| Plan Review Stops For Permit 19110550 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-23 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-23 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-17 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-17 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2019-12-17 17:46:33 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | PLEASE PROVIDE A SCHEDULE ON THE PLANS TO IDENTIFY WHAT | | | THE LETTER DESIGNATIONS ARE (TS, WP, T ARE NOT DEFINED | | | ON PLAN). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-12-04 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-04 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-04 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2019-12-04 09:13:31 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1 PROVIDE A SCHEDULE TO INDICATE WHAT | | | SYMBOLS (TS,WP,P1 THROUGH P6) ON PLAN ARE IDENTIFYING | | | AND IF THERE ARE ANY ASSOCIATED STRUCTURAL CONNECTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-11-18 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-11-18 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2019-11-18 17:20:47 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC 107.2.1, PROVIDE SIGNED/SEALED DETAIL FOR THE LIGHT | | | POST BASES INCLUDING FOOTING (DIMENSIONS, CONCRETE, | | | REINFORCEMENT AND CONNECTION DETAILS). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-23 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-23 |
Time |
10:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-17 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-17 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2019-12-17 12:10:56 | I DON'T HAVE TIME TO LOOK THROUGH ALL THE FIXTURES THAT | | | ON THIS JOB TO FIND PARKING LOT LIGHTING. | | | | | | PLEASE SUBMIT ONLY THE LIGHTS THAT PERTAIN TO THIS SITE | | | LIGHTING JOB. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-03 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-03 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2019-12-03 12:30:03 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SUBMIT CUTSHEETS FOR THE DIFFERENT FIXTURES AND | | | POLES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-11-18 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-18 |
Time |
16:09 |
Sent To |
B |
|
| Notes |
| 2019-11-18 16:11:22 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE FOR WORK LOOKS LOW, PLEASE SUBMIT A SIGNED | | | CONTRACT WITH THE OWNER. | | | | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 2) SUBMIT CUTSHEETS FOR THE DIFFERENT FIXTURES AND | | | POLES. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-23 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-19 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2019-12-20 13:45:10 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-17 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-10 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2019-12-11 15:06:02 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-04 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-04 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-11-27 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2019-12-02 15:03:55 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-11-18 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-12 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2019-11-13 14:04:05 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-11-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-11-15 |
Time |
|
Sent To |
E |
|
| Notes |
| 2019-11-15 10:58:23 | ZONING APPROVED WITH THE FOLLOWING PROVISO: | | | | | | 1.) ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE | | | GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE | | | AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT | | | RESIDENCES OR PUBLIC THOROUGHFARES. | | | | | | (REFERENCE: PB 997C - GEORGIAN GARDENS APARTMENTS MINOR | | | PD AMENDMENT (AS-BUILTS)) |
|
|