Plan Review Details - Permit 19110659
Plan Review Stops For Permit 19110659
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2020-01-03 Time 06:49 Sent To  
Notes
2020-01-03 13:35:52NEW BUILDING 2019. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By dbattles Date 2020-02-04 Time 12:23 Rev Time 0.00
Received By dbattles Date 2020-02-03 Time 14:55 Sent To  
Notes
2020-02-04 12:43:15DEFERRED SUBMITTALS:
 SHEET LS-1-1
  
 PROVIDE PRODUCT APPROVALS FOR WNDOWS, DOORS AND NANA
 WALLS AND LOUVERS.
  
 SEPARATE PERMIT FOR AWNINGS/CANOPIES, FIRE ALARM, FIRE
 SPRINKLER, LOW VOLTAGE AND SECURITY SYSTEM REQUI

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2020-01-03 Time 06:49 Sent To  
Notes
2020-01-03 13:33:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110659
 ADD: 201 N. FLAGLER DR. 1ST FLOOR INT. BUILD-OUT
 RESTAURANT/ A-2
 CONT: RCC ASSOCIATES INC.
 TEL: 954-429-3700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 02/2020
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS. SHEET LS.1.0 IS NOT THE CODE
 DATA AND GENERAL NOTES SHEET BUT IS THE SHEET INDEX,
 PLEASE CORRECT THE DISCREPANCY IN PLANS. W 2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATIVE CODE.
  
 2) SHEET LS-1.1LIFE SAFETY PLAN- RESTAURANT:
 2A) UNDER THE HEADINGS OF APPLICABLE CODES, AND
 CLASSIFICATION OF WORK BOTH HEADINGS INDICATE CODE
 COMPLIANCE WITH THE 2017 EXISTING BUILDING CODE SECTION
 504- ALTERATIONS LEVEL 2. PLEASE REFER TO THE 2017
 FBC-EXISTING BUILDING CODE SECTION 101.4.1. BUILDINGS
 NOT PREVIOUSLY OCCUPIED (SHELL BUILDINGS).
 A BUILDING OR PORTION OF A BUILDING THAT HAS NOT BEEN
 PREVIOUSLY OCCUPIED OR USED FOR ITS INTENDED PURPOSE IN
 ACCORDANCE WITH THE LAWS IN EXISTENCE AT THE TIME OF
 ITS COMPLETION SHALL BE PERMITTED TO COMPLY WITH THE
 PROVISIONS OF THE LAWS IN EXISTENCE AT THE TIME OF ITS
 ORIGINAL PERMIT UNLESS SUCH PERMIT HAS EXPIRED.
 SUBSEQUENT PERMITS SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE FOR NEW CONSTRUCTION.
 PLEASE CORRECT CODE COMPLIANCE STATEMENTS.
  
 2B) PLEASE REVIEW THE TOTAL OCCUPANT LOADS BETWEEN THE
 EGRESS CALCULATIONS AND THE PLUMBING FIXTURE
 REQUIREMENTS. IT WOULD APPEAR THE 268 OCCUPANTS UNDER
 EGRESS HAS BEEN FLIPPED TO 286 OCCUPANTS UNDER THE
 PLUMBING FIXTURE REQUIREMENTS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2C) THE LIFE SAFETY PLAN DOES NOT SHOW A CUMULATIVE
 OCCUPANT LOAD AS THEY PROCEED OUT OF THE BUILDING AND
 EITHER DOWN THE STAIRS AND OR RAMP TO THE PUBLIC WAY.
  
 2C)(1)2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS
 OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 2C)(2)THE LIFE SAFETY PLAN FAILS TO SHOW COMPLIANCE
 WITH THE 2017 FBC-B SECTION 1028.5 ACCESS TO A PUBLIC
 WAY.
  
 2D) THE LIFE SAFETY PLAN INDICATES AS WELL AS A-1.1.1
 EXTERIOR DOOR 110B AS A 36 INCH OPENING, THE PLANS DO
 NOT INDICATE THAT THE DOOR IS EXISTING OR NOT AND THE
 DOOR IS NOT ON THE DOOR SCHEDULE FOUND ON SHEET
 A-7.1.1. THIS DOOR IS DESIGNATED AS AN EXIT DOOR
 REQUIRING PANIC OR FIRE EXIT HARDWARE IN COMPLIANCE
 WITH 2017 FBC-B SECTION 1010.10. ADDITIONAL INFORMATION
 IS REQUIRED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2E) SHEET A-1.1.1 INDICATES DOOR IN QUESTION AS 101C,
 THE DOOR SCHEDULE INDICATES THIS DOOR AS A 3 FOOT WIDE
 DOOR. THE LIFE SAFETY SHEET INDICATES THIS DOOR AS AN
 EGRESS DOOR AND STATES ON THE LIFE SAFETY PLAN AS A 32
 INCH OPENING. SCALING THE DOOR ON SHEET A-1.1.2 THE
 DOOR IS OVERALL 33 INCHES. THIS DOOR DOES NOT SHOW
 COMPLIANCE WITH 1010.1.1 FOR EGRESS DOORS. A 32 INCH
 CLEAR OPENING IS REQUIRED, MEASURED FROM THE FACE OF
 THE DOOR PERPENDICULAR TO THE OPPOSING DOOR STOP AT A
 90 DEGREE ANGLE.
  
 2F) SHEET A-1.1.2 THE 1ST FLOOR DIMENSION PLAN WITH THE
 DOOR 101C IN QUESTION AS TO THE SIZE, DRAWN CURRENTLY
 AS 32 TO 33 INCHES JAMB TO JAMB. PLEASE ALSO PROVIDE
 THE MEASUREMENT FROM THE SWING EDGE OF THE BAR TO THE
 ADJACENT BAR AND COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION ACCESS. CODE 404.2.4
 MANEUVERING CLEARANCES. DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE FOR
 SIDE CLEARANCE. SEE FIGURE 404.2.4.1(A) 18 INCHES
 MINIMUM PULL SIDE.
  
 2G) THE LIFE SAFETY SHEET LS-1.1 DOES NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE;
 2G)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2G(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2G)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2G)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 2G)(5) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2G)(6) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2H) THE LIFE SAFETY SHEET DOES NOT SHOW ANY BARS AS
 ACCESSIBLE. SHEET A-1.1.1 DOES HAVE A NOTE OF AN
 ACCESSIBLE BAR AREA, TO SEE DETAIL 3/ A9.3.1. THIS
 DETAIL DOES SHOW AN AREA OF DROPPED SECTION OF THE BAR
 FOR AN ACCESSIBLE ELEMENT OF THE BAR WITH THE USE OF A
 COUNTERBALANCE CORP. SERV-A-SYSTEM. PLEASE SHOW
 DOCUMENTATION THAT THIS SYSTEM HAS APPROVAL WITH THE
 AMERICAN DISABILITIES ACT OR HAS GONE BEFORE THE
 FLORIDA ACCESSIBILITY BOARD AND RECEIVED A WAIVER.
 PLEASE NOTE WITHIN THE 2017 FBC-ACCESSIBILITY CODE
 SECTION 902 DINING SURFACES HAS NO GREY BOXES (FLORIDA
 SPECIFIC LAW) WHICH MEANS THE FLORIDA BOARD FOR
 ACCESSIBILITY PROBABLY WILL NOT APPROVE A WAIVER. HAS
 THE U S DEPARTMENT OF JUSTICE GIVEN AN APPROVAL THAT
 THE PROPOSED SYSTEM WILL MEET THE REQUIREMENTS FOR
 ACCESSIBILITY AND MEET EQUIVALENT FACILITATION AS
 REQUIRED BY SECTION 103 OF THE 2017 FLORIDA
 ACCESSIBILITY CODE?
  
 3) SHEET S4.0.0 INDICATES TYPICAL HSS 6X6 STRUCTURAL
 STEEL AND FIELD WELDING. PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 4) NO ACTION NEEDED. THE DESIGNER OF RECORD HAS ELECTED
 TO HAVE DEFERRED SUBMITTALS FOR THE FOLLOWING;
 EXTERIOR DOORS, WINDOWS, NANA WALL SYSTEMS AND LOUVERS.
 AWNINGS/ CANOPIES AND ASSOCIATED CONNECTIONS & EXTERIOR
 DECORATIVE ELEMENTS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-30 Cont ID  
Sent By jpearson Date 2020-01-30 Time 09:23 Rev Time 0.00
Received By jpearson Date 2020-01-30 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-22 Cont ID  
Sent By jpearson Date 2019-12-22 Time 14:52 Rev Time 0.00
Received By jpearson Date 2019-12-22 Time 14:52 Sent To  
Notes
2019-12-22 14:52:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTION FOR RECEPTACLE OUTLETS
 LOCATED OUTDOORS. NEC 210.8(B)(4)
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-24 Cont ID  
Sent By pleduc Date 2020-01-24 Time   Rev Time 0.00
Received By pleduc Date 2020-01-24 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-12-03 Cont ID  
Sent By pleduc Date 2019-12-03 Time   Rev Time 0.00
Received By pleduc Date 2019-11-26 Time 16:28 Sent To  
Notes
2019-12-03 16:27:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.1 - THERE IS AN INDICATION OF AN EXIT
 LEADING THRU THE KITCHEN TO A FENCED IN AREA THAT IS
 NOT A PUBLIC WAY.
  
 THERE IS A SLIDING GATE; HOWEVER, THERE IS NO EXIT SIGN
 AT THE GATE OF EXIT HARDWARE MEETING THE REQUIRMENT OF
 NFPA 101, CH 7 MEANS OF EGRESS.
  
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.14 SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION
 OR
 FOLDING DOOR ASSEMBLIES. SPECIAL-PURPOSE HORIZONTALLY
 SLIDING
 ACCORDION OR FOLDING DOOR ASSEMBLIES SHALL BE PERMITTED
 IN MEANS
 OF EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE DOOR LEAF IS READILY OPERABLE FROM EITHER SIDE
 WITHOUT
 SPECIAL KNOWLEDGE OR EFFORT.
 (2) THE FORCE THAT, WHEN APPLIED TO THE OPERATING
 DEVICE IN THE
 DIRECTION OF EGRESS, IS REQUIRED TO OPERATE THE DOOR
 LEAF IS NOT
 MORE THAN 15 LBF (67 N).
 (3) THE FORCE REQUIRED TO OPERATE THE DOOR LEAF IN THE
 DIRECTION OF
 TRAVEL IS NOT MORE THAN 30 LBF (133 N) TO SET THE LEAF
 IN
 MOTION AND IS NOT MORE THAN 15 LBF (67 N) TO CLOSE THE
 LEAF OR
 OPEN IT TO THE MINIMUM REQUIRED WIDTH.
 (4) THE DOOR LEAF IS OPERABLE USING A FORCE OF NOT MORE
 THAN 50
 LBF (222 N) WHEN A FORCE OF 250 LBF (1100 N) IS APPLIED
 PERPENDICULARLY TO THE LEAF ADJACENT TO THE OPERATING
 DEVICE,
 UNLESS THE DOOR OPENING IS AN EXISTING SPECIAL-PURPOSE
 HORIZONTAL-SLIDING ACCORDION OR FOLDING EXIT ACCESS
 DOOR
 ASSEMBLY SERVING AN AREA WITH AN OCCUPANT LOAD OF FEWER
 THAN 50.
 (5) THE DOOR ASSEMBLY COMPLIES WITH THE FIRE PROTECTION
 RATING,
 IF REQUIRED, AND, WHERE RATED, IS SELF-CLOSING OR
 AUTOMATIC CLOSING
 BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH
 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80,
 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES.
 (6) THE DOOR, IF POWER OPERATED, SHALL BE CAPABLE OF
 BEING
 OPERATED MANUALLY IN THE EVENT OF POWER FAILURE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 CODE.
  
  
 2) SHEET LS 1.1 - THERE ARE INDICATION OF A OUTDOOR
 SEATING PLAN; HOWEVER, THERE APPEARS TO BE ENCROACHMENT
 INTO THE EGRESS PATH LEADING TO EXITS.
  
