRE
 SERVICE IS REQUIRED, IN ADDTION TO THE ONE PROVIDED FOR
 THE RESIDENTIAL UNIT, TO CONFIRM THE CAPACITY IS
 SUFFICIENT. PROVIDE CORRECTION. NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-27 Time 14:35 Sent To  
Notes
2019-12-02 14:35:14RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-14 Time 15:57 Sent To  
Notes
2019-11-15 15:58:06REVISION ROUTED TO JPEARSON


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved