Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-12-23 Cont ID  
Sent By pvalenti Date 2019-12-23 Time 14:27 Rev Time 0.00
Received By pvalenti Date 2019-12-23 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-12-17 Cont ID  
Sent By pvalenti Date 2019-12-17 Time 17:41 Rev Time 0.00
Received By pvalenti Date 2019-12-17 Time 17:41 Sent To  
Notes
2019-12-17 17:46:33***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 PLEASE PROVIDE A SCHEDULE ON THE PLANS TO IDENTIFY WHAT
 THE LETTER DESIGNATIONS ARE (TS, WP, T ARE NOT DEFINED
 ON PLAN).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-04 Cont ID  
Sent By pvalenti Date 2019-12-04 Time 09:03 Rev Time 0.00
Received By pvalenti Date 2019-12-04 Time 09:03 Sent To  
Notes
2019-12-04 09:13:31***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 PROVIDE A SCHEDULE TO INDICATE WHAT
 SYMBOLS (TS,WP,P1 THROUGH P6) ON PLAN ARE IDENTIFYING
 AND IF THERE ARE ANY ASSOCIATED STRUCTURAL CONNECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By pvalenti Date 2019-11-18 Time 17:16 Rev Time 0.00
Received By pvalenti Date 2019-11-18 Time 17:16 Sent To  
Notes
2019-11-18 17:20:47***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC 107.2.1, PROVIDE SIGNED/SEALED DETAIL FOR THE LIGHT
 POST BASES INCLUDING FOOTING (DIMENSIONS, CONCRETE,
 REINFORCEMENT AND CONNECTION DETAILS).

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-12-23 Cont ID  
Sent By jleahy Date 2019-12-23 Time 10:49 Rev Time 0.00
Received By jleahy Date 2019-12-23 Time 10:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-12-17 Cont ID  
Sent By jleahy Date 2019-12-17 Time 12:09 Rev Time 0.00
Received By jleahy Date 2019-12-17 Time 12:09 Sent To  
Notes
2019-12-17 12:10:56I DON'T HAVE TIME TO LOOK THROUGH ALL THE FIXTURES THAT
 ON THIS JOB TO FIND PARKING LOT LIGHTING.
  
 PLEASE SUBMIT ONLY THE LIGHTS THAT PERTAIN TO THIS SITE
 LIGHTING JOB.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-03 Cont ID  
Sent By jleahy Date 2019-12-03 Time 12:24 Rev Time 0.00
Received By jleahy Date 2019-12-03 Time 12:24 Sent To  
Notes
2019-12-03 12:30:03FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SUBMIT CUTSHEETS FOR THE DIFFERENT FIXTURES AND
 POLES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 16:09 Rev Time 0.00
Received By jleahy Date 2019-11-18 Time 16:09 Sent To B
Notes
2019-11-18 16:11:22FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR WORK LOOKS LOW, PLEASE SUBMIT A SIGNED
 CONTRACT WITH THE OWNER.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SUBMIT CUTSHEETS FOR THE DIFFERENT FIXTURES AND
 POLES.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-12-23 Cont ID  
Sent By pvalenti Date 2019-12-23 Time 14:27 Rev Time 0.00
Received By pvalenti Date 2019-12-19 Time 13:44 Sent To  
Notes
2019-12-20 13:45:10RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-17 Cont ID  
Sent By pvalenti Date 2019-12-17 Time 17:46 Rev Time 0.00
Received By pvalenti Date 2019-12-10 Time 15:05 Sent To  
Notes
2019-12-11 15:06:02RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-04 Cont ID  
Sent By pvalenti Date 2019-12-04 Time 09:13 Rev Time 0.00
Received By pvalenti Date 2019-11-27 Time 15:03 Sent To  
Notes
2019-12-02 15:03:55RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 16:09 Rev Time 0.00
Received By jleahy Date 2019-11-12 Time 14:03 Sent To  
Notes
2019-11-13 14:04:05ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-15 Cont ID  
Sent By llouie Date 2019-11-15 Time   Rev Time 0.00
Received By llouie Date 2019-11-15 Time   Sent To E
Notes
2019-11-15 10:58:23ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES OR PUBLIC THOROUGHFARES.
  
 (REFERENCE: PB 997C - GEORGIAN GARDENS APARTMENTS MINOR
 PD AMENDMENT (AS-BUILTS))