 PER NFPA 101, CH 12, NEW ASSEMLY OCCUOPANCIES
  
 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES.
 12.2.5.7.1 THE REQUIRED CLEAR WIDTH OF AN AISLE
 ACCESSWAY SHALL BE
 NOT LESS THAN 12 IN. (305 MM) WHERE MEASURED IN
 ACCORDANCE WITH
 12.2.5.7.3 AND SHALL BE INCREASED AS A FUNCTION OF
 LENGTH IN
 ACCORDANCE WITH 12.2.5.7.4, UNLESS OTHERWISE PERMITTED
 BY
 12.2.5.7.2.
 12.2.5.7.2* IF USED BY NOT MORE THAN FOUR PERSONS, NO
 MINIMUM
 CLEAR WIDTH SHALL BE REQUIRED FOR THE PORTION OF AN
 AISLE ACCESSWAY
 HAVING A LENGTH NOT EXCEEDING 6 FT (1830 MM) AND
 LOCATED FARTHEST
 FROM AN AISLE.
 12.2.5.7.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE ACCESSWAY OR AISLE, THE MEASUREMENT OF
 REQUIRED CLEAR
 WIDTH OF THE AISLE ACCESSWAY OR AISLE SHALL BE MADE TO
 A LINE 19 IN.
 (485 MM), MEASURED PERPENDICULARLY TO THE EDGE OF THE
 TABLE,
 AWAY FROM THE EDGE OF SAID TABLE.
 12.2.5.7.4* THE MINIMUM REQUIRED CLEAR WIDTH OF AN
 AISLE
 ACCESSWAY, MEASURED IN ACCORDANCE WITH 12.2.5.4.8 AND
 12.2.5.7.3,
 SHALL BE INCREASED BEYOND THE 12 IN. (305 MM)
 REQUIREMENT OF
 12.2.5.7.1 BY ? IN. (13 MM) FOR EACH ADDITIONAL 12 IN.
 (305 MM)
 OR FRACTION THEREOF BEYOND 12 FT (3660 MM) OF AISLE
 ACCESSWAY
 LENGTH, WHERE MEASURED FROM THE CENTER OF THE SEAT
 FARTHEST FROM
 AN AISLE.
 12.2.5.7.5 THE PATH OF TRAVEL ALONG THE AISLE ACCESSWAY
 SHALL NOT
 EXCEED 36 FT (11 M) FROM ANY SEAT TO THE CLOSEST AISLE
 OR EGRESS
 DOORWAY.
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
 12.2.5.8.1* AISLES THAT CONTAIN STEPS OR THAT ARE
 RAMPED, SUCH AS
 AISLES SERVING DINNER THEATER?STYLE CONFIGURATIONS,
 SHALL COMPLY
 WITH THE REQUIREMENTS OF 12.2.5.6.
 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT
 TABLES SHALL BE
 NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN
 OCCUPANT LOAD
 EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN
 OCCUPANT
 LOAD OF 50 OR FEWER.
 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF
 THE AISLE SHALL
 BE MADE TO A LINE 19 IN. (485 MM), MEASURED
 PERPENDICULARLY TO
 THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID
 TABLE.
 12.2.5.9 APPROVAL OF LAYOUTS.
 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF
 FURNISHINGS OR
 EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE
 BUILDING
 OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE
 WITH THE PROVISIONS OF 12.2.5.
 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY
 ACCEPTABLE
 ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS
 MET:
 (1) THE PLANS ARE REVISED.
 (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED.
 (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE
 APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT
 LOAD IS
 NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED.
  
 PLEASE PROVIDE DETAILED DIEMSIONS OF ALONG THE EGRESS
 PATH.
  
  
 3)
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By gjohnson Date 2020-02-05 Time 14:44 Rev Time 0.00
Received By gjohnson Date 2020-02-05 Time 14:44 Sent To  
Notes
2020-02-05 15:05:31PROVISO:
  
 GAS COMMENTS: COMPLY PRIOR TO FINAL INSPECTION
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDE FOR THE TORCH LITES AND THE OUTDOOR FIREPLACE.
 PER WPB AMEND TO FBC 107.2.1
  
 2. THE TIKI TORCHES SHALL COMPLY WITH FBC FG 628.3
  
 3. PROVIDE MANUFACTURES SPECIFICATIONS FOR THE FLU
 PIPING FOR THE PIZZA OVEN. PER WPB AMEND TO FBC 107.2.1
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL
 GAS CODE SEC. 502 THRU 505.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-12-23 Cont ID  
Sent By gjohnson Date 2019-12-23 Time 13:01 Rev Time 0.00
Received By gjohnson Date 2019-12-20 Time 17:34 Sent To  
Notes
2019-12-23 13:01:583RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1.PLEASE LABEL THE TYPE OF PIPE ON THE GAS ISOMETRIC.
 PER WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2017 FUEL GAS CODE SEC. 304
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS SEC.
 402.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-02-07 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-06 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-05 Cont ID  
Sent By gjohnson Date 2020-02-05 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2020-01-22 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-15 Time 16:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-11 Cont ID  
Sent By lmarchan Date 2020-02-11 Time 16:48 Rev Time 0.00
Received By lmarchan Date 2020-02-11 Time 10:30 Sent To  
Notes
2020-02-11 16:48:34NO FEES DUE - FEES WERE PAID UNDER PERMIT 17110857
 (MU2018-024209)
  
2020-02-11 10:30:522/11/20 SENT EMAIL TO IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jwitmer Date 2020-01-03 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2020-01-03 Time 06:49 Sent To  
Notes
2020-01-03 13:34:32PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-02-07 Cont ID  
Sent By ccole Date 2020-02-07 Time 10:02 Rev Time 0.00
Received By ccole Date 2020-02-07 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-01-31 Cont ID  
Sent By ccole Date 2020-01-31 Time 11:37 Rev Time 0.00
Received By ccole Date 2020-01-30 Time 11:25 Sent To  
Notes
2020-01-31 11:38:172ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19110659
 1/31/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.1.3 & M1.1.3: THE EXHAUST SHAFT CANNOT
 SERVE MULTIPLE EXHAUST DUCTS, PIPING, AND WIRING-
 SECTION 506.3.11 FBC M. IF THE INTENTION IS FOR ALL
 EXHAUST DUCT TO BE WRAPPED IN 2-HR FIRE RATED DUCT WRAP
 ENCLOSURES, PLEASE PLACE A NOTE ON THE PLAN
 ACCORDINGLY. PLEASE NOTE HOWEVER THAT THE PIZZA OVEN
 AND SOLID FUEL APPLIANCE MANUFACTURER'S MAY RECOMMEND
 UL LISTED AND LABELED EXHAUST DUCTS THAT MAY NOT BE
 RATED AS DUCT ENCLOSURES, AND MAY ALSO PROHIBIT DUCT
 WRAPPING- SEE SECTIONS 506.3.1.1 & 506.3.11.3. IT IS
 IMPORTANT TO GET THESE DETAILS STRAIGHT ON THE MAIN
 PERMIT PLANS NOW PRIOR TO REVIEW OF THE SEPARATE PERMIT
 PLANS FOR THE KITCHEN EXHAUST SYSTEMS.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SOLID
 FUEL COOKING APPLIANCE- SECTION 917.1 FBC M. UL 2162
 LISTING AND LABELING REQUIRED.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OUTDOOR
 TIKI TORCHES, AND THE GAS FIREPLACE- SECTIONS 626 AND
 605 FBC FG. THESE SUBMITTALS WERE LEFT OUT OF THE
 SUBMITTAL PACKAGE.
  
 4) SHEETS M1.1.1, M1.1.2, M1.1.3: PLEASE ADD THE SOLID
 FUEL FIRED COOKING APPLIANCE TO THE LIST OF SEPARATELY
 PERMITTED ITEMS, AND INCLUDE COMBUSTION AIR
 CALCULATIONS- SECTION 701.1 FBC M.
  
 5) SHEET M1.1.3: PLEASE PLACE A TOP INDICATING THAT ALL
 ROOFTOP MECHANICAL EQUIPMENT AND APPLIANCES SHALL BE
 INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDED
 CLEARANCES, AND TO ALLOW ACCESS FOR SERVICE AND
 REPLACEMENT.
  
 A) RELOCATE FAN 2-B TO PROVIDE CLEARANCE TO THE RACK
 AND CU'S- SECTIONS 306.1 AND 506.3.13.3 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By ccole Date 2019-12-24 Time 12:09 Rev Time 0.00
Received By ccole Date 2019-12-24 Time 12:09 Sent To  
Notes
2019-12-24 12:17:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110659
 12/24/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS, PIZZA OVENS, FIRE SUPPRESSION SYSTEMS,
 AND THE WALK-IN COOLER AND FREEZER. PLEASE PLACE A BOLD
 NOTE ON THE PLAN- SECTION 107.2.1 WPB.
  
 2) PLEASE INDICATE HOW COMBUSTION AIR WILL BE SUPPLIED
 TO THE GAS AND SOLID FUEL FIRED COOKING APPLIANCES, AND
 THE PIZZA OVENS AND PROVIDE CALCULATIONS- SEE SECTION
 304.1 FBC FG. PLEASE NOTE THAT PRODUCT SPECIFICATIONS
 FOR ALL THE APPLIANCES SHALL BE SUBMITTED IN THE SECOND
 REVIEW CYCLE OR MAY BE DEFERRED BY REQUEST.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES- TABLE 403.3.1.1 FBC M.
  
 4) PROVIDE ENGINEERING FOR IINSTALLATION OF ALL THE
 ROOFTOP MECHANICAL EQUIPMENT, APPLIANCES, AND DUCTWORK-
 SECTION 301.15 FBC M.
  
 5) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER
 HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC EC.
 SUBMIT A COMMISSIONING PLAN AS OUTLINED IN SECTION
 C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2-
 C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT
 FINAL INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By gjohnson Date 2020-02-05 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2020-02-04 Time 17:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-23 Cont ID  
Sent By gjohnson Date 2019-12-23 Time 12:48 Rev Time 0.00
Received By gjohnson Date 2019-12-20 Time 17:33 Sent To  
Notes
2019-12-23 12:49:161ST REVIEW 19110659
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC PL = FLORIDA BUILDING CODE PLUMBING 2017 6TH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P1.2.1 PLEASE EXPAND AND SEPARATE THE WATER AND
 GAS ISOMETRICS THEY ARE TO COMPACT TO DETERMINE CODE
 COMPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. P1.2.2 PLEASE EXPAND THE SANITARY ISOMETRIC
 DRAWING SOME OF THE PIPES APPEAR TO BE CONNECTING WHERE
 THEY CROSS. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE BACK FLOW DEVISES ON ALL APPLIANCES
 CONNECTED TO THE WATER SYSTEM SUCH AS WATER FILTERS,
 ICE MACHINES COFFEE AND TEA MAKERS . PER FBC PL 608.3,
 608.16.1,608.16.10
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-02-07 Cont ID  
Sent By ccole Date 2020-02-07 Time 10:02 Rev Time 0.00
Received By ccole Date 2020-02-07 Time 10:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By dbattles Date 2020-02-04 Time 12:38 Rev Time 0.00
Received By dbattles Date 2020-02-04 Time 12:38 Sent To  
Notes
2020-02-04 12:41:24OK-ALL SHEETS FOR 2ND REVIEW.
  
 ANY ADDITIONAL SHEETS PROVIDED WILL NEED TO BE
 DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By shill Date 2020-01-06 Time 11:52 Rev Time 0.00
Received By shill Date 2020-01-06 Time 11:52 Sent To  
Notes
2020-01-03 13:36:53ARCHITECTURAL AND STRUCTURAL SHEETS, SIGNATURE OK. JW
 01/02/2020
2019-12-24 12:46:44MECHANICAL PLANS, ENERGY AND AC CALCULATIONS GOOD.
2019-12-22 14:54:29ELECTRICAL SHEETS OK.